Partner Name | Sturdie Trade Services |
---|
State | VIC |
---|
Date of Visit | 26/09/2022 |
---|
Technician's Name | Nathan McBain |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 67216 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in VIC | northland |
---|
|
|
---|
Location Name | Preston (Northland) |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
DB-1 |
1 |
Y |
25 |
19 |
P |
|
|
DB-1 |
2 |
Y |
28 |
18 |
P |
|
|
DB-1 |
3 |
Y |
25 |
16 |
P |
|
|
DB-1 |
4 |
Y |
28 |
18 |
P |
|
|
DB-1 |
5 |
Y |
25 |
16 |
P |
|
|
DB-1 |
6 |
Y |
28 |
18 |
P |
|
|
DB-1 |
7 |
Y |
28 |
18 |
P |
|
|
DB-1 |
8 |
Y |
28 |
18 |
P |
|
|
DB-1 |
9 |
Y |
26 |
16 |
P |
|
|
DB-1 |
10 |
Y |
28 |
18 |
P |
|
|
DB-1 |
11 |
Y |
26 |
17 |
P |
|
|
DB-1 |
12 |
Y |
28 |
18 |
P |
|
|
DB-1 |
13 |
Y |
26 |
18 |
P |
|
|
DB-1 |
14 |
Y |
28 |
18 |
P |
|
|
DB-1 |
15 |
Y |
28 |
18 |
P |
|
|
DB-1 |
16 |
Y |
28 |
18 |
P |
|
|
DB-1 |
17 |
Y |
24 |
15 |
P |
|
|
DB-1 |
18 |
Y |
28 |
18 |
P |
|
|
DB-1 |
19 |
Y |
28 |
18 |
P |
|
|
DB-1 |
20 |
Y |
28 |
18 |
P |
|
|
DB-1 |
21 |
Y |
28 |
18 |
P |
|
|
DB-1 |
22 |
Y |
28 |
18 |
P |
|
|
DB-1 |
23 |
Y |
28 |
18 |
P |
|
|
DB-1 |
24 |
Y |
28 |
18 |
P |
|
|
DB-1 |
25 |
Y |
25 |
33 |
P |
|
|
DB-1 |
26 |
Y |
28 |
18 |
P |
|
|
DB-1 |
27 |
Y |
24 |
19 |
P |
|
|
DB-1 |
28 |
Y |
28 |
18 |
P |
|
|
DB-1 |
29 |
Y |
28 |
19 |
P |
|
|
DB-1 |
30 |
Y |
28 |
18 |
P |
|
|
DB-1 |
31 |
Y |
28 |
18 |
P |
|
|
DB-1 |
32 |
Y |
28 |
18 |
P |
|
|
DB-1 |
33 |
Y |
23 |
33 |
P |
|
|
DB-1 |
34 |
Y |
28 |
18 |
P |
|
|
DB-1 |
35 |
Y |
28 |
18 |
P |
|
|
DB-1 |
37 |
Y |
28 |
18 |
P |
|
|
DB-1 |
38 |
Y |
24 |
18 |
P |
|
|
DB-1 |
39 |
Y |
28 |
18 |
P |
|
|
DB-1 |
40 |
Y |
28 |
18 |
P |
|
|
DB-1 |
41 |
Y |
25 |
16 |
P |
|
|
DB-1 |
42 |
Y |
28 |
18 |
P |
|
|
DB-1 |
43 |
Y |
24 |
17 |
P |
|
|
DB-1 |
45 |
Y |
28 |
18 |
P |
|
|
DB-1 |
47 |
Y |
24 |
15 |
P |
|
|
DB-1 |
49 |
Y |
28 |
18 |
P |
|
|
DB-1 |
50 |
Y |
28 |
18 |
P |
|
|
DB-1 |
51 |
Y |
25 |
16 |
P |
|
|
DB-1 |
52 |
Y |
29 |
19 |
P |
|
|
DB-1 |
53 |
Y |
29 |
15 |
P |
|
|
DB-1 |
54 |
Y |
24 |
34 |
P |
|
|
DB-1 |
55 |
Y |
23 |
18 |
P |
|
|
DB-1 |
57 |
Y |
24 |
15 |
P |
|
|
DB-1 |
59 |
Y |
30 |
21 |
P |
|
|
DB-1 |
61 |
Y |
25 |
17 |
P |
|
|
DB-1 |
63 |
Y |
24 |
21 |
P |
|
|
DB-1 |
65 |
Y |
35 |
35 |
P |
|
|
DB-2 |
1 |
Y |
28 |
18 |
P |
|
|
DB-2 |
2 |
Y |
25 |
16 |
P |
|
|
DB-2 |
3 |
Y |
28 |
18 |
P |
|
|
DB-2 |
4 |
Y |
25 |
19 |
P |
|
|
DB-2 |
5 |
Y |
25 |
17 |
P |
|
|
DB-2 |
6 |
Y |
29 |
19 |
P |
|
|
DB-2 |
7 |
Y |
25 |
16 |
P |
|
|
DB-2 |
8 |
Y |
24 |
19 |
P |
|
|
DB-2 |
9 |
Y |
24 |
19 |
P |
|
|
DB-2 |
10 |
Y |
29 |
17 |
P |
|
|
DB-2 |
11 |
Y |
29 |
19 |
P |
|
|
DB-2 |
12 |
Y |
28 |
18 |
P |
|
|
DB-2 |
13 |
Y |
25 |
16 |
P |
|
|
DB-2 |
14 |
Y |
29 |
22 |
P |
|
|
DB-2 |
15 |
Y |
26 |
17 |
P |
|
|
DB-2 |
16 |
Y |
28 |
18 |
P |
|
|
DB-2 |
17 |
Y |
28 |
18 |
P |
|
|
DB-2 |
18 |
Y |
30 |
20 |
P |
|
|
DB-2 |
19 |
Y |
24 |
15 |
P |
|
|
DB-2 |
20 |
Y |
25 |
17 |
P |
|
|
DB-2 |
21 |
Y |
28 |
18 |
P |
|
|
DB-2 |
22 |
Y |
27 |
20 |
P |
|
|
DB-2 |
23 |
Y |
28 |
18 |
P |
|
|
DB-2 |
24 |
Y |
24 |
16 |
P |
|
|
DB-2 |
25 |
Y |
28 |
18 |
P |
|
|
DB-2 |
26 |
Y |
28 |
21 |
P |
|
|
DB-2 |
27 |
Y |
28 |
18 |
P |
|
|
DB-2 |
28 |
Y |
24 |
16 |
P |
|
|
DB-2 |
29 |
Y |
30 |
20 |
P |
|
|
DB-2 |
30 |
Y |
26 |
18 |
P |
|
|
DB-2 |
31 |
Y |
25 |
17 |
P |
|
|
DB-2 |
32 |
Y |
23 |
16 |
P |
|
|
DB-2 |
33 |
Y |
27 |
15 |
P |
|
|
DB-2 |
34 |
Y |
25 |
18 |
P |
|
|
DB-2 |
35 |
Y |
24 |
16 |
P |
|
|
DB-2 |
36 |
Y |
28 |
18 |
P |
|
|
DB-2 |
37 |
Y |
28 |
18 |
P |
|
|
DB-2 |
38 |
Y |
28 |
18 |
P |
|
|
DB-2 |
39 |
Y |
28 |
18 |
P |
|
|
DB-2 |
40 |
Y |
26 |
17 |
P |
|
|
DB-2 |
41 |
Y |
28 |
18 |
P |
|
|
DB-2 |
42 |
Y |
28 |
18 |
P |
|
|
DB-2 |
43 |
Y |
28 |
18 |
P |
|
|
DB-2 |
44 |
Y |
25 |
19 |
P |
|
|
DB-2 |
45 |
Y |
24 |
16 |
P |
|
|
DB-2 |
46 |
Y |
28 |
18 |
P |
|
|
DB-2 |
48 |
Y |
28 |
18 |
P |
|
|
DB-4 |
1 |
Y |
30 |
18 |
P |
|
|
DB-4 |
3 |
Y |
28 |
18 |
P |
|
|
DB-4 |
5 |
Y |
243 |
247 |
P |
|
|
DB-4 |
7 |
Y |
25 |
17 |
P |
|
|
DB-4 |
9 |
Y |
32 |
23 |
P |
|
|
DB-4 |
11 |
Y |
30 |
20 |
P |
|
|
DB-4 |
13 |
Y |
28 |
18 |
P |
|
|
DB-4 |
15 |
Y |
28 |
18 |
P |
|
|
DB-4 |
17 |
Y |
28 |
18 |
P |
|
|
DB-4 |
19 |
Y |
28 |
18 |
P |
|
|
DB-4 |
21 |
Y |
28 |
18 |
P |
|
|
DB-4 |
23 |
Y |
28 |
19 |
P |
|
|
DB-4 |
24 |
Y |
28 |
18 |
P |
|
|
DB-4 |
25 |
Y |
28 |
18 |
P |
|
|
DB-4 |
26 |
Y |
28 |
18 |
P |
|
|
DB-4 |
27 |
Y |
28 |
18 |
P |
|
|
DB-4 |
28 |
Y |
28 |
18 |
P |
|
|
DB-4 |
29 |
Y |
28 |
18 |
P |
|
|
DB-4 |
30 |
Y |
28 |
18 |
P |
|
|
DB-4 |
31 |
Y |
28 |
18 |
P |
|
|
DB-4 |
32 |
Y |
29 |
19 |
P |
|
|
DB-4 |
34 |
Y |
29 |
20 |
P |
|
|
DB-4 |
36 |
Y |
28 |
16 |
P |
|
|
DB-3 |
1 |
Y |
24 |
18 |
P |
|
|
DB-3 |
2 |
Y |
28 |
18 |
P |
|
|
DB-3 |
3 |
Y |
28 |
19 |
P |
|
|
DB-3 |
4 |
Y |
30 |
20 |
P |
|
|
DB-3 |
5 |
Y |
28 |
18 |
P |
|
|
DB-3 |
6 |
Y |
28 |
18 |
P |
|
|
DB-3 |
7 |
Y |
28 |
19 |
P |
|
|
DB-3 |
8 |
Y |
31 |
21 |
P |
|
|
DB-3 |
9 |
Y |
30 |
20 |
P |
|
|
DB-3 |
10 |
Y |
29 |
19 |
P |
|
|
DB-3 |
11 |
Y |
29 |
19 |
P |
|
|
DB-3 |
15r |
Y |
17 |
7 |
P |
|
|
DB-3 |
15w |
Y |
17 |
7 |
P |
|
|
DB-3 |
15b |
Y |
17 |
7 |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB1 |
2 |
R |
Y |
Y |
Y |
P |
|
|
|
|
5 |
R |
Y |
Y |
Y |
P |
|
|
|
|
6 |
R |
Y |
Y |
Y |
P |
|
|
|
|
7 |
R |
Y |
Y |
Y |
P |
|
|
|
|
8 |
R |
Y |
Y |
Y |
P |
|
|
|
|
9 |
R |
Y |
Y |
Y |
P |
|
|
|
|
11 |
R |
Y |
Y |
Y |
P |
|
|
|
|
14 |
R |
Y |
Y |
Y |
P |
|
|
|
|
17 |
R |
Y |
Y |
Y |
P |
|
|
|
|
18 |
R |
Y |
Y |
Y |
P |
|
|
|
|
19 |
R |
Y |
Y |
Y |
P |
|
|
|
|
20 |
R |
Y |
Y |
Y |
P |
|
|
|
|
21 |
R |
Y |
Y |
Y |
P |
|
|
|
|
24 |
R |
Y |
N |
Y |
F |
FAILED 90MIN DISCHARGE TEST |
Y |
N |
|
25 |
R |
Y |
Y |
Y |
P |
|
|
|
|
26 |
R |
Y |
Y |
Y |
P |
|
|
|
|
28 |
R |
Y |
Y |
Y |
P |
|
|
|
|
32 |
R |
Y |
Y |
Y |
P |
|
|
|
|
33 |
R |
Y |
Y |
Y |
P |
|
|
|
|
34 |
R |
Y |
Y |
Y |
P |
|
|
|
|
36 |
R |
Y |
Y |
Y |
P |
|
|
|
|
38 |
R |
Y |
Y |
Y |
P |
|
|
|
|
39 |
R |
Y |
Y |
Y |
P |
|
|
|
|
40 |
R |
Y |
Y |
Y |
P |
|
|
|
|
42 |
R |
Y |
Y |
Y |
P |
|
|
|
|
43 |
R |
Y |
Y |
Y |
P |
|
|
|
|
44 |
R |
Y |
Y |
Y |
P |
|
|
|
|
45 |
R |
Y |
Y |
Y |
P |
|
|
|
|
46 |
R |
Y |
N |
Y |
F |
FAILED 90MIN DISCHARGE TEST |
Y |
N |
|
47 |
R |
Y |
Y |
Y |
P |
|
|
|
|
48 |
R |
Y |
Y |
Y |
P |
|
|
|
|
49 |
R |
Y |
Y |
Y |
P |
|
|
|
|
51 |
R |
Y |
Y |
Y |
P |
|
|
|
|
54 |
S |
Y |
Y |
Y |
P |
|
|
|
|
55 |
S |
Y |
Y |
Y |
P |
|
|
|
|
57 |
S |
Y |
Y |
Y |
P |
|
|
|
|
58 |
S |
Y |
Y |
Y |
P |
|
|
|
|
60 |
S |
Y |
Y |
Y |
P |
|
|
|
|
63 |
S |
Y |
Y |
Y |
P |
|
|
|
|
64 |
S |
Y |
Y |
Y |
P |
|
|
|
|
65 |
S |
Y |
Y |
Y |
P |
|
|
|
|
66 |
S |
Y |
Y |
Y |
P |
|
|
|
|
67 |
R |
Y |
Y |
Y |
P |
|
|
|
|
69 |
S |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB1 |
3 |
Y |
Y |
Y |
P |
|
|
|
|
10 |
Y |
Y |
Y |
P |
|
|
|
|
13 |
Y |
Y |
Y |
P |
|
|
|
|
31 |
Y |
Y |
Y |
P |
|
|
|
|
35 |
Y |
Y |
Y |
P |
|
|
|
|
37 |
Y |
Y |
Y |
P |
|
|
|
|
41 |
Y |
Y |
Y |
P |
|
|
|
|
50 |
Y |
Y |
Y |
P |
|
|
|
|
53 |
Y |
Y |
Y |
P |
|
|
|
|
56 |
Y |
Y |
Y |
P |
|
|
|
|
59 |
Y |
Y |
Y |
P |
|
|
|
|
61 |
Y |
Y |
Y |
P |
|
|
|
|
62 |
Y |
Y |
Y |
P |
|
|
|
|
68 |
Y |
Y |
Y |
P |
|
|
|
|
70 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
TRI LED TUBED TROFFERS (BOH) |
|
LED HIGHBAYS |
|
LED PANEL LIGHTS |
|
70MM LED DOWNLIGHT |
|
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
EM24 |
MICROSOFT SURFACE |
1 |
FAILED 90MIN DISCHARGE TEST |
Y |
N |
N |
REPLACED |
EM46 |
STAFF HALLWAY BETWEEN COMMS ROOM AND TOILETS |
1 |
FAILED 90MIN DISCHARGE TEST |
Y |
N |
N |
REPLACED |
PANEL LIGHT |
FRONT COUNTER |
1 |
FAILED TO ILLUMINATE |
Y |
N |
N |
REPLACED |
PANEL LIGHT |
PRINTERS |
1 |
FAILED TO ILLUMINATE |
Y |
N |
N |
REPLACED |
PANEL LIGHT |
WEBER |
1 |
FAILED TO ILLUMINATE |
Y |
N |
N |
PLUG WAS PUT BACK IN POSITION |
TEST AND TAG |
STORE |
80+ |
TEST AND TAG IN-DATE, RETEST DUE 11 MARCH 2023 |
N |
N |
N |
OBSERVATION |
DAMAGED CEILING TILES |
TAPS(1)/ SEASONAL(5)/GAMING (1)/ MIXERS(2)/ FRONT ENTRANCE (1) |
10 |
DAMAGED CEILING TILES/ WATER DAMAGE |
N |
N |
N |
OBSERVATION |
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 26/03/2023 |
---|
| |
---|
| |