Partner NameBuilt Services
StateVIC
Date of Visit18/07/2022
Technician's NameDaniel Breen
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number67200
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICtraralgon

Location NameTraralgon
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
MSB 4 Y 32 29 P
6 Y 36 42 P
8 Y 37 38 P
10 Y 37 38 P
12 Y 38 37 P
14 Y 38 33 P
16 Y 38 33 P
18 Y 34 31 P
20 Y 40 37 P
22 Y 40 34 P
24 Y 32 30 P
26 Y 39 38 P
32 Y 37 32 P
37 Y 37 38 P
39 Y 7 18 P
41 Y 45 43 P
42 Y 59 39 P
43 Y 41 41 P
45 Y 33 35 P
46 Y 38 31 P
47 Y 40 36 P
48 Y 39 31 P
50 Y 38 38 P
51 Y 35 39 P
52 Y 128 117 P
53 Y 41 39 P
54 Y 89 98 P
55 Y 42 34 P
56 Y 39 39 P
57 Y 11 17 P
59 Y 38 38 P
60 Y 38 39 P
63 Y 39 39 P
65 Y 36 40 P
67 Y 38 39 P
68 Y 7 17 P
79 Y 5 12 P
83 Y 7 17 P
DB2 2 Y 35 35 P
4 Y 32 35 P
8 Y 43 36 P
10 Y 33 31 P
12 Y 42 37 P
14 Y 32 38 P
15 Y 48 40 P
16 Y 34 38 P
17 Y 39 38 P
18 Y 38 36 P
20 Y 33 34 P
22 Y 32 30 P
24 Y 40 35 P
26 Y 41 42 P
28 Y 36 34 P
32 Y 44 43 P
34 Y 38 32 P
38 Y 39 35 P
40 Y 30 31 P
42 Y 39 32 P
44 Y 38 37 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB 4 S Y Y Y P
MSB 5 S Y Y Y P
MSB 6 S Y Y Y P
MSB 7 S N N Y F Failed 90 Min Test Y N
DB2 11 R Y Y Y P
DB2 12 R Y Y Y P
DB2 13 R N N Y F Failed 90 Min Test Y N
DB2 15 R Y Y Y P
DB2 16 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB 1 N N Y F Failed 90 Min Test Y N
MSB 2 Y Y Y P
MSB 3 N N Y F Failed 90 Min Test Y N
DB2 8 Y Y Y P
DB2 9 Y Y Y P
DB2 10 Y Y Y P
DB2 14 N N Y F Failed 90 Min Test Y N
DB2 17 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Twin 4ft LED Fluorescent Lights Y
Batten lights Y
Recessed halogen downlights Y
2ft display fluorescent lights Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
5ft bare batten Above DB2 1 2 x lamp N TBA TBA Added to the fortnightly repairs list
5ft bare batten Fridge store (BOH) 1 1 x lamp N TBA TBA Added to the fortnightly repairs list
4ft Diffused batten Dispatch office 2 1 x fitting N TBA TBA Added to the fortnightly repairs list
4ft Diffused batten Tea room 1 1 x lamp N TBA TBA Added to the fortnightly repairs list
Exhaust fan Comms Rack 1 Not working N N N Observation
4ft bare batten Staff room and managers office 2 1 x lamp in each N TBA TBA Added to the fortnightly repairs list
5ft bare batten Store main floor 1 1 X faulty fitting N TBA TBA Added to the fortnightly repairs list
5ft bare batten Store main floor 19 Lamps out N TBA TBA Added to the fortnightly repairs list
LED Advertising sign lights Multiple Lamps out N TBA TBA Added to the fortnightly repairs list
2ft Vanda light Rear entry 1 Faulty Y N N Replaced
Flood lights Front sign 9 Faulty N TBA TBA Added to the fortnightly repairs list
Batten holder lamp Front Window 22 Faulty N Y N Added to the fortnightly repairs list
Downlights Front window 9 Faulty Y N N Replaced
Bus bar barrier MSB 1 Non-existent Y N N Replaced
Fire caulk MSB + DB2 2 Non-existent N N N Observation
Broken Toggle MSB + CB05 1 Broken Y N N Replaced
Emergency labels MSB + DB2 6 Missing Y N N Replaced
Surface mounted emergency#5 #7 MSB 1 Failed discharge test Y N N Replaced
Surface mounted emergency#5 MSB 1 Failed discharge test Y N N Replaced
Recessed emergency light #13 DB2 1 Failed discharge test Y N N Replaced
EXIT LIGHT #1 MSB 1 Failed discharge test Y N N Replaced
EXIT LIGHT #3 MSB 1 Failed discharge test Y N N Replaced
EXIT LIGHT #14 DB2 1 Failed discharge test Y N N Replaced
Site Status SelectorStore now fully compliant
Next Test Due in 6 months18/01/2023