Carry out push button test and record the results below.
RCD Details (Biennial)
Distribution Board No.
Circuit No.
Push Button (YorN)
0 Degrees
180 Degrees
Pass / Fail (PorF)
Fault?
Repaired on Site (YorN)
DB-T12B
2
Y
.024
.034
P
4
Y
.044
.034
P
5
Y
.044
.054
P
6
Y
.028
.038
P
7
Y
.024
.037
P
8
Y
.088
.033
P
9
Y
.044
.054
P
10
Y
.025
.035
P
11
Y
.045
.035
P
12
Y
.045
.034
P
13
Y
.044
.033
P
14
Y
.048
.037
P
16
Y
.023
.038
P
18
Y
.026
.036
P
20
Y
.028
.018
P
21
Y
.044
.034
P
22
Y
.025
.034
P
23
Y
.029
.018
P
24
Y
.023
.016
P
25
Y
.029
.021
P
27
Y
.026
.017
P
29
Y
.024
.015
P
31
Y
.028
.038
P
32
Y
.029
.039
P
33
Y
.029
.035
P
34
Y
.028
.018
P
35
Y
.029
.013
P
36
Y
.038
.044
P
37
Y
.024
.034
P
38
Y
.044
.034
P
40
Y
.044
.054
P
42
Y
.028
.038
P
43
Y
.024
.037
P
44
Y
.088
.034
P
46
Y
.044
.054
P
48
Y
.025
.035
P
50
Y
.045
.033
P
52
Y
.045
.035
P
53
Y
.047
.037
P
DB-T12C
2
Y
.046
.036
P
4
Y
.048
.037
P
5
Y
.023
.016
P
6
Y
.028
.018
P
7
Y
.029
.013
P
8
Y
.044
.034
P
9
Y
.046
.036
P
10
Y
.052
.042
P
11
Y
.033
.045
P
12
Y
.030
.037
P
13
Y
.026
.016
P
14
Y
.030
.043
P
15
Y
.028
.018
P
16
Y
.028
.018
P
17
Y
.033
.017
P
18
Y
.028
.018
P
19
Y
.022
.035
P
20
Y
.025
.034
P
21
Y
.029
.018
P
22
Y
.023
.015
P
23
Y
.029
.022
P
24
Y
.027
.020
P
25
Y
.029
.013
P
26
Y
.029
.018
P
27
Y
.028
.038
P
28
Y
.044
.034
P
29
Y
.024
.015
P
30
Y
.028
.018
P
31
Y
.046
.036
P
32
Y
.046
.038
P
33
Y
.043
.053
P
34
Y
.060
.049
P
35
Y
.044
.033
P
36
Y
.023
.016
P
38
Y
.029
.039
P
39
Y
.035
.022
P
40
Y
.028
.018
P
41
Y
.028
.018
P
42
Y
.029
.035
P
43
Y
.023
.038
P
44
Y
.044
.034
P
45
Y
.026
.016
P
46
Y
.027
.016
P
47
Y
.030
.018
P
48
Y
.045
.038
P
49
Y
.029
.019
P
50
Y
.030
.043
P
51
Y
.023
.015
P
52
Y
.025
.035
P
53
Y
.044
.033
P
55
Y
.028
.018
P
59
Y
.022
.016
P
60
Y
.037
.025
P
DB-T12D
1
Y
.028
.018
P
2
Y
.027
.018
P
3
Y
.030
.023
P
4
Y
.028
.018
P
5
Y
.028
.018
P
6
Y
.028
.018
P
7
Y
.026
.035
P
8
Y
.028
.018
P
9
Y
.035
.044
P
10
Y
.023
.013
P
11
Y
.033
.043
P
12
Y
.029
.037
P
15
Y
.022
.015
P
16
Y
.030
.O17
P
17
Y
.028
.018
P
18
Y
.030
.043
P
19
Y
.025
.033
P
20
Y
.027
.017
P
21
Y
.028
.018
P
22
Y
.028
.018
P
23
Y
.028
.018
P
25
Y
.033
.048
P
27
Y
.028
.022
P
29
Y
.023
.016
P
DB-T12E
1
Y
.028
.018
P
3
Y
.028
.018
P
5
Y
.033
.021
P
7
Y
.045
.033
P
9
Y
.047
.037
P
10
Y
.028
.038
P
11
Y
.028
.018
P
12
Y
.029
.013
P
13
Y
.028
.038
P
14
Y
.023
.016
P
15
Y
.029
.039
P
16
Y
.024
.015
P
17
Y
.025
.033
P
19
Y
.025
.034
P
20
Y
.029
.019
P
21
Y
.029
.019
P
34
Y
.028
.038
P
44
Y
.028
.018
P
THERMOGRAPHIC TEST RESULTS
THERMOGRAPHIC TEST RESULTS
SF43 Exit/Emergency
SF43 EXIT/EMERGENCY LIGHTING
Exit/Emergency Light Checklist
Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
Check timers for correct operation and timing
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No.
ID No.
Surface mounted or recessed? (SorR)
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
T12C
1
S
Y
Y
Y
P
T12C
2
S
Y
Y
Y
P
T12C
6
S
Y
Y
Y
P
T12C
7
S
Y
Y
Y
P
T12C
11
S
Y
Y
Y
P
T12C
12
S
Y
Y
Y
P
T12C
13
S
Y
Y
Y
P
T12C
14
S
Y
Y
Y
P
T12C
15
S
Y
Y
Y
P
T12C
17
S
Y
Y
Y
P
T12C
18
S
Y
Y
Y
P
T12C
20
S
Y
Y
Y
P
T12C
23
R
Y
Y
Y
P
T12C
24
R
Y
Y
Y
P
T12C
25
R
Y
Y
Y
P
T12C
26
R
Y
Y
Y
P
T12C
28
R
Y
Y
Y
P
T12C
29
R
Y
Y
Y
P
T12C
30
S
Y
Y
Y
P
T12C
31
R
Y
Y
Y
P
T12C
33
S
Y
Y
Y
P
T12C
35
R
Y
Y
Y
P
T12C
40
S
Y
Y
Y
P
T12C
41
S
Y
Y
Y
P
T12C
42
S
Y
Y
Y
P
T12C
43
S
Y
Y
Y
P
T12C
44
S
Y
Y
Y
P
T12C
45
S
Y
Y
Y
P
T12C
46
S
Y
Y
Y
P
T12C
47
S
Y
Y
Y
P
T12C
51
S
Y
Y
Y
P
T12C
52
S
Y
Y
Y
P
T12C
54
R
Y
Y
Y
P
T12C
55
R
Y
Y
Y
P
T12C
57
R
Y
Y
Y
P
T12C
58
R
Y
Y
Y
P
T12C
59
R
Y
Y
Y
P
T12C
60
R
Y
Y
Y
P
T12C
61
R
Y
Y
Y
P
T12C
62
R
Y
Y
Y
P
T12C
63
R
Y
Y
Y
P
T12C
64
R
Y
Y
Y
P
T12C
65
R
Y
Y
Y
P
T12C
67
R
Y
Y
Y
P
T12C
69
R
Y
Y
Y
P
HTML Block
EXIT LIGHTS
Distribution Board No.
ID No.
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
T12C
3
Y
Y
Y
P
T12C
4
Y
Y
Y
P
T12C
5
Y
Y
Y
P
T12C
8
Y
Y
Y
P
T12C
9
Y
Y
Y
P
T12C
10
Y
Y
Y
P
T12C
16
Y
Y
Y
P
T12C
19
Y
Y
Y
P
T12C
21
Y
Y
Y
P
T12C
22
Y
Y
Y
P
T12C
27
Y
Y
Y
P
T12C
32
Y
Y
Y
P
T12C
34
Y
Y
Y
P
T12C
36
Y
Y
Y
P
T12C
37
Y
Y
Y
P
T12C
38
Y
Y
Y
P
T12C
39
Y
Y
Y
P
T12C
48
Y
Y
Y
P
T12C
49
Y
Y
Y
P
T12C
50
Y
Y
Y
P
T12C
53
Y
Y
Y
P
T12C
56
Y
Y
Y
P
T12C
66
Y
Y
Y
P
T12C
68
Y
Y
Y
P
SF44 General Lighting & Works
SF44 GENERAL LIGHTING & WORKS
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
HTML Block
General Operation/Additional items
Check with Store Manager to ensure there are no other issues
Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au
Yes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten)
Existing (YorN)
Ci-C Fluoro
Y
2x36w Diffused
Y
400w Flood Light
Y
70mm Downlight
Y
1x18 T5 Diffused
Y
2x18w T5 Caged Fluoro
Y
2x18w Waterproof T5
Y
140mm Downlight
Y
18w Compact Fluoro
Y
Twin Par 38 Sensor
Y
250w Square Diffused
Y
36w Lamps
Y
Square Recessed Fluoro
Y
Are there any Warranty items needing to be repaired?
No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
Power point in kitchenette
BOH
1
Double adapter being used
Y
N
N
Supplied and installed 1 x double GPO above existing GPO
Fridge Displays
Fridges
2
Extension leads are in use
N
N
N
2 x Display bays are being ran from general extension leads with normal power boards. Recommend installing power droppers. Quote recommendation listed on fortnightly report
Exit Light
Near rear airlock
1
Exit fittings had been tied up
Y
N
N
Rectified
Site Status Selector
Store now fully compliant
Next Test Due in 6 months
08/02/2023