| Partner Name | DCS Electrical |
|---|
| State | TAS |
|---|
| Date of Visit | 15/11/2022 |
|---|
| Technician's Name | Nathan Rainbird |
|---|
| Which Company are you working for? | Sturdie Trade Services |
|---|
| Sturdie Job Number | 67336 |
|---|
| Email | Email hidden; Javascript is required. |
|---|
| The Good Guys Site in TAS | moonah |
|---|
|
|
|---|
| Location Name | Moonah |
|---|
| |
|---|
| HTML Block |
|
|---|
| Test Period | Biennial Test (once every two years) |
|---|
| Push Button Test | - Carry out push button test for correct operation
|
|---|
| Carry out push button test for correct operation | |
|---|
| HTML Block |
|
|---|
| Carry out test with RCD Tester | Carry out push button test and record the results below. |
|---|
| RCD Details (Biennial) | | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
|
1 |
Y |
0280 |
0247 |
P |
|
|
|
2 |
y |
0290 |
0291 |
p |
|
|
|
3 |
y |
0270 |
0278 |
p |
|
|
|
4 |
y |
0230 |
0245 |
p |
|
|
|
5 |
y |
0220 |
0236 |
p |
|
|
|
6 |
y |
0255 |
0245 |
p |
|
|
|
7 |
y |
0288 |
0234 |
p |
|
|
|
8 |
y |
0280 |
0275 |
p |
|
|
|
9 |
y |
0290 |
0300 |
p |
|
|
|
10 |
y |
0278 |
0310 |
p |
|
|
|
11 |
y |
0237 |
0178 |
p |
|
|
|
12 |
y |
0258 |
0254 |
p |
|
|
|
13 |
y |
0231 |
0247 |
p |
|
|
|
14 |
y |
0255 |
0236 |
p |
|
|
|
15 |
y |
0244 |
0298 |
p |
|
|
|
16 |
y |
0255 |
0287 |
p |
|
|
|
17 |
y |
0280 |
0278 |
p |
|
|
|
18 |
y |
0255 |
0295 |
p |
|
|
|
19 |
y |
0230 |
0236 |
p |
|
|
|
20 |
y |
0280 |
0278 |
p |
|
|
|
21 |
y |
0290 |
0236 |
p |
|
|
|
22 |
y |
0290 |
0269 |
p |
|
|
|
23 |
y |
0280 |
0258 |
p |
|
|
|
24 |
y |
0255 |
047 |
p |
|
|
|
25 |
y |
0236 |
0256 |
p |
|
|
|
26 |
y |
0235 |
0236 |
p |
|
|
|
27 |
y |
0245 |
0214 |
p |
|
|
|
28 |
y |
0280 |
0231 |
p |
|
|
|
29 |
y |
0255 |
0248 |
p |
|
|
|
30 |
y |
0276 |
0236 |
p |
|
|
|
31 |
y |
0278 |
0214 |
p |
|
|
|
32 |
y |
0300 |
0214 |
p |
|
|
|
33 |
y |
0260 |
0215 |
p |
|
|
|
34 |
y |
0278 |
0216 |
p |
|
|
|
35 |
y |
0280 |
0236 |
p |
|
|
|
36 |
y |
0255 |
0278 |
p |
|
|
|
37 |
y |
0260 |
0214 |
p |
|
|
|
38 |
y |
0267 |
0236 |
p |
|
|
|
39 |
y |
0258 |
0258 |
p |
|
|
|
40 |
y |
0259 |
0310 |
p |
|
|
|
41 |
y |
0300 |
0236 |
p |
|
|
|
42 |
y |
0214 |
0258 |
p |
|
|
|
43 |
y |
0215 |
0266 |
p |
|
|
|
44 |
y |
0216 |
0255 |
p |
|
|
|
45 |
y |
0214 |
0236 |
p |
|
|
|
46 |
y |
0289 |
0239 |
p |
|
|
|
47 |
y |
0289 |
0278 |
p |
|
|
|
48 |
y |
0255 |
0300 |
p |
|
|
| DB1 |
1 |
y |
0230 |
0247 |
p |
|
|
|
2 |
y |
0247 |
0236 |
p |
|
|
|
3 |
y |
0256 |
0275 |
p |
|
|
|
4 |
y |
0255 |
0296 |
p |
|
|
|
5 |
y |
0236 |
0285 |
p |
|
|
|
6 |
y |
0249 |
0296 |
p |
|
|
|
7 |
y |
0264 |
0236 |
p |
|
|
|
8 |
y |
0256 |
0293 |
p |
|
|
|
9 |
y |
0253 |
0286 |
p |
|
|
|
10 |
y |
0293 |
0271 |
p |
|
|
|
11 |
y |
0287 |
0248 |
p |
|
|
|
12 |
y |
0289 |
0284 |
p |
|
|
|
13 |
y |
0239 |
0295 |
p |
|
|
|
14 |
y |
0267 |
0285 |
p |
|
|
|
15 |
y |
0223 |
0296 |
p |
|
|
|
16 |
y |
0233 |
0236 |
p |
|
|
|
17 |
y |
0255 |
0296 |
p |
|
|
|
18 |
y |
0266 |
0275 |
p |
|
|
|
19 |
y |
0265 |
0285 |
p |
|
|
|
20 |
y |
0293 |
0312 |
p |
|
|
|
21 |
y |
0300 |
0296 |
p |
|
|
|
22 |
y |
0255 |
0285 |
p |
|
|
|
23 |
y |
0269 |
0274 |
p |
|
|
|
24 |
y |
0254 |
0296 |
p |
|
|
|
25 |
y |
0234 |
0236 |
p |
|
|
|
26 |
y |
0245 |
0296 |
p |
|
|
|
27 |
y |
0237 |
0285 |
p |
|
|
|
28 |
y |
0279 |
0275 |
p |
|
|
|
29 |
y |
0289 |
0356 |
p |
|
|
|
30 |
y |
0255 |
0248 |
p |
|
|
|
31 |
y |
0248 |
0298 |
p |
|
|
|
32 |
y |
0236 |
0348 |
p |
|
|
|
33 |
y |
0247 |
0298 |
p |
|
|
|
34 |
y |
0236 |
0247 |
p |
|
|
|
35 |
y |
0214 |
0258 |
p |
|
|
|
36 |
y |
0219 |
0245 |
p |
|
|
|
37 |
y |
0293 |
0268 |
p |
|
|
|
38 |
y |
0254 |
0289 |
p |
|
|
|
39 |
y |
0246 |
0247 |
p |
|
|
|
40 |
y |
0214 |
0245 |
p |
|
|
|
41 |
y |
0258 |
0246 |
p |
|
|
|
42 |
y |
0269 |
0256 |
p |
|
|
|
43 |
y |
0247 |
0235 |
p |
|
|
|
44 |
y |
0247 |
0267 |
p |
|
|
|
45 |
y |
0239 |
0269 |
p |
|
|
|
46 |
y |
0256 |
0237 |
p |
|
|
|
47 |
y |
0256 |
0258 |
p |
|
|
|
48 |
y |
0247 |
0269 |
p |
|
|
|
49 |
y |
0239 |
0247 |
p |
|
|
|
50 |
y |
0247 |
0234 |
p |
|
|
|
51 |
y |
0214 |
0258 |
p |
|
|
|
52 |
y |
0258 |
0247 |
p |
|
|
|
53 |
y |
0256 |
0214 |
p |
|
|
|
54 |
y |
0249 |
0271 |
p |
|
|
|
55 |
y |
0253 |
0214 |
p |
|
|
|
|---|
| THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
|---|
| SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
|---|
| Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
|---|
| Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
|---|
| Timers | - Check timers for correct operation and timing
|
|---|
| Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
|---|
| HTML Block |
|
|---|
| EMERGENCY LIGHTS | | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| DB2 |
2 |
S |
Y |
Y |
Y |
P |
|
|
|
|
3 |
S |
Y |
Y |
Y |
P |
|
|
|
|
4 |
S |
Y |
Y |
Y |
P |
|
|
|
|
5 |
S |
Y |
Y |
Y |
P |
|
|
|
|
6 |
S |
Y |
Y |
Y |
P |
|
|
|
|
7 |
S |
Y |
Y |
Y |
P |
|
|
|
|
9 |
S |
Y |
Y |
Y |
P |
|
|
|
|
10 |
S |
Y |
Y |
Y |
P |
|
|
|
|
11 |
S |
Y |
Y |
Y |
P |
|
|
|
|
12 |
S |
Y |
Y |
Y |
P |
|
|
|
|
13 |
S |
Y |
Y |
Y |
P |
|
|
|
|
15 |
S |
Y |
Y |
Y |
P |
|
|
|
|
16 |
S |
Y |
Y |
Y |
P |
|
|
|
|
17 |
S |
Y |
Y |
Y |
P |
|
|
|
|
18 |
S |
Y |
Y |
Y |
P |
|
|
|
|
19 |
S |
Y |
Y |
Y |
P |
|
|
|
|
20 |
S |
Y |
Y |
Y |
P |
|
|
|
|
21 |
S |
Y |
Y |
Y |
P |
|
|
|
|
22 |
S |
Y |
Y |
Y |
P |
|
|
|
|
23 |
S |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| HTML Block |
|
|---|
| EXIT LIGHTS | | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| DB2 |
1 |
Y |
Y |
Y |
P |
|
|
|
|
8 |
Y |
Y |
Y |
P |
|
|
|
|
14 |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
|---|
| General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
|---|
| HTML Block |
|
|---|
| General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
|---|
| HTML Block |
|
|---|
| Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
|---|
| Lighting Report | | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
| 2 x 36W Bare Batten |
Y |
| Diffused Hi Bays |
Y |
| 2 x 36W Diffused Batten |
Y |
| 1 x 36W Diffused Batten |
Y |
|
|---|
| Are there any Warranty items needing to be repaired? | No |
|---|
| LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
| Emergency Lighting Plan |
Site Folder |
x 1 |
Inaccurate |
N |
N |
N |
Plan to be updated and placed in site folder next audit |
|
|---|
| Next Test Due in 6 months | 11/05/2022 |
|---|
| |
|---|
| |