Partner Name | Built Services |
---|
State | VIC |
---|
Date of Visit | 18/07/2022 |
---|
Technician's Name | Daniel Breen |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 67200 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in VIC | traralgon |
---|
|
|
---|
Location Name | Traralgon |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
MSB |
4 |
Y |
32 |
29 |
P |
|
|
|
6 |
Y |
36 |
42 |
P |
|
|
|
8 |
Y |
37 |
38 |
P |
|
|
|
10 |
Y |
37 |
38 |
P |
|
|
|
12 |
Y |
38 |
37 |
P |
|
|
|
14 |
Y |
38 |
33 |
P |
|
|
|
16 |
Y |
38 |
33 |
P |
|
|
|
18 |
Y |
34 |
31 |
P |
|
|
|
20 |
Y |
40 |
37 |
P |
|
|
|
22 |
Y |
40 |
34 |
P |
|
|
|
24 |
Y |
32 |
30 |
P |
|
|
|
26 |
Y |
39 |
38 |
P |
|
|
|
32 |
Y |
37 |
32 |
P |
|
|
|
37 |
Y |
37 |
38 |
P |
|
|
|
39 |
Y |
7 |
18 |
P |
|
|
|
41 |
Y |
45 |
43 |
P |
|
|
|
42 |
Y |
59 |
39 |
P |
|
|
|
43 |
Y |
41 |
41 |
P |
|
|
|
45 |
Y |
33 |
35 |
P |
|
|
|
46 |
Y |
38 |
31 |
P |
|
|
|
47 |
Y |
40 |
36 |
P |
|
|
|
48 |
Y |
39 |
31 |
P |
|
|
|
50 |
Y |
38 |
38 |
P |
|
|
|
51 |
Y |
35 |
39 |
P |
|
|
|
52 |
Y |
128 |
117 |
P |
|
|
|
53 |
Y |
41 |
39 |
P |
|
|
|
54 |
Y |
89 |
98 |
P |
|
|
|
55 |
Y |
42 |
34 |
P |
|
|
|
56 |
Y |
39 |
39 |
P |
|
|
|
57 |
Y |
11 |
17 |
P |
|
|
|
59 |
Y |
38 |
38 |
P |
|
|
|
60 |
Y |
38 |
39 |
P |
|
|
|
63 |
Y |
39 |
39 |
P |
|
|
|
65 |
Y |
36 |
40 |
P |
|
|
|
67 |
Y |
38 |
39 |
P |
|
|
|
68 |
Y |
7 |
17 |
P |
|
|
|
79 |
Y |
5 |
12 |
P |
|
|
|
83 |
Y |
7 |
17 |
P |
|
|
DB2 |
2 |
Y |
35 |
35 |
P |
|
|
|
4 |
Y |
32 |
35 |
P |
|
|
|
8 |
Y |
43 |
36 |
P |
|
|
|
10 |
Y |
33 |
31 |
P |
|
|
|
12 |
Y |
42 |
37 |
P |
|
|
|
14 |
Y |
32 |
38 |
P |
|
|
|
15 |
Y |
48 |
40 |
P |
|
|
|
16 |
Y |
34 |
38 |
P |
|
|
|
17 |
Y |
39 |
38 |
P |
|
|
|
18 |
Y |
38 |
36 |
P |
|
|
|
20 |
Y |
33 |
34 |
P |
|
|
|
22 |
Y |
32 |
30 |
P |
|
|
|
24 |
Y |
40 |
35 |
P |
|
|
|
26 |
Y |
41 |
42 |
P |
|
|
|
28 |
Y |
36 |
34 |
P |
|
|
|
32 |
Y |
44 |
43 |
P |
|
|
|
34 |
Y |
38 |
32 |
P |
|
|
|
38 |
Y |
39 |
35 |
P |
|
|
|
40 |
Y |
30 |
31 |
P |
|
|
|
42 |
Y |
39 |
32 |
P |
|
|
|
44 |
Y |
38 |
37 |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
MSB |
4 |
S |
Y |
Y |
Y |
P |
|
|
|
MSB |
5 |
S |
Y |
Y |
Y |
P |
|
|
|
MSB |
6 |
S |
Y |
Y |
Y |
P |
|
|
|
MSB |
7 |
S |
N |
N |
Y |
F |
Failed 90 Min Test |
Y |
N |
DB2 |
11 |
R |
Y |
Y |
Y |
P |
|
|
|
DB2 |
12 |
R |
Y |
Y |
Y |
P |
|
|
|
DB2 |
13 |
R |
N |
N |
Y |
F |
Failed 90 Min Test |
Y |
N |
DB2 |
15 |
R |
Y |
Y |
Y |
P |
|
|
|
DB2 |
16 |
R |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
MSB |
1 |
N |
N |
Y |
F |
Failed 90 Min Test |
Y |
N |
MSB |
2 |
Y |
Y |
Y |
P |
|
|
|
MSB |
3 |
N |
N |
Y |
F |
Failed 90 Min Test |
Y |
N |
DB2 |
8 |
Y |
Y |
Y |
P |
|
|
|
DB2 |
9 |
Y |
Y |
Y |
P |
|
|
|
DB2 |
10 |
Y |
Y |
Y |
P |
|
|
|
DB2 |
14 |
N |
N |
Y |
F |
Failed 90 Min Test |
Y |
N |
DB2 |
17 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
Twin 4ft LED Fluorescent Lights |
Y |
Batten lights |
Y |
Recessed halogen downlights |
Y |
2ft display fluorescent lights |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
5ft bare batten |
Above DB2 |
1 |
2 x lamp |
N |
TBA |
TBA |
Added to the fortnightly repairs list |
5ft bare batten |
Fridge store (BOH) |
1 |
1 x lamp |
N |
TBA |
TBA |
Added to the fortnightly repairs list |
4ft Diffused batten |
Dispatch office |
2 |
1 x fitting |
N |
TBA |
TBA |
Added to the fortnightly repairs list |
4ft Diffused batten |
Tea room |
1 |
1 x lamp |
N |
TBA |
TBA |
Added to the fortnightly repairs list |
Exhaust fan |
Comms Rack |
1 |
Not working |
N |
N |
N |
Observation |
4ft bare batten |
Staff room and managers office |
2 |
1 x lamp in each |
N |
TBA |
TBA |
Added to the fortnightly repairs list |
5ft bare batten |
Store main floor |
1 |
1 X faulty fitting |
N |
TBA |
TBA |
Added to the fortnightly repairs list |
5ft bare batten |
Store main floor |
19 |
Lamps out |
N |
TBA |
TBA |
Added to the fortnightly repairs list |
LED |
Advertising sign lights |
Multiple |
Lamps out |
N |
TBA |
TBA |
Added to the fortnightly repairs list |
2ft Vanda light |
Rear entry |
1 |
Faulty |
Y |
N |
N |
Replaced |
Flood lights |
Front sign |
9 |
Faulty |
N |
TBA |
TBA |
Added to the fortnightly repairs list |
Batten holder lamp |
Front Window |
22 |
Faulty |
N |
Y |
N |
Added to the fortnightly repairs list |
Downlights |
Front window |
9 |
Faulty |
Y |
N |
N |
Replaced |
Bus bar barrier |
MSB |
1 |
Non-existent |
Y |
N |
N |
Replaced |
Fire caulk |
MSB + DB2 |
2 |
Non-existent |
N |
N |
N |
Observation |
Broken Toggle |
MSB + CB05 |
1 |
Broken |
Y |
N |
N |
Replaced |
Emergency labels |
MSB + DB2 |
6 |
Missing |
Y |
N |
N |
Replaced |
Surface mounted emergency#5 #7 |
MSB |
1 |
Failed discharge test |
Y |
N |
N |
Replaced |
Surface mounted emergency#5 |
MSB |
1 |
Failed discharge test |
Y |
N |
N |
Replaced |
Recessed emergency light #13 |
DB2 |
1 |
Failed discharge test |
Y |
N |
N |
Replaced |
EXIT LIGHT #1 |
MSB |
1 |
Failed discharge test |
Y |
N |
N |
Replaced |
EXIT LIGHT #3 |
MSB |
1 |
Failed discharge test |
Y |
N |
N |
Replaced |
EXIT LIGHT #14 |
DB2 |
1 |
Failed discharge test |
Y |
N |
N |
Replaced |
|
---|
Site Status Selector | Store now fully compliant |
---|