Partner Name | Built Services |
---|
State | NSW |
---|
Date of Visit | 20/10/2022 |
---|
Technician's Name | Josh Bennison |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 67333 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in NSW | port_macquarie |
---|
|
|
---|
Location Name | Port Macquarie |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
DB01 |
6 |
Y |
27.90 |
37.90 |
P |
|
|
|
7 |
Y |
26.90 |
36.90 |
P |
|
|
|
26 |
Y |
38.90 |
38.90 |
P |
|
|
|
39 |
Y |
40.90 |
40.90 |
P |
|
|
|
40 |
Y |
40.90 |
40.90 |
P |
|
|
|
41 |
Y |
40.90 |
41.90 |
P |
|
|
|
42 |
Y |
40.90 |
40.90 |
P |
|
|
|
43 |
Y |
47.90 |
38.90 |
P |
|
|
|
44 |
Y |
44.90 |
45.90 |
P |
|
|
|
45 |
Y |
39.90 |
39.90 |
P |
|
|
|
46 |
Y |
37.90 |
38.90 |
P |
|
|
|
47 |
Y |
44.90 |
44.90 |
P |
|
|
|
48 |
Y |
40.90 |
49.90 |
P |
|
|
|
49 |
Y |
80.90 |
80.90 |
P |
|
|
|
50 |
Y |
80.90 |
79.90 |
P |
|
|
|
51 |
Y |
19.90 |
29.90 |
P |
|
|
|
52 |
Y |
15.90 |
24.90 |
P |
|
|
|
53 |
Y |
16.90 |
26.90 |
P |
|
|
|
54 |
Y |
78.90 |
83.90 |
P |
|
|
DB02 |
1 |
Y |
8.90 |
16.90 |
P |
|
|
|
2 |
Y |
10.90 |
16.90 |
P |
|
|
|
3 |
Y |
11.90 |
20.90 |
P |
|
|
|
4 |
Y |
11.90 |
18.90 |
P |
|
|
|
5 |
Y |
7.90 |
14.90 |
P |
|
|
|
6 |
Y |
8.90 |
16.90 |
P |
|
|
|
7 |
Y |
10.90 |
19.90 |
P |
|
|
|
8 |
Y |
10.90 |
20.90 |
P |
|
|
|
9 |
Y |
10.90 |
20.90 |
P |
|
|
|
10 |
Y |
7.90 |
18.90 |
P |
|
|
|
11 |
Y |
6.90 |
16.90 |
P |
|
|
|
12 |
Y |
6.90 |
16.90 |
P |
|
|
|
13 |
Y |
8.90 |
17.90 |
P |
|
|
|
14 |
Y |
10.90 |
17.90 |
P |
|
|
|
15 |
Y |
8.90 |
18.90 |
P |
|
|
|
16 |
Y |
10.90 |
19.90 |
P |
|
|
|
17 |
Y |
11.90 |
17.90 |
P |
|
|
|
18 |
Y |
10.90 |
17.90 |
P |
|
|
|
19 |
Y |
11.90 |
21.90 |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB01 |
1 |
S |
Y |
Y |
Y |
P |
|
|
|
|
2 |
S |
Y |
Y |
Y |
P |
|
|
|
|
3 |
S |
Y |
Y |
Y |
P |
|
|
|
|
4 |
S |
Y |
Y |
Y |
P |
|
|
|
|
5 |
S |
Y |
Y |
Y |
P |
|
|
|
|
6 |
S |
Y |
Y |
Y |
P |
|
|
|
|
7 |
S |
Y |
Y |
Y |
P |
|
|
|
|
8 |
S |
Y |
Y |
Y |
P |
|
|
|
|
9 |
S |
Y |
Y |
Y |
P |
|
|
|
|
10 |
S |
Y |
Y |
Y |
P |
|
|
|
|
11 |
S |
Y |
Y |
Y |
P |
|
|
|
|
12 |
S |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB01 |
1 |
Y |
Y |
Y |
P |
|
|
|
|
6 |
Y |
Y |
Y |
P |
|
|
|
|
7 |
Y |
Y |
Y |
P |
|
|
|
|
8 |
Y |
Y |
Y |
P |
|
|
|
|
9 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
200W Square Fluoro |
Y |
200W High Bay Fluoro |
Y |
36W Single Fluoro with LED Tubes |
Y |
2x36W Fluoro Fittings with LED Tubes |
Y |
2x28W Fluoro Fitting |
Y |
18W Fluoro Fitting |
Y |
30W Fluoro Fitting |
Y |
36W Emergency Maintained Fluoro |
Y |
LED Exit Light |
Y |
Twin Halogen Spot Emergency Floodlight |
Y |
LED Spitfire |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 29/04/2023 |
---|
| |
---|
| |