Partner NameBuilt Services
StateNSW
Date of Visit09/01/2023
Technician's NameCon Karakiozis
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number70917
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWcampbelltown

Location NameCampbelltown
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB1 1 Y P
2 Y P
4 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
14 Y P
16 Y P
17 Y P
18 Y P
20 Y P
22 Y P
24 Y P
25 Y P
26 Y P
27 Y P
28 Y P
30 Y P
32 Y P
34 Y P
DB15 1 Y P
3 Y P
5 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
21 Y P
23 Y P
25 Y P
28 Y P
39 Y P
41 Y P
43 Y P
44 Y P
45 Y P
46 Y P
47 Y P
48 Y P
49 Y P
50 Y P
51 Y P
52 Y P
53 Y P
54 Y P
55 Y P
56 Y P
57 Y P
58 Y P
59 Y P
60 Y P
DB13 7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
21 Y P
22 Y P
23 Y P
24 Y P
26 Y P
28 Y P
30 Y P
32 Y P
34 Y P
DB14 3 Y P
5 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
14 Y P
16 Y P
18 Y P
20 Y P
22 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB15 1 R Y Y Y P
2 S Y Y Y P
3 S Y Y Y P
4 S Y Y Y P
5 S Y Y Y P
6 S Y Y Y P
7 S Y Y Y P
8 S Y Y Y P
9 S Y Y Y P
10 S Y Y Y P
11 S Y Y Y P
12 S Y Y Y P
13 S Y Y Y P
14 R Y Y Y P
15 R Y Y Y P
16 R Y Y Y P
17 R Y Y Y P
18 R Y Y Y P
19 R Y Y Y P
20 R Y Y Y P
21 R Y Y Y P
22 R Y Y Y P
23 S Y Y Y P
24 S Y Y Y P
25 S Y Y Y P
26 S Y Y Y P
27 R Y Y Y P
28 S Y Y Y P
29 S Y Y Y P
30 S Y Y Y P
31 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB15 1 Y Y Y P
2 Y Y Y P
3 Y Y Y P
4 Y Y Y P
5 Y Y Y P
6 Y Y Y P
7 Y Y Y P
8 Y Y Y P
9 Y Y Y P
10 Y Y Y P
11 Y Y Y P
12 Y Y Y P
13 Y Y Y P
14 Y Y Y P
15 Y Y Y P
16 Y Y Y P
17 Y Y Y P
18 Y Y Y P
19 Y Y Y P
20 Y Y Y P
21 Y Y Y P
22 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
YML 200W Lamp Highbay Lights Y
LED Highbay 150W Davis Y
1 x 36W Single 4 Foot Fluoro 840 Y
4 Foot Twin 28W T5 865 Y
2 x 36W Twin 4 Foot Fluoro 840 Y
LED Downlights Lumalod 10W Y
AZ Elite 24W Dimmable LED Downlights Y
PL-C 13W Twin Globes Y
T5 Lamps 28W/865 Light Display Signs Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Vintec display Wall bay 2 LED downlights can not be plugged into power board. display will need to be removed in order to access power boards. N N N Supplier funded stand. Please raise a new work order if you would like Sturdie to repair
Technika display Kitchen 1 LED downlight cannot be plugged into power board. Display will need to be pulled apart in order to reach power board. N N N Supplier funded stand. Please raise a new work order if you would like Sturdie to repair
Fridges Fridges 3 Displays unplugged Y N N Connected 3 x kitchen displays as they were unplugged.
Electrolux fridge display Fridges 1 Faulty power supply. We cannot access power supply. Power supply is mounted under display. N N N Supplier funded stand. Please raise a new work order if you would like Sturdie to repair
Exit light Fridges 1 Catenary wire broken Y N N Re-connected wiring.
Mircrowaves Small goods 1 Power board Y N N Connected end cap power to display. PB4 outlet was unplugged.
Time Clock Sound bars, Sonos & Headphones 1 Time clock not programmed Y N N Programmed time clock for wall bay display units.
Door Bell Front Door 1 No door bell N TBA TBA Added to the fortnightly repairs list. as requested by Wilson
Site Status SelectorStore now fully compliant
Next Test Due in 6 months10/07/2023