Partner Name | Built Services |
---|
State | NSW |
---|
Date of Visit | 24/11/2022 |
---|
Technician's Name | Peter Tsoukarellis |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 66882 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in NSW | warrawong |
---|
|
|
---|
Location Name | Warrawong |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
msb light and power |
1 |
Y |
14 |
23 |
P |
|
|
msb light and power |
2 |
Y |
12 |
22 |
P |
|
|
msb light and power |
3 |
Y |
9 |
18 |
P |
|
|
msb light and power |
4 |
Y |
9 |
18 |
P |
|
|
msb light and power |
8 |
Y |
9 |
19 |
P |
|
|
msb light and power |
9 |
Y |
9 |
18 |
P |
|
|
msb light and power |
10 |
Y |
9 |
18 |
P |
|
|
msb light and power |
11 |
Y |
18 |
27 |
P |
|
|
msb light and power |
12 |
Y |
14 |
22 |
P |
|
|
msb light and power |
16 |
Y |
11 |
20 |
P |
|
|
msb light and power |
17 |
Y |
9 |
18 |
P |
|
|
msb light and power |
18 |
Y |
9 |
18 |
P |
|
|
msb light and power |
19 |
Y |
18 |
19 |
P |
|
|
msb light and power |
20 |
Y |
18 |
20 |
P |
|
|
msb light and power |
21 |
Y |
30 |
42 |
P |
|
|
msb light and power |
22 |
Y |
19 |
20 |
P |
|
|
msb light and power |
23 |
Y |
19 |
20 |
P |
|
|
msb light and power |
24 |
Y |
19 |
19 |
P |
|
|
msb light and power |
25 |
Y |
20 |
20 |
P |
|
|
msb light and power |
26 |
Y |
19 |
20 |
P |
|
|
msb light and power |
27 |
Y |
19 |
28 |
P |
|
|
msb light and power |
28 |
Y |
19 |
20 |
P |
|
|
msb light and power |
29 |
Y |
19 |
20 |
P |
|
|
msb light and power |
30 |
Y |
28 |
19 |
P |
|
|
msb light and power |
31 |
Y |
19 |
20 |
P |
|
|
msb light and power |
32 |
Y |
9 |
18 |
P |
|
|
msb light and power |
33 |
Y |
9 |
18 |
P |
|
|
msb light and power |
37 |
Y |
9 |
18 |
P |
|
|
msb light and power |
38 |
Y |
8 |
18 |
P |
|
|
msb light and power |
39 |
Y |
9 |
18 |
P |
|
|
msb light and power |
40 |
Y |
8 |
18 |
P |
|
|
msb light and power |
41 |
Y |
9 |
19 |
P |
|
|
msb light and power |
42 |
Y |
9 |
18 |
P |
|
|
msb light and power |
43 |
Y |
9 |
18 |
P |
|
|
msb light and power |
44 |
Y |
9 |
19 |
P |
|
|
msb light and power |
45 |
Y |
9 |
18 |
P |
|
|
msb light and power |
46 |
Y |
12 |
20 |
P |
|
|
msb light and power |
47 |
Y |
17 |
26 |
P |
|
|
msb light and power |
48 |
Y |
14 |
23 |
P |
|
|
msb light and power |
52 |
Y |
9 |
18 |
P |
|
|
msb light and power |
53 |
Y |
13 |
23 |
P |
|
|
msb light and power |
54 |
Y |
9 |
20 |
P |
|
|
msb light and power |
55 |
Y |
19 |
20 |
P |
|
|
msb light and power |
56 |
Y |
19 |
20 |
P |
|
|
msb light and power |
57 |
Y |
9 |
19 |
P |
|
|
msb light and power |
58 |
Y |
19 |
29 |
P |
|
|
msb light and power |
59 |
Y |
20 |
29 |
P |
|
|
msb light and power |
60 |
Y |
19 |
20 |
P |
|
|
msb light and power |
61 |
Y |
19 |
20 |
P |
|
|
msb light and power |
62 |
Y |
19 |
20 |
P |
|
|
msb light and power |
63 |
Y |
19 |
29 |
P |
|
|
msb light and power |
64 |
Y |
19 |
29 |
P |
|
|
msb light and power |
65 |
Y |
19 |
20 |
P |
|
|
msb light and power |
66 |
Y |
19 |
20 |
P |
|
|
msb light and power |
67 |
Y |
13 |
21 |
P |
|
|
msb light and power |
71 |
Y |
9 |
18 |
P |
|
|
msb light and power |
72 |
Y |
20 |
29 |
P |
|
|
msb selling area a |
1 |
Y |
11 |
21 |
P |
|
|
msb selling area a |
2 |
Y |
13 |
22 |
P |
|
|
msb selling area a |
3 |
Y |
8 |
18 |
P |
|
|
msb selling area a |
4 |
Y |
14 |
23 |
P |
|
|
msb selling area a |
5 |
Y |
14 |
24 |
P |
|
|
msb selling area a |
6 |
Y |
13 |
22 |
P |
|
|
msb selling area a |
10 |
Y |
12 |
22 |
P |
|
|
msb selling area a |
11 |
Y |
12 |
22 |
P |
|
|
msb selling area a |
12 |
Y |
9 |
18 |
P |
|
|
msb selling area a |
13 |
Y |
14 |
23 |
P |
|
|
msb selling area a |
14 |
Y |
10 |
20 |
P |
|
|
msb selling area b |
1 |
Y |
13 |
22 |
P |
|
|
msb selling area b |
2 |
Y |
9 |
18 |
P |
|
|
msb selling area b |
3 |
Y |
13 |
22 |
P |
|
|
msb selling area b |
4 |
Y |
14 |
23 |
P |
|
|
msb selling area b |
5 |
Y |
13 |
22 |
P |
|
|
msb selling area b |
6 |
Y |
13 |
22 |
P |
|
|
msb selling area b |
10 |
Y |
13 |
23 |
P |
|
|
msb selling area b |
11 |
Y |
13 |
22 |
P |
|
|
msb selling area b |
12 |
Y |
11 |
21 |
P |
|
|
msb selling area b |
13 |
Y |
9 |
19 |
P |
|
|
msb selling area b |
14 |
Y |
10 |
20 |
P |
|
|
msb external lighting |
1 |
Y |
10 |
20 |
P |
|
|
msb external lighting |
2 |
N |
NA |
NA |
NA |
RCBO tripped. Fault on circuit. |
Y |
msb external lighting |
3 |
Y |
10 |
20 |
P |
|
|
msb external lighting |
4 |
Y |
58 |
68 |
P |
|
|
msb external lighting |
7 |
Y |
10 |
20 |
P |
|
|
DB1 |
1 |
Y |
78 |
89 |
P |
|
|
DB1 |
2 |
Y |
30 |
38 |
P |
|
|
DB1 |
3 |
Y |
30 |
30 |
P |
|
|
DB1 |
4 |
Y |
31 |
54 |
P |
|
|
DB1 |
5 |
Y |
30 |
20 |
P |
|
|
DB1 |
6 |
Y |
78 |
50 |
P |
|
|
DB1 |
7 |
Y |
30 |
30 |
P |
|
|
DB1 |
8 |
Y |
38 |
38 |
P |
|
|
DB1 |
9 |
Y |
38 |
38 |
P |
|
|
DB1 |
10 |
Y |
45 |
45 |
P |
|
|
DB1 |
11 |
Y |
76 |
56 |
P |
|
|
DB1 |
12 |
Y |
- |
- |
F |
RCBO Fault |
Y |
DB1 |
13 |
Y |
57 |
36 |
P |
|
|
DB1 |
14 |
Y |
70 |
40 |
P |
|
|
DB1 |
15 |
Y |
29 |
20 |
P |
|
|
DB1 |
16 |
Y |
29 |
21 |
P |
|
|
DB1 |
17 |
Y |
38 |
38 |
P |
|
|
DB1 |
18 |
Y |
- |
- |
F |
RCBO Fault |
Y |
DB1 |
19 |
Y |
39 |
20 |
P |
|
|
DB1 |
20 |
Y |
90 |
62 |
P |
|
|
DB1 |
21 |
Y |
30 |
20 |
P |
|
|
DB1 |
22 |
Y |
30 |
29 |
P |
|
|
DB1 |
23 |
Y |
38 |
38 |
P |
|
|
DB1 |
24 |
Y |
23 |
28 |
P |
|
|
DB1 |
25 |
Y |
28 |
43 |
P |
|
|
DB1 |
26 |
Y |
39 |
44 |
P |
|
|
DB1 |
27 |
Y |
23 |
24 |
P |
|
|
DB1 |
28,30,32 |
Y |
36 |
28 |
P |
|
|
DB1 |
29 |
Y |
29 |
59 |
P |
|
|
DB1 |
31 |
Y |
38 |
38 |
P |
|
|
DB2 |
1 |
Y |
28 |
20 |
P |
|
|
DB2 |
2 |
Y |
33 |
26 |
P |
|
|
DB2 |
3 |
Y |
29 |
20 |
P |
|
|
DB2 |
4 |
Y |
29 |
20 |
P |
|
|
DB2 |
5 |
Y |
22 |
19 |
P |
|
|
DB2 |
6 |
Y |
23 |
19 |
P |
|
|
DB2 |
7 |
Y |
29 |
19 |
P |
|
|
DB2 |
8 |
Y |
36 |
30 |
P |
|
|
DB2 |
9 |
Y |
29 |
20 |
P |
|
|
DB2 |
10 |
Y |
27 |
19 |
P |
|
|
DB2 |
11 |
Y |
29 |
21 |
P |
|
|
DB2 |
12 |
Y |
30 |
20 |
P |
|
|
DB2 |
13 |
Y |
49 |
19 |
P |
|
|
DB2 |
14 |
Y |
28 |
18 |
P |
|
|
DB2 |
15 |
Y |
29 |
20 |
P |
|
|
DB2 |
16 |
Y |
43 |
45 |
P |
|
|
DB2 |
17 |
Y |
29 |
20 |
P |
|
|
DB2 |
18 |
Y |
26 |
20 |
P |
|
|
DB2 |
19 |
Y |
29 |
21 |
P |
|
|
DB2 |
20 |
Y |
49 |
45 |
P |
|
|
DB2 |
21 |
Y |
30 |
19 |
P |
|
|
DB2 |
22 |
Y |
23 |
22 |
P |
|
|
DB2 |
23 |
Y |
34 |
46 |
P |
|
|
DB2 |
24 |
Y |
29 |
20 |
P |
|
|
DB2 |
25 |
Y |
34 |
24 |
P |
|
|
DB2 |
26 |
Y |
24 |
20 |
P |
|
|
DB2 |
27 |
Y |
29 |
20 |
P |
|
|
DB2 |
28 |
Y |
23 |
19 |
P |
|
|
DB2 |
29 |
Y |
20 |
29 |
P |
|
|
DB2 |
30 |
Y |
35 |
44 |
P |
|
|
DB2 |
31 |
Y |
28 |
33 |
P |
|
|
DB2 |
32 |
Y |
26 |
19 |
P |
|
|
DB2 |
33 |
Y |
29 |
44 |
P |
|
|
DB2 |
35 |
Y |
29 |
20 |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
MSB |
EM1 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM2 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM3 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM4 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM5 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM6 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM7 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM8 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM9 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM10 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM11 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM12 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM13 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM14 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM15 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM16 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM17 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM18 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM19 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM20 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM21 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM22 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM23 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM24 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM25 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM30 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM33 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM35 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM38 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM39 |
|
Y |
Y |
Y |
P |
|
|
|
|
EM40 |
|
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
MSB |
EX1 |
Y |
Y |
Y |
P |
|
|
|
|
EX2 |
Y |
Y |
Y |
P |
|
|
|
|
EX3 |
Y |
Y |
Y |
P |
|
|
|
|
EX4 |
Y |
Y |
Y |
P |
|
|
|
|
EX5 |
Y |
Y |
Y |
P |
|
|
|
|
EX6 |
Y |
Y |
Y |
P |
|
|
|
|
EX7 |
Y |
Y |
Y |
P |
|
|
|
|
EX8 |
Y |
Y |
Y |
P |
|
|
|
|
EX9 |
Y |
Y |
Y |
P |
|
|
|
|
EX10 |
Y |
Y |
Y |
P |
|
|
|
|
EX11 |
Y |
Y |
Y |
P |
|
|
|
|
EX12 |
Y |
Y |
Y |
P |
|
|
|
|
EX13 |
Y |
Y |
Y |
P |
|
|
|
|
EX14 |
Y |
Y |
Y |
P |
|
|
|
|
EX15 |
Y |
Y |
Y |
P |
|
|
|
|
EX16 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
Hi Bays Halo Globe |
Y |
50mm LED Downlight |
Y |
Fluoro Pelmet Lights |
Y |
200mm Downlight Folded Fluoro Twin Globe |
Y |
2x30W Caged Fluoro Fitting |
Y |
1x30W Diffused Fluoro Fitting |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
Wall bay fluoro light boxes |
Perimeter of the store |
14 x 3.6 m long light boxes |
some are all out some are working at 50% capacity |
N |
N |
N |
Added to fortnightly repairs list. |
External IP56 power point |
Outside RHS of shop entrance |
1 |
Missing screw top and flap |
Y |
N |
N |
|
Pendant Lights |
Smeg & Technika section |
4 |
Faulty Lamps |
Y |
N |
N |
|
Hisense light |
Refrigerator section |
1 |
Hisense LED light flashing abovr the refrigerator |
Y |
N |
N |
Replaced faulty driver. |
RCBO #12 |
DB-1 |
1 |
Faulty |
Y |
N |
N |
|
RCBO #18 |
DB-1 |
1 |
Faulty |
Y |
N |
N |
|
RCBO # 2 |
MSB |
1 |
Tripped |
Y |
N |
N |
RCD tripped due to faulty low bay light. Light removed, RCD working as usual again. |
External Lights |
External perimeter of the store |
1 |
Not working |
Y |
N |
N |
Traced fault to a faulty low bay light. Removed faulty light, all working as intended. |
Emergency lighting plan |
Logbook Maintenance Folder |
1 |
No plan on site. |
Y |
N |
N |
New lighting plan drawn up on site and placed in folder. |
Weber stand light |
weber section |
1 |
No power to weber light stand |
N |
N |
N |
Supplier funded repairs. Please advise if you wish for Sturdie to repair. |
High Bay Light |
Shop floor |
1 |
Not working |
N |
N |
Y |
Added to fortnightly repairs list. |
Main Office |
Upstairs |
1 x light batten and 1 x emergency spitfire |
Previously removed due to roof water damage |
N |
N |
N |
Please advise once roof has been installed so we can replace lights. |
Haier washing machine |
washing maching section |
1 |
Sign not illuminated |
N |
N |
N |
Supplier funded repairs. Please advise if you wish for Sturdie to repair. |
Fisher & Paykel |
washing machine section |
1 |
Sign not illuminated |
N |
N |
N |
Supplier funded repairs. Please advise if you wish for Sturdie to repair. |
Floodlights |
Carpark |
3 |
Not working |
N |
N |
N |
Please advise if Sturdie are to replace these. |
Good Guys Sign |
entrance of car park |
1 |
Sign not working |
N |
N |
N |
Added to fortnightly repairs list. |
External Lights |
main entrance |
2 |
Not working |
N |
N |
N |
Added to fortnightly repairs list. |
Low Bay LED Light |
Left hand side of entrance |
1 |
Full of water |
N |
N |
N |
Removed light and made safe. Added to fortnightly repairs list. |
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 24/05/2023 |
---|
| |
---|
| |