Partner Name | Built Services |
---|
State | NSW |
---|
Date of Visit | 17/11/2022 |
---|
Technician's Name | Peter Tsoukarellis |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 66883 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in NSW | penrith |
---|
|
|
---|
Location Name | Penrith |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
Main |
1 |
Y |
42 |
32 |
P |
|
|
|
2 |
Y |
35 |
26 |
P |
|
|
|
3 |
Y |
29 |
19 |
P |
|
|
|
4 |
Y |
28 |
18 |
P |
|
|
|
5 |
Y |
29 |
18 |
P |
|
|
|
6 |
Y |
24 |
17 |
P |
|
|
|
7 |
Y |
26 |
20 |
P |
|
|
|
8 |
Y |
25 |
19 |
P |
|
|
|
9 |
Y |
29 |
19 |
P |
|
|
|
10 |
Y |
25 |
19 |
P |
|
|
|
11 |
Y |
24 |
17 |
P |
|
|
|
12 |
Y |
> 300MM |
- |
F |
Failed test |
Y |
|
15 |
Y |
29 |
19 |
p |
|
|
|
16 |
Y |
25 |
17 |
p |
|
|
|
39 |
Y |
29 |
19 |
P |
|
|
|
40 |
Y |
28 |
18 |
P |
|
|
|
41 |
Y |
29 |
19 |
P |
|
|
|
43 |
Y |
28 |
18 |
P |
|
|
|
44 |
Y |
29 |
19 |
P |
|
|
|
45 |
Y |
28 |
18 |
P |
|
|
|
46 |
Y |
18 |
18 |
P |
|
|
|
47 |
Y |
29 |
19 |
P |
|
|
|
48 |
Y |
29 |
19 |
P |
|
|
|
49 |
Y |
29 |
19 |
P |
|
|
|
69 |
Y |
27 |
17 |
P |
|
|
|
70 |
Y |
29 |
22 |
P |
|
|
|
71 |
Y |
28 |
17 |
P |
|
|
|
76 |
Y |
29 |
39 |
P |
|
|
|
77 |
Y |
29 |
39 |
P |
|
|
|
78 |
N |
Faulty |
- |
F |
Failed test |
Y |
|
79 |
Y |
29 |
20 |
P |
|
|
|
80 |
Y |
24 |
33 |
P |
|
|
|
81 |
Y |
29 |
39 |
P |
|
|
|
82 |
Y |
29 |
39 |
P |
|
|
|
83 |
Y |
29 |
39 |
P |
|
|
|
84 |
Y |
29 |
39 |
P |
|
|
|
85 |
Y |
34 |
44 |
P |
|
|
|
86 |
Y |
29 |
40 |
P |
|
|
|
87 |
Y |
29 |
44 |
P |
|
|
|
88 |
Y |
24 |
34 |
P |
|
|
|
89 |
Y |
27 |
37 |
P |
|
|
|
90 |
Y |
29 |
39 |
P |
|
|
|
91 |
Y |
29 |
39 |
P |
|
|
|
92 |
Y |
29 |
39 |
P |
|
|
|
93 |
Y |
29 |
39 |
P |
|
|
|
94 |
Y |
28 |
38 |
P |
|
|
|
95 |
Y |
29 |
39 |
P |
|
|
|
97 |
Y |
29 |
39 |
P |
|
|
|
98 |
Y |
28 |
18 |
P |
|
|
|
99 |
Y |
29 |
39 |
P |
|
|
|
100 |
Y |
29 |
39 |
P |
|
|
|
101 |
Y |
29 |
33 |
P |
|
|
|
102 |
Y |
29 |
39 |
P |
|
|
|
103 |
Y |
29 |
19 |
P |
|
|
|
104 |
Y |
34 |
44 |
P |
|
|
|
105 |
Y |
25 |
17 |
P |
|
|
|
106 |
Y |
25 |
18 |
P |
|
|
|
111 |
Y |
28 |
33 |
P |
|
|
|
112 |
Y |
34 |
48 |
P |
|
|
|
113 |
Y |
25 |
20 |
P |
|
|
|
114 |
Y |
25 |
35 |
P |
|
|
|
115 |
Y |
31 |
21 |
P |
|
|
|
116 |
Y |
29 |
18 |
P |
|
|
|
117 |
Y |
29 |
18 |
P |
|
|
|
118 |
Y |
29 |
18 |
P |
|
|
|
119 |
Y |
25 |
18 |
P |
|
|
|
120 |
Y |
28 |
28 |
P |
|
|
|
121 |
Y |
36 |
41 |
P |
|
|
|
122 |
Y |
29 |
33 |
P |
|
|
|
123 |
Y |
29 |
39 |
P |
|
|
|
124 |
Y |
30 |
39 |
P |
|
|
|
125 |
Y |
24 |
64 |
P |
|
|
|
127 |
Y |
29 |
39 |
P |
|
|
|
128 |
Y |
29 |
19 |
P |
|
|
|
129 |
Y |
29 |
39 |
P |
|
|
|
130 |
Y |
27 |
41 |
P |
|
|
|
131 |
Y |
35 |
45 |
P |
|
|
|
135 |
Y |
29 |
19 |
P |
|
|
|
136 |
Y |
29 |
17 |
P |
|
|
|
137 |
Y |
32 |
21 |
P |
|
|
|
138 |
Y |
26 |
20 |
P |
|
|
|
139 |
Y |
26 |
18 |
P |
|
|
|
140 |
Y |
31 |
20 |
P |
|
|
|
141 |
Y |
24 |
16 |
P |
|
|
|
142 |
Y |
31 |
21 |
P |
|
|
|
143 |
Y |
31 |
19 |
P |
|
|
|
144 |
Y |
37 |
30 |
P |
|
|
|
145 |
Y |
27 |
17 |
P |
|
|
DB 1A |
1 |
Y |
19 |
19 |
p |
|
|
|
2 |
Y |
21 |
20 |
p |
|
|
|
7 |
Y |
19 |
20 |
p |
|
|
|
8 |
Y |
19 |
19 |
P |
|
|
|
9 |
Y |
24 |
24 |
P |
|
|
|
10 |
Y |
19 |
11 |
P |
|
|
|
11 |
Y |
19 |
19 |
P |
|
|
|
12 |
Y |
20 |
18 |
P |
|
|
|
13 |
Y |
19 |
19 |
P |
|
|
|
14 |
Y |
20 |
20 |
P |
|
|
|
15 |
Y |
19 |
20 |
P |
|
|
|
19 |
Y |
18 |
123 |
P |
|
|
|
20 |
Y |
33 |
23 |
P |
|
|
|
21 |
Y |
19 |
18 |
P |
|
|
|
31 |
Y |
18 |
18 |
P |
|
|
|
32 |
Y |
29 |
25 |
P |
|
|
|
33 |
Y |
19 |
19 |
P |
|
|
|
34 |
Y |
31 |
32 |
P |
|
|
|
35 |
Y |
19 |
19 |
P |
|
|
|
36 |
Y |
20 |
19 |
P |
|
|
|
38 |
Y |
20 |
21 |
P |
|
|
|
41 |
Y |
20 |
20 |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB01 - Test Switch |
S1 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S2 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S3 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S4 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S5 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S6 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S7 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S8 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S9 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S10 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S11 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S12 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S13 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S14 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S15 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S16 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S17 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S18 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S19 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S20 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S21 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S22 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S23 |
R |
Y |
Y |
Y |
P |
|
|
|
DB01A - Test Switch |
S24 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S25 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S26 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S27 |
R |
N |
N |
N |
F |
FAILED 90 MIN TEST |
Y |
N |
|
S28 |
|
Y |
Y |
Y |
P |
|
|
|
|
S29 |
|
Y |
Y |
Y |
P |
|
|
|
|
S30 |
|
Y |
Y |
Y |
P |
|
|
|
|
S31 |
|
Y |
Y |
Y |
P |
|
|
|
|
S32 |
|
Y |
Y |
Y |
P |
|
|
|
|
S33 |
|
Y |
|
YY |
P |
|
|
|
|
S34 |
|
Y |
Y |
Y |
P |
|
|
|
|
S35 |
|
Y |
Y |
Y |
P |
|
|
|
|
S36 |
|
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB01 - Test Switch |
EX1 |
Y |
Y |
Y |
P |
|
|
|
|
EX2 |
Y |
Y |
Y |
P |
|
|
|
|
EX3 |
Y |
Y |
Y |
P |
|
|
|
|
EX4 |
Y |
Y |
Y |
P |
|
|
|
|
EX5 |
Y |
Y |
Y |
P |
|
|
|
|
EX6 |
Y |
Y |
Y |
P |
|
|
|
|
EX7 |
Y |
Y |
Y |
P |
|
|
|
|
EX8 |
Y |
Y |
Y |
P |
|
|
|
|
EX9 |
Y |
Y |
Y |
P |
|
|
|
|
EX10 |
Y |
Y |
Y |
P |
|
|
|
|
EX11 |
Y |
Y |
Y |
P |
|
|
|
|
EX12 |
Y |
Y |
Y |
P |
|
|
|
|
EX13 |
Y |
Y |
Y |
P |
|
|
|
|
EX14 |
Y |
Y |
Y |
P |
|
|
|
|
EX15 |
Y |
Y |
Y |
P |
|
|
|
|
EX16 |
Y |
Y |
Y |
P |
|
|
|
|
EX17 |
Y |
Y |
Y |
P |
|
|
|
|
EX24 |
Y |
Y |
Y |
P |
|
|
|
|
EX26 |
Y |
Y |
Y |
P |
|
|
|
DB01A - Test Switch |
EX18 |
Y |
Y |
Y |
P |
|
|
|
|
EX19 |
Y |
Y |
Y |
P |
|
|
|
|
EX20 |
Y |
Y |
Y |
P |
|
|
|
|
EX21 |
Y |
Y |
Y |
P |
|
|
|
|
EX22 |
Y |
Y |
Y |
P |
|
|
|
|
EX23 |
Y |
Y |
Y |
P |
|
|
|
|
EX25 |
Y |
Y |
Y |
P |
|
|
|
|
EX27 |
Y |
Y |
Y |
P |
|
|
|
|
EX28 |
Y |
Y |
Y |
P |
|
|
|
|
EX29 |
Y |
Y |
Y |
P |
|
|
|
|
EX30 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
4ft Twin Fluoro 840 |
Y |
2ft Twin Fluoro 840 |
Y |
Highbays LED 150W |
Y |
35W 865 T5 Single Lights Shop |
Y |
4ft Light x 3 Lamps 36W 860 |
Y |
4ft Twin Lights 840 |
Y |
4ft Twin T5 28W Lamps 865 |
Y |
2 x 3ft LED Strips LPF-40D-12 |
Y |
Entry Circular Long Life ES20W 865 |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
T5 35W TUBES |
SHOP FLOOR |
3 |
NOT WORKING |
Y |
N |
N |
|
HIGH BAY |
BOH |
1 |
NOT WORKING |
Y |
N |
N |
|
RECESSED EMERGECY LIGHT |
#27 |
1 |
FAILED 90 MIN TEST |
Y |
N |
N |
|
EXIT |
#11 |
1 |
CATENARY CABLE HAD BEEN DISLODGED FROM EXIT SIGN |
Y |
N |
N |
REPAIRED CATENARY CABLE |
EXIT |
#14 |
1 |
CATENARY CABLE HAS BEEN DISLODGED FROM EXIT SIGN |
Y |
N |
N |
REPAIRED CATENARY CABLE |
CIRCUIT BREAKER |
#78 - MSB |
1 |
RCBO DOES NOT TRIP |
Y |
N |
N |
|
CIRCUIT BREAKER |
#12 - MSB |
1 |
GREATER THAN 300MM |
Y |
N |
N |
|
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 17/05/2023 |
---|
| |
---|
| |