Partner NameBuilt Services
StateSA
Date of Visit27/09/2022
Technician's NameAntonio Portolesi
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number67286
EmailEmail hidden; Javascript is required.
The Good Guys Site in SAmarion

Location NameMarion
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
mdbt2 R5 Y 19 19 P
mdbt2 W5 Y 19 19 P
mdbt2 B5 Y 30 28 P
mdbt2 R7 Y 17 16 P
mdbt2 W7 Y 19 19 P
mdbt2 R19 Y 29 19 P
mdbt2 W19 Y 17 17 P
mdbt2 B19 Y 16 16 P
mdbt2 R21 Y 18 17 P
mdbt2 W21 Y 21 21 P
mdbt2 W23 Y 25 25 P
mdbt2 B23 Y 20 18 P
mdbt2 R25 Y 34 28 P
mdbt2 W25 Y 83 64 P
mdbt2 B25 Y 22 22 P
mdbt2 R27 Y 21 21 P
mdbt2 W27 Y 24 23 P
mdbt2 W6 Y 32 31 P
mdbt2 B6 Y 34 34 P
mdbt2 R8 Y 40 40 P
mdbt2 W20 Y 16 16 P
mdbt3 W5 Y 19 19 P
mdbt3 B5 Y 19 19 P
mdbt3 R7 Y 17 16 P
mdbt3 W7 Y 19 19 P
mdbt3 B7 Y 17 17 P
mdbt3 W19 Y 18 18 P
mdbt3 B19 Y 23 58 P
mdbt3 R21 Y 22 21 P
mdbt3 W21 Y 29 19 P
mdbt3 B21 Y 25 24 P
mdbt3 R23 Y 38 21 P
mdbt3 W23 Y 17 16 P
mdbt3 B23 Y 16 16 P
mdbt3 R25 Y 26 25 P
mdbt3 W25 Y 29 19 P
mdbt3 R6 Y 29 19 P
mdbt3 R20 Y 29 19 P
mdbt3 W20 Y 31 21 P
mdbt3 B20 Y 33 21 P
mdbt3 R22 Y 30 21 P
mdbt3 W22 Y 24 18 P
mdbt3 B22 Y 29 18 P
mdbt3 R26 Y 29 19 P
mdbt3 W26 Y 23 13 P
mdbt3 B26 Y 29 19 P
mdbt3 R28 Y 24 18 P
mdbt3 W28 Y 16 16 P
dbt2-2 R1 Y 28 29 P
dbt2-2 W1 Y 17 17 P
dbt2-2 B1 Y 17 17 P
dbt2-2 R3 Y 29 19 P
dbt2-2 R21 Y 22 22 P
dbt2-2 W21 Y 17 17 P
dbt2-2 B21 Y 24 24 P
dbt2-2 R23 Y 18 18 P
dbt2-2 W23 Y 43 31 P
dbt2-2 B23 Y 20 20 P
dbt2-2 R25 Y 22 24 P
dbt2-2 W25 Y 21 21 P
dbt2-2 B25 Y 16 17 P
dbt2-2 R27 Y 29 19 P
dbt2-2 W27 Y 24 15 P
dbt2-2 B27 Y 29 19 P
dbt2-2 R29 Y 25 15 P
dbt2-2 R22 Y 21 21 P
dbt2-2 W22 Y 22 22 P
dbt2-2 B22 Y 23 22 P
dbt2-2 R24 Y 16 16 P
dbt2-2 W24 Y 31 20 P
dbt2-2 B24 Y 25 24 P
dbt2-2 R26 Y 21 21 P
dbt2-2 W26 Y 37 24 P
dbt2-2 B26 Y 54 18 P
dbt2-2 R28 Y 24 14 P
dbt2-2 W28 Y 27 17 P
dbt2-2 B28 Y 25 15 P
dbt2-2 R30 Y 28 19 P
dbt2-2 W30 Y 29 18 P
dbt2-2 B30 Y 30 17 P
dbt2-2 R32 Y 38 29 P
dbt3-2 R11 Y 19 18 P
dbt3-2 W11 Y 110 24 P
dbt3-2 B11 Y 16 16 P
dbt3-2 R8 Y 26 17 P
dbt3-2 W8 Y 21 25 P
dbt3-2 B8 Y 17 21 P
dbt3-2 R10 Y 24 23 P
dbt3-2 W10 Y 17 17 P
dbt3-2 B10 Y 18 18 P
dbt3-2 R12 Y 24 24 P
dbt3-2 W12 Y 20 21 P
dbt3-2 B12 Y 17 17 P
dbt3-2 R14 Y 17 17 P
dbt3-2 W14 Y 16 17 P
dbt3-2 B14 Y 17 17 P
dbt3-2 W16 Y 17 17 P
dbt3-2 B16 Y 17 16 P
dbt3-2 R18 Y 16 16 P
dbt3-2 W18 Y 19 19 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 1 S N Y Y F T8 36W LAMP NOT ILLUMINATING Y N
DB 2 S Y Y Y P
DB 3 S N Y Y F T8 36W LAMP NOT ILLUMINATING Y N
DB 4 S N Y Y F T8 36W LAMP NOT ILLUMINATING Y N
DB 5 S N Y Y F T8 36W LAMP NOT ILLUMINATING Y N
DB 6 S N Y Y F T8 36W LAMP NOT ILLUMINATING Y N
DB 7 S Y Y Y P
DB 8 S N Y Y F T8 36W LAMP NOT ILLUMINATING Y N
DB 9 S N Y Y F T8 36W LAMP NOT ILLUMINATING Y N
DB 10 S Y Y Y P
DB 11 S Y Y Y P
DB 12 S Y Y Y P
DB 13 S N Y Y F T8 36W LAMP NOT ILLUMINATING Y N
DB 14 S N Y Y F T8 36W LAMP NOT ILLUMINATING Y N
DB 15 RR Y Y Y P
DB 16 RR Y Y Y P
DB 17 RR Y Y Y P
DB 18 RR Y Y Y P
DB 19 RR Y Y Y P
DB 20 RR Y Y Y P
DB 21 S Y Y Y P
DB 22 S Y Y Y P
DB 23 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 1 Y Y Y P
DB 2 Y Y Y P
DB 3 Y Y Y P
DB 3A Y Y Y P
DB 4 Y Y Y P
DB 5 Y Y Y P
DB 6 Y Y Y P
DB 7 Y Y Y P
DB 8 Y Y Y P
DB 9 Y Y Y P
DB 10 Y Y Y P
DB 11 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auNo
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
SURFACE MOUNT T8 2X36W PANEL LIGHT Y
RECESSED T8 PANEL LIGHT Y
90MM LED DOWNLIGHT Y
HIGH BAYS - ROUND FLOURESCENT TUBES Y
T5 SINGLE BATTEN FLOURESCENT BATTENS Y
Are there any Warranty items needing to be repaired?No
WARRANTY
Defect Item Location of Item (on premises) Quantity Details of fault/problem Manufacturer Part Number Repaired on Site Comments
SURFACE MOUNT EMERGENCY LIGHT #4 1 FAULTY LVX SURFACE MOUNT EMERGENCY Y
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
SURFACE MOUNT EMERGENCY LIGHT #1 #3 #5 #6 #8 #9 #13 #14 9 LAMP NOT ILLUMINATING Y N N SCISSOR AND SPOTTER REQUIRED
Site Status SelectorStore now fully compliant
Next Test Due in 6 months27/03/2023