State | NSW |
---|
Date of Visit | 22/07/2022 |
---|
Technician's Name | con karakiozis |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 66874 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in NSW | blacktown |
---|
|
|
---|
Location Name | Blacktown |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
DB1 |
17 |
Y |
19 |
19 |
P |
|
|
|
19 |
Y |
19 |
19 |
P |
|
|
|
21 |
Y |
19 |
19 |
P |
|
|
|
23 |
Y |
18 |
19 |
P |
|
|
|
25 |
Y |
19 |
19 |
P |
|
|
|
27 |
Y |
22 |
27 |
P |
|
|
|
29 |
Y |
19 |
19 |
P |
|
|
|
18 |
Y |
18 |
19 |
P |
|
|
|
20 |
Y |
19 |
19 |
P |
|
|
|
22 |
Y |
30 |
22 |
P |
|
|
|
24 |
Y |
19 |
19 |
P |
|
|
|
26 |
Y |
19 |
19 |
P |
|
|
|
28 |
Y |
21 |
21 |
P |
|
|
|
32 |
Y |
19 |
20 |
P |
|
|
|
34 |
Y |
18 |
18 |
P |
|
|
|
36 |
Y |
21 |
21 |
P |
|
|
DB1B |
1 |
Y |
32 |
33 |
P |
|
|
|
2 |
Y |
42 |
114 |
P |
|
|
|
3 |
Y |
29 |
89 |
P |
|
|
|
4 |
Y |
32 |
111 |
P |
|
|
|
5 |
Y |
32 |
79 |
P |
|
|
|
6 |
Y |
50 |
69 |
P |
|
|
|
7 |
Y |
48 |
146 |
P |
|
|
|
8 |
Y |
28 |
94 |
P |
|
|
|
9 |
Y |
167 |
288 |
P |
|
|
|
10 |
Y |
29 |
61 |
P |
|
|
|
11 |
Y |
30 |
91 |
P |
|
|
DB2 |
3 |
Y |
39 |
30 |
P |
|
|
|
5 |
Y |
11 |
18 |
P |
|
|
|
7 |
Y |
10 |
19 |
P |
|
|
|
6 |
Y |
50 |
69 |
P |
|
|
|
10 |
Y |
48 |
146 |
P |
|
|
|
12 |
Y |
28 |
94 |
P |
|
|
|
14 |
Y |
167 |
288 |
P |
|
|
|
22 |
Y |
29 |
61 |
P |
|
|
|
24 |
Y |
30 |
91 |
P |
|
|
DB3 |
15 |
Y |
35 |
25 |
P |
|
|
|
4 |
Y |
24 |
16 |
P |
|
|
|
6 |
Y |
29 |
19 |
P |
|
|
|
8 |
Y |
32 |
23 |
P |
|
|
|
10 |
Y |
29 |
19 |
P |
|
|
|
16 |
Y |
26 |
17 |
P |
|
|
|
18 |
Y |
28 |
19 |
P |
|
|
|
20 |
Y |
25 |
15 |
P |
|
|
|
22 |
Y |
34 |
25 |
P |
|
|
|
28 |
Y |
20 |
18 |
P |
|
|
|
30 |
Y |
31 |
19 |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
|
1 |
S |
Y |
Y |
Y |
P |
|
|
|
|
2 |
S |
Y |
Y |
Y |
P |
|
|
|
|
3 |
S |
Y |
Y |
Y |
P |
|
|
|
|
4 |
4 |
Y |
Y |
Y |
P |
|
|
|
|
5 |
S |
Y |
Y |
Y |
P |
|
|
|
|
6 |
S |
Y |
Y |
Y |
P |
|
|
|
|
7 |
S |
Y |
Y |
Y |
P |
|
|
|
|
8 |
S |
Y |
Y |
Y |
P |
|
|
|
|
9 |
S |
Y |
Y |
Y |
P |
|
|
|
|
10 |
S |
Y |
Y |
Y |
P |
|
|
|
|
11 |
S |
Y |
Y |
Y |
P |
|
|
|
|
12 |
S |
Y |
Y |
Y |
P |
|
|
|
|
13 |
S |
Y |
Y |
Y |
P |
|
|
|
|
14 |
R |
Y |
Y |
Y |
P |
|
|
|
|
15 |
R |
N |
N |
N |
F |
MISSING LIGHT |
Y |
N |
|
16 |
R |
Y |
Y |
Y |
P |
|
|
|
|
17 |
S |
Y |
Y |
Y |
P |
|
|
|
|
18 |
S |
Y |
Y |
Y |
P |
|
|
|
|
19 |
S |
Y |
N |
Y |
F |
FAILED 90 MIN TEST |
Y |
N |
|
20 |
S |
Y |
Y |
Y |
P |
|
|
|
|
21 |
S |
Y |
Y |
Y |
P |
|
|
|
|
22 |
S |
Y |
Y |
Y |
P |
|
|
|
|
23 |
S |
Y |
Y |
Y |
P |
|
|
|
|
24 |
S |
Y |
Y |
Y |
P |
|
|
|
|
25 |
S |
Y |
Y |
Y |
P |
|
|
|
|
26 |
S |
Y |
N |
Y |
F |
FAILED 90 MIN TEST |
Y |
N |
|
27 |
S |
Y |
N |
Y |
F |
FAILED 90 MIN TEST |
Y |
N |
|
28 |
S |
Y |
Y |
Y |
P |
|
|
|
|
29 |
R |
Y |
Y |
Y |
P |
|
|
|
|
30 |
R |
Y |
Y |
Y |
P |
|
|
|
|
31 |
R |
Y |
Y |
Y |
P |
|
|
|
|
32 |
R |
Y |
Y |
Y |
P |
|
|
|
|
33 |
R |
Y |
Y |
Y |
P |
|
|
|
|
34 |
R |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
|
1 |
Y |
Y |
Y |
P |
|
|
|
|
2 |
Y |
Y |
Y |
P |
|
|
|
|
3 |
Y |
Y |
Y |
P |
|
|
|
|
4 |
Y |
Y |
Y |
P |
|
|
|
|
5 |
Y |
Y |
Y |
P |
|
|
|
|
6 |
Y |
Y |
Y |
P |
|
|
|
|
7 |
Y |
Y |
Y |
P |
|
|
|
|
8 |
Y |
Y |
Y |
P |
|
|
|
|
9 |
Y |
Y |
Y |
P |
|
|
|
|
10 |
Y |
Y |
Y |
P |
|
|
|
|
11 |
Y |
Y |
Y |
P |
|
|
|
|
12 |
Y |
Y |
Y |
P |
|
|
|
|
13 |
Y |
Y |
Y |
P |
|
|
|
|
14 |
Y |
Y |
Y |
P |
|
|
|
|
15 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
Halo High Bays |
Y |
Pelmet Lights 21W and 28W T5 Light Boxes |
Y |
2 x 28W Plastic Diffused Fluoro Fitting |
Y |
2 x 28W Caged Fluoro Fitting |
Y |
5W LED Downlight 50mm Fitting |
Y |
150mm LED Downlight |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
SURFACE MOUNT EMERGENCY LIGHTS |
BOH |
3 |
EM 19, 26 & 27 FAILED 90MIN TEST. |
Y |
N |
N |
RETURNED TO SITE WITH A SCISSOR LIFT AND REPLACED WITH NEW. |
RECESSED EMERGENCY LIGHT |
SHOP FLOOR |
1 |
EM15 MISSING |
Y |
N |
N |
RETURNED TO SITE TO INSTALL NEW LIGHT (CEILING RECENTLY REPAIRED/PATCHED WHERE LIGHT WAS LOCATED PREVIOUSLY) |
DOOR BUZZER |
BACK DOOR |
1 |
DAMAGED |
Y |
N |
N |
RETURNED TO SITE TO REPLACE WITH NEW. |
SWITCHBOARDS |
DB1,DB1B,DB2 & DB3 |
4 |
RCBO'S REQUIRED |
N |
N |
N/A |
ADDED TO FORTNIGHTLY REPAIRS LIST |
JBL |
SOUNDBARS |
1 |
DISPLAY IS FLICKERING |
N |
N |
N/A |
DISCONNECTED DISPLAY TO STOP FLICKERING |
DOWNLIGHTS |
TV SECTION |
4 |
FAULTY |
Y |
N |
N |
RETURNED TO SITE AND REPLACED WITH NEW. |
DROPPER |
SAMSUNG TV AREA |
1 |
NEEDS CAT WIRE RE-ATTACHED & DROPPER RE-ALIGNED. |
N |
N |
N/A |
OBSERVATION ONLY |
DROPPER |
HISENSE TV DROPPER |
1 |
NEEDS TO BE RE-ALIGNED |
N |
N |
N/A |
OBSERVATION ONLY |
EXTENSION LEAD DROPPER |
ADJACENT MAIN COUNTER |
1 |
NEEDS TO BE REMOVED |
N |
N |
N/A |
OBSERVATION ONLY |
DROPPER |
TV BULKSTACK |
1 |
REQUIRED |
N |
N |
N/A |
OBSERVATION ONLY |
WESTINGHOUSE |
FRIDGE DISPLAY |
1 |
DISPLAY NOT ILLUMINATED. |
N |
N |
N/A |
ADDED TO FORTNIGHTLY REPARIS LIST |
SAMSUNG |
FRIDGE DISPLAY |
1 |
LOGO NOT ILLUMINATED. 12V 5AMP DRIVER REQUIRED |
N |
N |
N/A |
ADDED TO FORTNIGHTLY REPAIRS LIST |
HISENSE |
FRIDGE DISPLAY |
1 |
12V DRIVER REQUIRED |
N |
N |
N/A |
ADDED TO FORTNIGHTLY REPAIRS LIST |
TECHNIKA |
KITCHEN DISPLAY |
1 |
2X LINKABLES & 1X STARTER LEAD REQUIRED |
N |
N |
N/A |
ADDED TO FORTNIGHTLY REPAIRS LIST |
LA GERMANIA |
OVEN DISPLAY |
4 |
LED DOWNLIGHTS REQUIRED |
N |
N |
N/A |
ADDED TO FORTNIGHTLY REPAIRS LIST |
FISHER & PAYKEL |
KITCHEN DISPLAY |
1 |
92MM DOWNLIGHT REQUIRED |
N |
N |
N/A |
ADDED TO FORTNIGHTLY REPAIRS LIST |
BOSCH |
KITCHEN DISPLAY |
1 |
2X LINKABLES & 1X STARTER LEAD REQUIRED |
N |
N |
N/A |
ADDED TO FORTNIGHTLY REPAIRS LIST |
SMEG |
ISLAND DISPLAY |
3 |
ES LAMPS REQUIRED |
N |
N |
N/A |
ADDED TO FORTNIGHTLY REPAIRS LIST |
SMEG |
KITCHEN DISPLAY |
1 |
2X LINKABLES & 1X STARTER LEAD REQUIRED |
N |
N |
N/A |
ADDED TO FORTNIGHTLY REPAIRS LIST |
EMERGENCY LIGHTING PLAN |
BOH |
1 |
NOT UPDATED |
Y |
N |
N |
UPDATED FOLDER WITH CURRENT EMERGENCY LIGHTING PLAN. |
MINI CIRCUIT BREAKERS |
DB2 |
ALL |
NOT TOGGLED THE SAME WAY AS RCBO'S |
Y |
N |
N |
RE-ORIENTATED MCB'S TO TOGGLE THE SAME WAY AS THE RCBO'S AS PER AS3000 STANDARDS. |
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 23/01/2023 |
---|
| |
---|
| |