StateNSW
Date of Visit04/07/2022
Technician's Namecon karakiozis
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number66869
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWtempe

Location NameTempe
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB1 1 Y 103 111 P
2 Y 12 12 P
3 Y 274 219 P
4 Y 20 20 P
5 Y 6 9 P
6 Y 9 9 P
7 Y 6 7 P
8 Y 60 60 P
9 Y 10 8 P
10 Y 8 8 P
11 Y 32 32 P
12 Y 18 17 P
13 Y 249 415 P
14 Y 10 10 P
15 Y 109 109 P
16 Y 8 8 P
17 Y 11 11 P
18 Y 6 6 P
19 Y 54 11 P
20 Y 169 168 P
21 Y 13 11 P
22 Y 35 30 P
23 Y 101 118 P
26 Y 63 47 P
DB2 1 Y 39 35 P
5 Y 29 29 P
6 Y 29 29 P
7 Y 19 20 P
8 Y 19 24 P
31 Y 16 17 P
DB-2A 17 Y 27 26 P
19 Y 29 30 P
21 Y 26 26 P
23 Y 27 28 P
27 Y 14 14 P
29 Y 15 15 P
31 Y 17 18 P
33 Y 17 17 P
35 Y 17 16 P
37 Y 16 15 P
39 Y 19 18 P
41 Y 14 13 P
43 Y 20 18 P
45 Y 18 18 P
47 Y 14 21 P
49 Y 93 29 F THE CURRENT RCBO WAS INCORRECT TYPE AND WAS SWITCHING ON AND OFF IN THE WRONG DIRECTION Y
51 Y 14 15 P
53 Y 14 14 P
55 Y 19 19 P
56 Y 18 19 P
54 Y 16 16 P
52 Y 16 15 P
50 Y 16 16 P
48 Y 16 16 P
46 Y 18 18 P
44 Y 15 15 P
42 Y 14 17 P
40 Y 18 18 P
38 Y 18 18 P
36 Y 18 18 P
34 Y 21 26 P
32 Y 15 15 P
30 Y 16 15 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB2A EM1 R Y Y Y P
EM2 R Y Y Y P
EM3 R Y Y Y P
EM4 R Y Y Y P
EM5 R Y Y Y P
EM6 R Y Y Y P
EM7 R Y Y Y P
EM8 R Y Y Y P
EM9 R Y Y Y P
EM10 R Y Y Y P
EM11 R Y Y Y P
EM12 R Y Y Y P
EM13 R Y Y Y P
EM14 S Y N Y F BATTERY Y N
EM15 S Y Y Y P
EM16 S Y Y Y P
EM17 S Y N Y F BATTERY Y N
EM18 S Y Y Y P
EM19 S Y Y Y P
EM20 S Y Y Y P
EM21 S Y Y Y P
EM22 S Y Y Y P
EM23 S Y Y Y P
EM24 S Y Y Y P
EM25 S Y Y Y P
EM26 S Y N Y F BATTERY Y N
EM27 S Y Y Y P
EM28 S Y Y Y P
EM29 S Y Y Y P
EM30 S Y N Y F BATTERY Y N
EM31 S Y Y Y P
EM32 S Y N Y F BATTERY Y N
EM33 S Y Y Y P
EM34 S Y Y Y P
EM35 S Y N Y F BATTERY Y N
EM36 S Y Y Y P
EM37 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB2A-CB42 EX1 Y Y Y P
EX2 Y Y Y P
EX3 Y Y Y P
EX4 Y Y Y P
EX5 Y Y Y P
EX6 Y Y Y P
EX7 Y Y Y P
EX8 Y Y Y P
EX9 Y Y Y P
EX10 Y F Y F BATTERY Y N
EX11 Y Y Y P
EX12 Y Y Y P
EX13 Y Y Y P
EX14 Y Y Y P
EX15 Y Y Y P
EX16 Y Y Y P
EX17 Y Y Y P
EX18 Y Y Y P
EX19 Y Y Y P
EX20 Y Y Y P
EX21 Y Y Y P
EX22 Y Y Y P
EX23 Y Y Y P
EX24 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
LED High Bays 150W Y
LED Downlight 210mm 31W S9075DP WH Y
Ledline 4ft 40W SLD4000CW Y
LED Strip Display Signs DC24V Y
LED Downlight 11W S9071CP WH Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
SM EMERGENCY FITTINGS AROUND STORE 6 EMERGENCY FITTINGS FAILED. Y N N RETURNED TO SITE AND REPLACED WITH NEW.
BAR FRIDGES SHOP FLOOR 2 TWO LED SIGNS ARE FAULTY AND NEED REPLACING. N/A N/A N/A NEED TO SPEAK TO THE SIGN CONTRACTOR OR REECE.
EXIT LIGHT #10 1 FAILED 90 MIN TEST Y N N RETURNED TO SITE AND REPLACED WITH NEW.
EXIT LIGHT BOH 1 FALLEN FROM CEILING Y N N RE-SECURED WITH JACK CHAIN & CABLE TIES
EMERGENCY LIGHTING PLAN SITE FOLDER 1 NOT ACCURATE Y N N UPDATED PLAN AND LEFT COPY IN SITE FOLDER
SWITCHBOARDS DB1,DB2 & DB2A 3 WE WILL NEED TO AUDIT SWITCHBOARD LEGENDS AND FLOOR CIRCUITS. AS THEY DO NOT MATCH UP TO CURRENT LABELS N N N ADDED TO FORTNIGHTLY REPAIRS LIST
SONY TV WALL BAY DISPLAY DISCONNECTED DUE TO WATER LEAK 1 SONY TV WALL BAY. WATER LEAK. ISOLATED CIRCUIT. Y N N RETURNED TO SITE AND RECONNECTED
RCBO BOH MSB 1 INCORRECT TYPE Y N N REPLACED WITH CORRECT RCBO
Site Status SelectorStore now fully compliant
Next Test Due in 6 months03/01/2023