Partner NameBuilt Electrical Australia
StateVIC
Date of Visit01/09/2022
Technician's NameAnthony Zammit
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number67205
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICbayswater

Location NameBayswater
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
MSB section 1 13 Y 132 45 P
MSB section 1 20 Y 28 38 P
MSB section 1 21 Y 31 41 P
MSB section 1 23 Y 28 21 P
MSB section 1 27 Y 28 38 P
MSB section 1 33 Y 30 40 P
MSB section 1 55 Y 19 25 P
MSB section 1 57 Y 20 20 P
MSB section 1 59 Y 28 28 P
MSB section 2 8 Y 30 35 P
MSB section 2 10 Y 33 42 P
MSB section 2 12 Y 31 41 P
MSB section 2 13 Y 28 38 P
MSB section 2 14 Y 30 26 P
MSB section 2 15 Y 28 38 P
MSB section 2 16 Y 23 57 P
MSB section 2 17 Y 28 38 P
MSB section 2 18 Y 24 26 P
MSB section 2 19 Y 28 21 P
MSB section 2 20 Y 31 41 P
MSB section 2 21 Y 84 37 P
MSB section 2 22 Y 31 41 P
MSB section 2 23 Y 28 38 P
MSB section 2 24 Y 28 22 P
MSB section 2 25 Y 30 40 P
MSB section 2 26 Y 42 26 P
MSB section 2 27 Y 30 41 P
MSB section 2 28 Y 26 49 P
MSB section 2 29 Y 28 20 P
MSB section 2 30 Y 28 38 P
MSB section 2 31 Y - - F Failed 0 and 180 degree test Y
MSB section 2 32 Y 22 32 P
MSB section 2 33 Y 37 37 P
MSB section 2 34 Y 31 41 P
MSB section 2 35 Y 28 38 P
MSB section 2 36 Y 25 35 P
MSB section 2 37 Y 37 40 P
DB02 1 Y 28 38 P
DB02 3 Y 28 18 P
DB02 4 Y 23 33 P
DB02 5 Y 28 18 P
DB02 6 Y 29 19 P
DB02 7 Y 28 18 P
DB02 8 Y 23 17 P
DB02 9 Y 28 18 P
DB02 10 Y 22 32 P
DB02 11 Y 30 40 P
DB02 12 Y 28 38 P
DB02 17 Y 28 18 P
DB02 18 Y 28 18 P
DB02 20 Y 28 18 P
DB02 22 Y 29 18 P
DB02 24 Y 28 18 P
DB01 section 1 1 Y 28 38 P
DB01 section 1 2 Y 38 41 P
DB01 section 1 3 Y 37 37 P
DB01 section 1 4 Y 28 - F Failed 180 degree test Y
DB01 section 1 5 Y 28 38 P
DB01 section 1 6 Y 28 38 P
DB01 section 1 7 Y 28 38 P
DB01 section 1 8 Y 37 - F Failed 180 degree test Y
DB01 section 1 9 Y 28 27 P
DB01 section 1 10 Y - - F Failed 0 and 180 degree test Y
DB01 section 1 11 Y 28 38 P
DB01 section 1 12 Y 39 39 P
DB01 section 1 13 Y 37 37 P
DB01 section 1 14 Y 28 20 P
DB01 section 1 15 Y 32 33 P
DB01 section 1 16 Y 28 38 P
DB01 section 1 17 Y 30 22 P
DB01 section 1 18 Y 28 38 P
DB01 section 1 19 Y 37 37 P
DB01 section 1 20 Y 28 21 P
DB01 section 1 21 Y 37 37 P
DB01 section 1 22 Y 28 38 P
DB01 section 1 23 Y 28 38 P
DB01 section 1 24 Y 30 22 P
DB01 section 1 25 Y 28 38 P
DB01 section 1 26 Y 28 38 P
DB01 section 1 27 Y 37 37 P
DB01 section 1 28 Y 35 37 P
DB01 section 1 29 Y 28 19 P
DB01 section 1 30 Y 28 38 P
DB01 section 1 33 Y 28 38 P
DB01 section 1 35 Y 43 42 P
DB01 Section 2 1 Y 24 19 P
DB01 Section 2 2 Y 31 40 P
DB01 Section 2 3 Y 29 39 P
DB01 Section 2 4 Y 30 40 P
DB01 Section 2 5 Y 24 19 P
DB01 Section 2 6 Y 29 39 P
DB01 Section 2 7 Y 28 38 P
DB01 Section 2 8 Y 30 23 P
DB01 Section 2 9 Y 28 38 P
DB01 Section 2 10 Y 28 38 P
DB01 Section 2 11 Y 28 18 P
DB01 Section 2 12 Y 28 38 P
DB01 Section 2 13 Y 28 20 P
DB01 Section 2 14 Y 28 38 P
DB01 Section 2 15 Y 31 26 P
DB01 Section 2 16 Y 26 38 P
DB01 Section 2 17 Y 30 40 P
DB01 Section 2 18 Y 22 35 P
DB01 Section 2 19 Y 28 38 P
DB01 Section 2 20 Y 33 33 P
DB01 Section 2 21 Y 27 32 P
DB01 Section 2 22 Y 30 39 P
DB01 Section 2 23 Y 29 20 P
DB01 Section 2 24 Y 30 20 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 1 S Y Y Y P
DB1 2 S Y Y Y P
DB1 3 S Y Y Y P
DB1 4 S Y Y Y P
DB1 5 S Y Y Y P
DB1 6 S Y Y Y P
DB1 7 S Y Y Y P
DB1 8 S Y Y Y P
DB1 9 S Y Y Y P
DB1 10 S Y Y Y P
DB1 11 S Y Y Y P
DB1 12 R Y Y Y P
DB1 13 R Y Y Y P
DB1 14 R Y Y Y P
DB1 15 R Y Y Y P
DB1 16 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 1 Y Y Y P
DB1 2 Y Y Y P
DB1 3 Y Y Y P
DB1 4 Y Y Y P
DB1 5 Y Y Y P
DB1 6 Y Y Y P
DB1 7 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Induction high bay lights Y
LED high bay lights Y
Emergency single 36w battern Y
Emergency recessed lights Y
Bardic Exit lights Y
70mm downlights Y
36W single fluorescent bare battern Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
LED high-bay Above e-scooter 1 Failed to illuminate N Y Y Need scissor lift to replace. Added to fortnightly repairs list.
28 watt single fluorescent lights Lunchroom 4 Failed to illuminate Y N N Replaced with new.
28 watt single fluorescent lights Upstairs meeting room 3 Failed to illuminate Y N N Replaced with new.
28 watt single fluorescent lights Lock up room 1 Failed to illuminate Y N N Replaced with new.
LED downlight Tv zone 2 Failed to illuminate Y N N Replaced with new.
LED downlight Toilets 1 Failed to illuminate Y N N Replaced with new.
20 amp RCBO MSB section 2 CB31 1 Failed 0 and 180 degree test Y N N Replaced with new.
20 amp RCBO DB01 Section 1 1 Failed 0 and 180 degree test Y N N Returned to site and replaced with new.
20 amp RCBO DB01 Section 1 1 Failed 180 degree test Y N N Returned to site and replaced with new.
20 amp RCBO DB01 Section 1 1 Failed 0 and 180 degree test Y N N Returned to site and replaced with new.
LED strip light box Seasonal 1 Failed to illuminate Y N N Repaired loose connection.
LED strip light box Mobile plans 1 Failed to illuminate. Need to replace power supply (outputDC 24 v, 1.25A, 30W) N N N Added to fortnightly repairs list.
LED strip light box Accessories 1 Failed to illuminate. Need to replace power supply (outputDC 24 v, 1.25A, 30W) N N N Added to fortnightly repairs list.
LED strip light box Wearable 1 Failed to illuminate. Need to replace power supply (outputDC 24 v, 1.25A, 30W) N N N Added to fortnightly repairs list.
LED strip light box Monitor 1 Failed to illuminate. Need to replace power supply (outputDC 24 v, 1.25A, 30W) N N N Added to fortnightly repairs list.
LED strip light box Smart speakers 1 Failed to illuminate. Need to replace power supply (outputDC 24 v, 1.25A, 30W) N N N Added to fortnightly repairs list.
LED strip light box Sound bars 1 Failed to illuminate. Need to replace power supply (outputDC 24 v, 1.25A, 30W) N N N Added to fortnightly repairs list.
LED strip light box Wall brackets 1 Failed to illuminate. Need to replace power supply (outputDC 24 v, 1.25A, 30W) N N N Added to fortnightly repairs list.
LED strip light box Television 1 Failed to illuminate. Need to replace power supply (outputDC 24 v, 1.25A, 30W) N N N Added to fortnightly repairs list.
Site Status SelectorStore now fully compliant
Next Test Due in 6 months01/03/2023