StateNSW
Date of Visit12/01/2023
Technician's Namecon karakiozis
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number70919
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWcasula

Location NameCasula
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
T18 DB 7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
22 Y P
23 Y P
24 Y P
25 Y P
26 Y P
27 Y P
28 Y P
29 Y P
30 Y P
31 Y P
32 Y P
33 Y P
34 Y P
35 Y P
36 Y P
37 Y P
38 Y P
39 Y P
41 Y P
44 Y P
46 Y P
48 Y P
49 Y P
50 Y P
51 Y P
52 Y P
53 Y P
54 Y P
55 Y P
56 Y P
57 Y P
58 Y P
59 Y P
60 Y P
61 Y P
62 Y P
63 Y P
64 Y P
65 Y P
67 Y P
69 Y P
71 Y P
DBA 1 Y P
2 Y P
3 Y P
4 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
22 Y P
23 Y P
24 Y P
25 Y P
26 Y P
28 Y P
30 Y P
32 Y P
34 Y P
36 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
T18 DB EM1 S Y Y Y P
T18 DB EM2 S Y Y Y P
T18 DB EM3 S Y Y Y P
T18 DB EM4 S Y Y Y P
T18 DB EM5 S Y Y Y P
T18 DB EM6 S Y Y Y P
T18 DB EM7 S Y Y Y P
T18 DB EM8 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
T18 DB EX1 Y Y Y P
T18 DB EX2 Y Y Y P
T18 DB EX3 Y Y Y P
T18 DB EX4 Y Y Y P
T18 DB EX5 Y Y Y P
T18 DB EX6 Y Y Y P
T18 DB EX7 Y Y Y P
T18 DB EX8 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Hi Bay Halo Globe Y
2 x 28W Fluoro Y
2 x 28W Caged Fluoro Y
1200mm LED Batten Y
LED Pelmet Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Plinth TV section 6 Power board issue N N N Added to fortnightly repairs list.
Fridges department work station 1 no issue, store managers has just requested that the work station be removed. N N N Scissor lift required. Please raise a work order if you want Sturdie to attend.
Hisense fridge display Fridges 2 2 x power supplies faulty N N N Supplied funded stand. Please raise a new work order if you would like Sturdie to repair.
Electrolux Fridges 1 1 x faulty power supply power supply is mounted under the fixture. this will require 2 x techs and the fixture to be flipped in order to replace. N N N Supplied funded stand. Please raise a new work order if you would like Sturdie to repair.
Viali Kitchen display 1 1 x faulty batten N N N Supplied funded stand. Please raise a new work order if you would like Sturdie to repair.
Fisher & Paykel Fridges 1 LED Lights not working Y N N
DJI display TV's 1 Flickering LED strips N N N Supplied funded stand. Please raise a new work order if you would like Sturdie to repair.
LED Batten Kitchen 1 Low voltage connection had broken wire Y N N
Switchboard DB T18 5 Missing pole fillers Y N N
Sturdie Maintenance Folder Office 1 Old Logo, needs to be updated. Y N N New updated folder has been sent to store.
Site Status SelectorStore now fully compliant
Next Test Due in 6 months13/06/2023