StateQLD
Date of Visit17/02/2023
Technician's NameAntonio Cavaliere
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number71061
EmailEmail hidden; Javascript is required.
The Good Guys Site in QLDcairns

Location NameCairns
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB1 - Rear of warehouse
DB1 - RCBO 1 Y P
DB1 - RCBO 2 Y P
DB1 - RCBO 3 Y P
DB1 - RCBO 4 Y P
DB1 - RCBO 5 Y P
DB1 - RCBO 6 Y P
DB1 - RCBO 7 Y P
DB1 - 3φ CB 8-10 Y P
DB1 - 3φ CB 11-13 Y P
DB1 - RCBO 14 Y P
DB1 - RCBO 15 Y P
DB1 - RCBO 16 Y P
DB1 - RCBO 17 Y P
DB1 - RCBO 18 Y P
DB1 - 3φ CB 19-21 Y P
DB1 - RCBO 22 Y P
DB1 - RCBO 23 Y P
DB1 - RCBO 24 Y P
DB1 - RCBO 25 Y P
DB1 - RCBO 26 Y P
DB1 - RCBO 27 Y P
DB1 - RCBO 28 Y P
DB1 - CB 29 Y P
DB1 - CB 30 Y P
DB1 - 3φ CB 31-33 Y P
DB1 - RCBO 34 Y P
DB1 - RCBO 35 Y P
DB1 - CB 36 Y P
DB1 - CB 37 Y P
DB1 - CB 38 Y P
DB1 - CB 39 Y P
DB1 - CB 40 Y P
DB1 - CB 41 Y P
DB1 - CB 42 Y P
DB1 - CB 43 Y P
DB1 - CB 44 Y P
DB1 - CB 45 Y P
DB1 - CB 46 Y P
DB1 - CB 47 Y P
DB1 - CB 48 Y P
DB1 - CB 49 Y P
DB1 - CB 50 Y P
DB1 - CB 51 Y P
DB1 - CB 52 Y P
DB1 - CB 53 Y P
DB1 - CB 54 Y P
DB1 - CB 55 Y P
DB1 - CB 56 Y P
DB1 - CB 57 Y P
DB1 - RCBO 58 Y P
DB1 - RCBO 59 Y P
DB1 - CB 60 Y P
DB1 - CB 61 Y P
DB1 - CB 62 Y P
DB1 - RCBO 63 Y P
DB1 - RCBO 64 Y P
DB1 - RCBO 65 Y P
DB1 - CB 66 Y P
DB1 - CB 67 Y P
DB1 - CB 68 Y P
DB1 - RCBO 69 Y P
DB1 - CB 70 Y P
DB1 - CB 71 Y P
DB1 - CB 72 Y P
DB - SR2 3φ CB 1,3,5 Y P
DB - SR2 Pole spare 7 Y P
DB - SR2 Pole spare 9 Y P
DB - SR2 RCBO 11 Y P
DB - SR2 RCBO 13 Y P
DB - SR2 RCBO 15 Y P
DB - SR2 RCBO 17 Y P
DB - SR2 RCBO 19 Y P
DB - SR2 Pole spare 21 Y P
DB - SR2 CB 23 Y P
DB - SR2 RCBO 2 Y P
DB - SR2 RCBO 4 Y P
DB - SR2 RCBO 6 Y P
DB - SR2 RCBO 8 Y P
DB - SR2 RCBO 10 Y P
DB - SR2 RCBO 12 Y P
DB - SR2 RCBO 14 Y P
DB - SR2 Pole spare 16,18 Y P
DB - SR2 RCBO 20 Y P
DB - SR2 Pole spare 22,24 Y P
DBX - Front of shop
DBX - RCBO 1 Y P
DBX - RCBO 3 Y P
DBX - RCBO 5 Y P
DBX - RCBO 7 Y P
DBX - CB 9 Y P
DBX - RCBO 11 Y P
DBX - RCBO 13 Y P
DBX - RCBO 15 Y P
DBX - RCBO 17 Y P
DBX - RCBO 19 Y P
DBX - RCBO 21 Y P
DBX - RCBO 23 Y P
DBX - RCBO 25 Y P
DBX - RCBO 27 Y P
DBX - RCBO 29 Y P
DBX - RCBO 31 Y P
DBX - RCBO 33 Y P
DBX - RCBO 35 Y P
DBX - RCBO 2 Y P
DBX - RCBO 4 Y P
DBX - RCBO 6 Y P
DBX - RCBO 8 Y P
DBX - RCBO 10 Y P
DBX - RCBO 12 Y P
DBX - RCBO 14 Y P
DBX - RCBO 16 Y P
DBX - RCBO 18 Y P
DBX - RCBO 20 Y P
DBX - RCBO 22 Y P
DBX - RCBO 24 Y P
DBX - RCBO 26 Y P
DBX - RCBO 28 Y P
DBX - RCBO 30 Y P
DBX - RCBO 32 Y P
DBX - RCBO 34 Y P
DBX - Spare pole 36 Y P
DBX - Adjacent DBX
DBX 2 - RCBO 1 Y P
DBX 2 - RCBO 3 Y P
DBX 2 - RCBO 5 Y P
DBX 2 - RCBO 7 Y P
DBX 2 - RCBO 9 Y P
DBX 2 - RCBO 11 Y P
DBX 2 - RCBO 13 Y P
DBX 2 - RCBO 15 Y P
DBX 2 - RCBO 17 Y P
DBX 2 - RCBO 19 Y P
DBX 2 - RCBO 21 Y P
DBX 2 - RCBO 23 Y P
DBX 2 - RCBO 2 Y P
DBX 2 - RCBO 4 Y P
DBX 2 - RCBO 6 Y P
DBX 2 - RCBO 8 Y P
DBX 2 - RCBO 10 Y P
DBX 2 - RCBO 12 Y P
DBX 2 - RCBO 14 Y P
DBX 2 - RCBO 16 Y P
DBX 2 - RCBO 18 Y P
DBX 2 - RCBO 20 Y P
DBX 2 - RCBO 22 Y P
DBX 2 - RCBO 24 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 1 R Y Y Y P
DB1 2 R Y Y Y P
DB1 3 R Y Y Y P
DB1 4 R Y Y Y P
DB1 5 R Y Y Y P
DB1 6 R Y Y Y P
DB1 7 R Y Y Y P
DB1 8 R Y Y Y P
DB1 9 R Y Y Y P
DB1 10 R Y Y Y P
DB1 11 R Y Y Y P
DB1 12 R Y Y Y P
DB1 13 R Y Y Y P
DB1 14 R Y Y Y P
DB1 15 R Y Y Y P
DB1 16 R Y Y Y P
DB1 17 R Y Y Y P
DB1 18 R Y Y Y P
DB1 19 R Y Y Y P
DB1 20 R Y Y Y P
DB1 21 S Y Y Y P
DB1 22 S Y Y Y P
DB1 23 S Y Y Y P
DB1 24 S Y Y Y P
DB1 25 S Y Y Y P
DB1 26 S Y Y Y P
DB1 27 S Y Y Y P
DB1 28 S Y Y Y P
DB1 29 S Y Y Y P
DB1 30 S Y Y Y P
DB1 31 R Y Y Y P
DB1 32 R Y Y Y P
DB1 33 R Y Y Y P
DB1 34 R Y Y Y P
DB1 35 R Y Y Y P
DB1 36 R Y Y Y P
DB1 37 R Y Y Y P
DB1 38 R Y Y Y P
DB1 39 R Y Y Y P
DB1 60 R Y Y Y P
DB1 61 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 40 Y Y Y P
DB1 41 Y Y Y P
DB1 42 Y Y Y P
DB1 43 Y Y Y P
DB1 44 Y Y Y P
DB1 45 Y Y Y P
DB1 46 Y Y Y P
DB1 47 Y Y Y P
DB1 48 Y Y Y P
DB1 49 Y Y Y P
DB1 50 Y Y Y P
DB1 51 Y Y Y P
DB1 52 Y Y Y P
DB1 53 Y Y Y P
DB1 54 Y Y Y P
DB1 55 Y Y Y P
DB1 56 Y Y Y P
DB1 57 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
LED Batten Y
Down Lights - LED Y
Down Lights - Display Lighting Y
LED Panels - Display Lighting Y
Square lights (Showroom trading lights) Y
LED strip lighting - displays CFL's Y
Round Fluro Down Lights - Toilet Y
High Bay LED Y
Are there any Warranty items needing to be repaired?No
Site Status SelectorQLD - Maintenance has been completed in accordance to ASS2293.2 and QDC MP6.1. - Store now fully compliant
Next Test Due in 6 months17/08/2023