State | NSW |
---|
Date of Visit | 18/07/2022 |
---|
Technician's Name | Con Karakiozis |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 66872 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in NSW | castle_hill |
---|
|
|
---|
Location Name | Castle Hill |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
DB1 |
25 |
Y |
24 |
23 |
P |
|
|
DBU2 |
21 |
Y |
19 |
19 |
P |
|
|
|
8 |
Y |
23 |
14 |
P |
|
|
|
10 |
Y |
18 |
19 |
P |
|
|
|
14 |
Y |
17 |
19 |
P |
|
|
|
20 |
Y |
16 |
17 |
P |
|
|
DBU3A |
17 |
Y |
19 |
19 |
P |
|
|
DBU3B |
3 |
Y |
10 |
19 |
P |
|
|
|
19 |
Y |
66 |
14 |
P |
|
|
|
21 |
Y |
10 |
15 |
P |
|
|
|
23 |
Y |
10 |
17 |
P |
|
|
|
18 |
Y |
11 |
16 |
P |
|
|
DB5A |
1 |
Y |
15 |
24 |
P |
|
|
|
2 |
Y |
8 |
13 |
P |
|
|
|
3 |
Y |
11 |
18 |
P |
|
|
|
4 |
Y |
14 |
23 |
P |
|
|
|
5 |
Y |
9 |
18 |
P |
|
|
|
7 |
Y |
5 |
12 |
P |
|
|
|
8 |
Y |
6 |
12 |
P |
|
|
|
9 |
Y |
6 |
12 |
P |
|
|
DB24 |
4 |
Y |
25 |
16 |
P |
|
|
|
8 |
Y |
32 |
23 |
P |
|
|
|
16 |
Y |
49 |
39 |
P |
|
|
|
18 |
Y |
28 |
20 |
P |
|
|
|
24 |
Y |
25 |
19 |
P |
|
|
DB05 |
1 |
Y |
41 |
77 |
P |
|
|
|
2 |
Y |
62 |
62 |
P |
|
|
|
3 |
Y |
59 |
66 |
P |
|
|
|
4 |
Y |
87 |
83 |
P |
|
|
|
5 |
Y |
56 |
43 |
P |
|
|
|
6 |
Y |
109 |
89 |
P |
|
|
|
7 |
Y |
39 |
39 |
P |
|
|
|
8 |
Y |
40 |
64 |
P |
|
|
|
9 |
Y |
72 |
99 |
P |
|
|
|
10 |
Y |
146 |
73 |
P |
|
|
|
11 |
Y |
84 |
96 |
P |
|
|
|
12 |
Y |
83 |
83 |
P |
|
|
|
13 |
Y |
83 |
83 |
P |
|
|
|
14 |
Y |
96 |
95 |
P |
|
|
|
15 |
Y |
119 |
113 |
P |
|
|
|
16 |
Y |
89 |
102 |
P |
|
|
|
17 |
Y |
83 |
79 |
P |
|
|
|
18 |
Y |
89 |
109 |
P |
|
|
|
27 |
Y |
41 |
38 |
P |
|
|
|
28 |
Y |
79 |
44 |
P |
|
|
|
29 |
Y |
50 |
50 |
P |
|
|
|
30 |
Y |
50 |
50 |
P |
|
|
|
31 |
Y |
39 |
39 |
P |
|
|
|
33 |
Y |
31 |
31 |
P |
|
|
|
34 |
Y |
42 |
41 |
P |
|
|
|
35 |
Y |
100 |
96 |
P |
|
|
|
36 |
Y |
60 |
60 |
P |
|
|
|
37 |
Y |
47 |
56 |
P |
|
|
|
38 |
Y |
35 |
45 |
P |
|
|
|
39 |
Y |
8 |
17 |
P |
|
|
|
40 |
Y |
28 |
18 |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB4 & DB01 |
EM1 |
R |
Y |
Y |
Y |
P |
|
|
|
|
EM2 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM3 |
R |
Y |
Y |
Y |
P |
|
|
|
|
EM4 |
R |
Y |
N |
Y |
F |
FAILED 90 MIN TEST |
Y |
N |
|
EM5 |
R |
Y |
Y |
Y |
P |
|
|
|
|
EM6 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM7 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM8 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM9 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM10 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM11 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM12 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM13 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM14 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM15 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM16 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM17 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM18 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM19 |
R |
Y |
Y |
Y |
P |
|
|
|
|
EM20 |
R |
Y |
Y |
Y |
P |
|
|
|
|
EM21 |
R |
Y |
Y |
Y |
P |
|
|
|
|
EM22 |
R |
Y |
Y |
Y |
P |
|
|
|
|
EM23 |
R |
Y |
N |
Y |
F |
FAILED 90 MIN TEST |
Y |
N |
|
EM24 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM25 |
R |
Y |
Y |
Y |
P |
|
|
|
|
EM26 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM27 |
S |
Y |
N |
Y |
F |
FAILED 90 MIN TEST |
Y |
N |
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB04 & DB01 |
EX1 |
Y |
Y |
Y |
P |
|
|
|
|
EX2 |
Y |
Y |
Y |
P |
|
|
|
|
EX3 |
Y |
Y |
Y |
P |
|
|
|
|
EX4 |
Y |
Y |
Y |
P |
|
|
|
|
EX5 |
Y |
Y |
Y |
P |
|
|
|
|
EX6 |
Y |
Y |
Y |
P |
|
|
|
|
EX7 |
Y |
Y |
Y |
P |
|
|
|
|
EX8 |
Y |
Y |
Y |
P |
|
|
|
|
EX9 |
Y |
Y |
Y |
P |
|
|
|
|
EX10 |
Y |
Y |
Y |
P |
|
|
|
|
EX11 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | No |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
Fluoro High-bays 200W |
Y |
LED 4ft Fluoro 20W |
Y |
2ft Single Fluoro 840 |
Y |
4ft Single Fluoro 840 |
Y |
4ft Twin Fluoro 840 |
Y |
4ft Twin LED Fluoro 18W |
Y |
4ft Single LED Fluoro 18W |
Y |
Shop Light Rectangle 38W |
Y |
LED Downlight 9W |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
SWITCHBOARDS |
DB1,DBU2,DBU3A,DBU3B,DB23 |
5 |
REQUIRE UPGRADING |
N |
N |
N/A |
ADDED TO FORTNIGHTLY REPAIRS LIST (FNE 24-07-22) |
SWITCHBOARD LEGENDS |
DB1,DBU2,DBU3A,DBU3B,DB24 |
5 |
NOT ACCURATE |
N |
N |
N/A |
TO BE UPDATED DURING UPCOMING RELAY WORKS. |
SWITCHBOARD LEGENDS |
DB5A,DB05 |
2 |
NOT ACCURATE |
N |
N |
N/A |
TO BE COMPLETED WITH WORKS ON APPROVED QUOTE # 64765 |
RECESSED EMERGENCY LIGHT |
EM #4, EM #23 |
2 |
FAILED 90 MIN TEST |
Y |
N |
N |
REPLACED WITH NEW. |
SURFACE MOUNT EMERGENCY LIGHT |
EM#27 |
1 |
FAILED 90 MIN TEST |
Y |
N |
N |
REPLACED WITH NEW. |
|
---|
Site Status Selector | Completed but with repairs required |
---|
Next Test Due in 6 months | 18/01/2023 |
---|
| |
---|
| |