Partner NameBuilt Electrical Australia
StateVIC
Date of Visit15/09/2022
Technician's NameAnthony Zammit
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number67209
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICsunbury

Location NameSunbury
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
BD-T1 Lighting 1 Y 28 18 P
BD-T1 Lighting 3 Y 28 18 P
BD-T1 Lighting 4 Y 28 18 P
BD-T1 Lighting 5 Y 28 18 P
BD-T1 Lighting 6 Y 29 19 P
BD-T1 Lighting 7 Y 28 18 P
BD-T1 Lighting 8 Y 28 18 P
BD-T1 Lighting 9 Y 28 18 P
BD-T1 Lighting 10 Y 28 18 P
BD-T1 Lighting 11 Y 30 18 P
BD-T1 Lighting 12 Y 28 18 P
BD-T1 Lighting 13 Y 28 18 P
BD-T1 Lighting 14 Y 28 18 P
BD-T1 Lighting 15 Y 23 35 P
BD-T1 Lighting 16 Y 28 18 P
BD-T1 Lighting 17 Y 46 48 P
BD-T1 Lighting 18 Y 28 18 P
BD-T1 Lighting 19 Y 28 18 P
BD-T1 Lighting 20 Y 28 18 P
BD-T1 Lighting 21 Y 24 15 P
BD-T1 Lighting 22 Y 28 18 P
BD-T1 Lighting 23 Y 28 18 P
BD-T1 Lighting 24 Y 28 18 P
Tenancy dedicated power 2 Y 80 16 P
Tenancy dedicated power 4 Y 90 17 P
Tenancy dedicated power 6 Y 25 17 P
Tenancy dedicated power 7 Y 24 16 P
Tenancy dedicated power 8 Y 24 16 P
Tenancy dedicated power 9 Y 28 18 P
Tenancy dedicated power 10 Y 25 18 P
Tenancy dedicated power 11 Y 25 17 P
Tenancy dedicated power 12 Y 28 18 P
Tenancy dedicated power 13 Y 26 17 P
Tenancy dedicated power 14 Y 28 18 P
Tenancy dedicated power 15 Y 24 17 P
Tenancy dedicated power 16 Y 28 18 P
Tenancy dedicated power 17 Y 28 18 P
Tenancy dedicated power 18 Y 28 18 P
Tenancy dedicated power 19 Y 28 18 P
Tenancy dedicated power 20 Y 28 18 P
Tenancy dedicated power 21 Y 25 19 P
Tenancy dedicated power 22 Y 28 18 P
Tenancy dedicated power 23 Y 24 16 P
Tenancy dedicated power 24 Y 28 18 P
Tenancy dedicated power 25 Y 29 20 P
Tenancy dedicated power 26 Y 28 18 P
Tenancy dedicated power 27 Y 29 19 P
Tenancy dedicated power 28 Y 28 18 P
Tenancy dedicated power 29 Y 25 18 P
Tenancy dedicated power 30 Y 28 18 P
Tenancy dedicated power 31 Y 23 15 P
Tenancy dedicated power 32 Y 28 18 P
Tenancy dedicated power 33 Y 24 15 P
Tenancy dedicated power 34 Y 23 15 P
Tenancy dedicated power 35 Y 24 21 P
Tenancy dedicated power 36 Y 25 16 P
Tenancy dedicated power 37 Y 25 17 P
Tenancy dedicated power 38 Y 28 18 P
Tenancy dedicated power 40 Y 23 15 P
Tenancy dedicated power 41 Y 23 15 P
Tenancy dedicated power 42 Y 28 18 P
Tenancy dedicated power 44 Y 28 18 P
Tenancy dedicated power 46 Y 28 16 P
Tenancy dedicated power 48 Y 28 18 P
Tenancy dedicated power 49 Y 28 18 P
Tenancy dedicated power 50 Y 28 18 P
Tenancy dedicated power 51 Y 28 16 P
Tenancy dedicated power 52 Y 28 18 P
Tenancy dedicated power 53 Y 28 18 P
Tenancy dedicated power 54 Y 25 17 P
Tenancy dedicated power 55 Y 28 18 P
Tenancy dedicated power 56 Y 25 19 P
Tenancy dedicated power 57 Y 28 18 P
Tenancy dedicated power 58 Y 24 19 P
Tenancy dedicated power 59 Y 28 18 P
Tenancy dedicated power 60 Y 23 17 P
Tenancy dedicated power 61 Y 28 18 P
Tenancy dedicated power 62 Y 28 18 P
Tenancy dedicated power 63 Y 28 18 P
Tenancy dedicated power 64 Y 28 18 P
Tenancy dedicated power 65 Y 28 18 P
Tenancy dedicated power 66 Y 28 18 P
Tenancy dedicated power 67 Y 28 18 P
Tenancy dedicated power 68 Y 28 18 P
Tenancy dedicated power 69 Y 28 18 P
Tenancy dedicated power 70 Y 28 18 P
Tenancy dedicated power 71 Y 28 18 P
Tenancy dedicated power 72 Y 28 18 P
Tenancy dedicated power 73 Y 28 18 P
Tenancy dedicated power 74 Y 28 18 P
Tenancy dedicated power 75 Y 28 18 P
Tenancy dedicated power 76 Y 28 18 P
Tenancy dedicated power 77 Y 28 18 P
Tenancy dedicated power 78 Y 28 18 P
Tenancy dedicated power 79 Y 28 18 P
Tenancy dedicated power 80 Y 28 18 P
Tenancy dedicated power 81 Y 28 18 P
Tenancy dedicated power 82 Y 28 18 P
Tenancy dedicated power 83 Y 28 18 P
Tenancy dedicated power 84 Y 28 18 P
Tenancy dedicated power 85 Y 28 18 P
Tenancy dedicated power 86 Y 28 18 P
Tenancy dedicated powerTenancy dedicated power 87 Y 28 18 P
Tenancy dedicated power 88 Y 28 18 P
Tenancy dedicated power 89 Y 28 18 P
Tenancy dedicated power 90 Y 28 18 P
Tenancy dedicated power 91 Y 28 18 P
Tenancy dedicated power 92 Y 28 18 P
Tenancy dedicated power 93 Y 28 18 P
Tenancy dedicated power 94 Y 28 18 P
Tenancy dedicated power 95 Y 28 18 P
Tenancy dedicated power 96 Y 28 18 P
DB1 1 Y 24 16 P
DB1 2 Y 43 38 P
DB1 3 Y 28 18 P
DB1 4 Y 28 15 P
DB1 5 Y 24 16 P
DB1 6 Y 23 16 P
DB1 7 Y 25 17 P
DB1 8 Y 28 18 P
DB1 9 Y 25 17 P
DB1 10 Y 29 17 P
DB1 11 Y 28 18 P
DB1 12 Y 26 17 P
DB1 13 Y 24 16 P
DB1 14 Y 24 16 P
DB1 15 Y 28 18 P
DB1 16 Y 24 17 P
DB1 17 Y 26 19 P
DB1 18 Y 24 16 P
DB1 19 Y 24 16 P
DB1 20 y 25 17 P
DB1 21 Y 25 40 P
DB1 22 Y 29 19 P
DB1 23 Y 24 16 P
DB1 24 Y 32 22 P
DB1 25 Y 24 17 P
DB1 26 y 25 17 P
DB1 27 Y 25 17 P
DB1 28 Y 28 17 P
DB1 29 Y 24 15 P
DB1 30 Y 24 16 P
DB1 31 Y 24 18 P
DB1 32 Y 30 19 P
DB1 33 Y 28 18 P
DB1 34 Y 24 17 P
DB1 35 y 24 17 P
DB1 36 Y 25 16 P
DB1 37 Y 29 31 P
DB1DB1 38 Y 26 17 P
DB1 39 Y 23 15 P
DB1 40 Y 25 17 P
DB1 41 Y 28 28 P
DB1 42 y 24 16 P
DB1 43 Y 23 32 P
DB1 44 Y 29 19 P
DB1 45 Y 29 19 P
DB1 46 Y 25 17 P
DB1 47 Y 23 18 P
DB1 48 Y 25 17 P
DB1 49 y 27 19 P
DB1 50 y 24 16 P
DB1 51 Y 25 16 P
DB1 52 y 28 18 P
DB1 53 y 28 20 P
DB1 54 Y 28 19 P
DB1 55 Y 24 16 P
DB1 56 y 29 19 P
DB1 57 Y 25 18 P
DB1 58 y 24 16 P
DB1 59 Y 28 18 P
DB1 60 Y 28 18 P
DB1 61 Y 32 22 P
DB1 63 Y 32 22 P
DB1 65 Y 11 19 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
6 R Y Y Y P
7 R Y Y Y P
8 R Y Y Y P
9 S Y Y Y P
10 S Y Y Y P
11 S Y Y Y P
12 S Y Y Y P
14 S Y Y Y P
15 S Y Y Y P
16 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
1 Y Y Y P
2 Y Y Y P
3 Y Y Y P
4 Y Y Y P
5 Y Y Y P
13 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
LED high-bay Y
LED track lights Y
Exit light Y
Surface mount emergency light Y
Recessed emergency light Y
LED downlight Y
Are there any Warranty items needing to be repaired?Yes
WARRANTY
Defect Item Location of Item (on premises) Quantity Details of fault/problem Manufacturer Part Number Repaired on Site Comments
LED high-bay Above fridges 2 Failed to illuminate Davis Lighting UFO150EA5K3B09 N Scissor lift required / to be completed on warranty job number 69118
LED high-bay Above ovens/kitchen display 2 Failed to illuminate Davis Lighting UFO150EA5K3B09 N Scissor lift required / to be completed on warranty job number 69118
LED high-bay Above washing machine 1 Failed to illuminate Davis Lighting UFO150EA5K3B09 N Scissor lift required / to be completed on warranty job number 69118
Site Status SelectorStore now fully compliant
Next Test Due in 6 months16/03/2023