Partner NameBuilt Services
StateSA
Date of Visit28/09/2022
Technician's NameAntonio Portolesi
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number67287
EmailEmail hidden; Javascript is required.
The Good Guys Site in SAgepps_cross

Location NameGepps Cross
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
MDB-T46 R3 Y 22 22 P
MDB-T46 W5 Y 10 10 P
MDB-T46 B5 Y 17 18 P
MDB-T46 R9 Y 48 52 P
MDB-T46 R13 Y 10 10 P
MDB-T46 W13 Y 10 10 P
MDB-T46 B13 Y 15 15 P
MDB-T46 R15 Y 11 11 P
MDB-T46 W15 Y 11 11 P
MDB-T46 B15 Y 11 10 P
MDB-T46 R17 Y 10 10 P
MDB-T46 W17 Y 11 11 P
MDB-T46 B17 Y 16 16 P
MDB-T46 R2 Y 12 12 P
MDB-T46 W2 Y 12 12 P
MDB-T46 B2 Y 12 12 P
MDB-T46 R4 Y 10 11 P
MDB-T46 W4 Y 11 11 P
MDB-T46 B4 Y 11 12 P
MDB-T46 R6 Y 12 12 P
MDB-T46 W6 Y 11 11 P
MDB-T46 B6 Y 12 12 P
MDB-T46 R8 Y 10 11 P
MDB-T46 W8 Y 10 13 P
MDB-T46 B8 Y 10 10 P
MDB-T46 R10 Y 11 11 P
MDB-T46 W10 Y 12 11 P
MDB-T46 B10 Y 25 10 P
MDB-T46 R12 Y 11 11 P
MDB-T46 W12 Y 26 11 P
MDB-T46 B12 Y 24 38 P
MDB-T46 R14 Y 17 11 P
MDB-T46 W14 Y 12 26 P
MDB-T46 B14 Y 10 24 P
MDB-T46 R16 Y 10 17 P
MDB-T46 W16 Y 10 11 P
MDB-T46 B16 Y 10 10 P
MDB-T46 R18 Y 11 10 P
MDB-T46 W18 Y 29 10 P
MDB-T46 B18 Y 13 10 P
MDB-T46 R20 Y 10 11 P
MDB-T46 W20 Y 12 19 P
MDB-T46 B20 Y 10 11 P
MDB-T46 R22 Y 10 10 P
MDB-T46 W22 Y 12 13 P
MDB-T46 B22 Y 11 10 P
MDB-T46 R24 Y 12 10 P
MDB-T46 W24 Y 10 11 P
MDB-T46 B24 Y 16 16 P
DB-1 R1 Y 10 11 P
DB-1 W1 Y 13 12 P
DB-1 B1 Y 19 13 P
DB-1 R2 Y 13 12 P
DB-1 W2 Y 13 13 P
DB-1 B2 Y 10 12 P
DB-1 R3 Y 29 29 P
DB-1 W3 Y 13 13 P
DB-1 B3 Y 10 11 P
DB-1 R4 Y 10 10 P
DB-1 W4 Y 10 10 P
DB-1 B4 Y 10 11 P
DB-1 R5 Y 10 12 P
DB-1 W5 Y 10 10 P
DB-1 B5 Y 18 17 P
DB-1 R6 Y 12 12 P
DB-1 W6 Y 19 18 P
DB-1 B6 Y 13 13 P
DB-1 R7 Y 26 26 P
DB-1 W7 Y 31 31 P
DB-1 B7 Y 10 10 P
DB-1 W8 Y 10 10 P
DB-1 B8 Y 12 12 P
DB-1 R9 Y 12 12 P
DB-1 W9 Y 12 12 P
DB-1 B9 Y 15 15 P
DB-1 R11 Y 10 10 P
DB-1 W11 Y 10 10 P
DB-1 B11 Y 12 12 P
DB-1 R12 Y 21 21 P
DB-1 W12 Y 11 11 P
DB-1 B12 Y 11 11 P
DB-1 R13 Y 11 11 P
DB-1 W13 Y 12 12 P
DB-1 B13 Y 17 17 P
DB-1 R14 Y 12 12 P
DB-1 W14 Y 12 12 P
DB-1 B14 Y 12 12 P
DB-1 R15 Y 11 10 P
DB-1 W15 Y 14 16 P
DB-1 R16 Y 31 32 P
DB-1 W16 Y 16 15 P
DB-1 R17 Y 23 23 P
DB-1 W17 Y 43 39 P
DB-1 B17 Y 31 31 P
DB-1 W18 Y 30 30 P
DB-1 B18 Y 24 24 P
DB-1 R19 Y 31 31 P
DB-1 W19 Y 29 29 P
DB-1 B19 Y 24 24 P
DB-1 R20 Y 30 30 P
DB-1 W20 Y 23 23 P
DB-1 B20 Y 19 19 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MDB-T46 BOH 1 S Y Y Y P
MDB-T46 BOH 2 S Y Y Y P
MDB-T46 BOH 3 S Y Y Y P
MDB-T46 BOH 4 S Y Y Y P
MDB-T46 BOH 5 S Y Y Y P
MDB-T46 BOH 6 S Y Y Y P
MDB-T46 6 R Y Y Y P
MDB-T46 7 R Y Y Y P
MDB-T46 10 S Y Y Y P
MDB-T46 11 S Y Y Y P
MDB-T46 12 S Y Y Y P
MDB-T46 14 S Y Y Y P
MDB-T46 15 S Y Y Y P
MDB-T46 16 S Y Y Y P
MDB-T46 17 S Y Y Y P
MDB-T46 18 S Y Y Y P
MDB-T46 19 S Y Y Y P
MDB-T46 20 S Y Y Y P
MDB-T46 21 S Y Y Y P
MDB-T46 22 S Y Y Y P
MDB-T46 24 S Y Y Y P
MDB-T46 25 S Y Y Y P
MDB-T46 27 S Y Y Y P
MDB-T46 28 S N N Y F Failed 90 Min Test Y N
MDB-T46 29 S Y Y Y P
MDB-T46 31 S Y Y Y P
MDB-T46 32 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MDB-T46 2 Y Y Y P
MDB-T46 3 Y Y Y P
MDB-T46 4 Y Y Y P
MDB-T46 8 Y Y Y P
MDB-T46 23 Y Y Y P
MDB-T46 26 Y Y Y P
MDB-T46 30 Y Y Y P
MDB-T46 33 Y Y Y P
MDB-T46 40 Y Y Y P
MDB-T46 41 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
600X600 LED PANELS Y
LED UFO HIGHBAYS Y
DOUBLE DIFFUSED 36W T8 FLUROS Y
70MM DOWNLIGHTS Y
LED STRIP LIGHTING Y
DOUBLE DIFFUSED EMG FLUROS Y
90MM LED DOWNLIGHTS Y
56W DOUBLE WATERPROOF FLUROS YU
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Surface Mount Emergency #28 1 Not illuminating Y N N Scissor Required
Site Status SelectorStore now fully compliant
Next Test Due in 6 months28/03/2023