Partner NameSturdie Trade Services
StateVIC
Date of Visit08/03/2023
Technician's NameNathan McBain
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number71130
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICnorthland

Location NamePreston (Northland)
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB01 01 Y P
DB01 02 Y P
DB01 03 Y P
DB01 04 Y P
DB01 05 Y P
DB01 06 Y P
DB01 07 Y P
DB01 08 Y P
DB01 09 Y P
DB01 10 Y P
DB01 11 Y P
DB01 12 Y P
DB01 13 Y P
DB01 14 Y P
DB01 15 Y P
DB01 16 Y P
DB01 17 Y P
DB01 18 Y P
DB01 18 Y P
DB01 19 Y P
DB01 20 Y P
DB01 21 Y P
DB01 22 Y P
DB01 23 Y P
DB01 24 Y P
DB01 25 Y P
DB01 26 Y P
DB01 27 Y P
DB01 28 Y P
DB01 29 Y P
DB01 30 Y P
DB01 31 Y P
DB01 32 Y P
DB01 33 Y P
DB01 34 Y P
DB01 35 Y P
DB01 37 Y P
DB01 38 Y P
DB01 39 Y P
DB01 40 Y P
DB01 41 Y P
DB01 42 Y P
DB01 43 Y P
DB01 45 Y P
DB01 47 Y P
DB01 49 Y P
DB01 50 Y P
DB01 51 Y P
DB01 52 Y P
DB01 53 Y P
DB01 54 Y P
DB01 55 Y P
DB01 57 Y P
DB01 59 Y P
DB01 61 Y P
DB01 63 Y P
DB01 65 Y P
DB02 01 Y P
DB02 02 Y P
DB02 03 Y P
DB02 04 Y P
DB02 05 Y P
DB02 06 Y P
DB02 07 Y P
DB02 08 Y P
DB02 09 Y P
DB02 10 Y P
DB02 11 Y P
DB02 12 Y P
DB02 13 Y P
DB02 14 Y P
DB02 15 Y P
DB02 16 Y P
DB02 17 Y P
DB02 18 Y P
DB02 19 Y P
DB02 20 Y P
DB02 21 Y P
DB02 22 Y P
DB02 23 Y P
DB02 24 Y P
DB02 25 Y P
DB02 26 Y P
DB02 27 Y P
DB02 28 Y P
DB02 29 Y P
DB02 30 Y P
DB02 31 Y P
DB02 32 Y P
DB02 33 Y P
DB02 34 Y P
DB02 35 Y P
DB02 36 Y P
DB02 37 Y P
DB02 38 Y P
DB02 39 Y P
DB02 40 Y P
DB02 41 Y P
DB02 42 Y P
DB02 43 Y P
DB02 44 Y P
DB02 45 Y P
DB02 46 Y P
DB02 48 Y P
DB03 01 Y P
DB03 02 Y P
DB03 03 Y P
DB03 04 Y P
DB03 05 Y P
DB03 06 Y P
DB03 07 Y P
DB03 08 Y P
DB03 09 Y P
DB03 10 Y P
DB03 11 Y P
DB03 15 Y P
DB04 01 Y P
DB04 03 Y P
DB04 05 Y P
DB04 07 Y P
DB04 09 Y P
DB04 11 Y P
DB04 13 Y P
DB04 15 Y P
DB04 17 Y P
DB04 19 Y P
DB04 21 Y P
DB04 23 Y P
DB04 24 Y P
DB04 25 Y P
DB04 26 Y P
DB04 27 Y P
DB04 28 Y P
DB04 29 Y P
DB04 30 Y P
DB04 31 Y P
DB04 32 Y P
DB04 34 Y P
DB04 36 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 2 R Y Y Y P
5 R N N Y F FAILED 90MIN DISCHARGE TEST Y N
6 R Y Y Y P
7 R Y Y Y P
8 R Y Y Y P
9 R Y Y Y P
11 R Y Y Y P
14 R Y Y Y P
17 R Y Y Y P
18 R Y Y Y P
19 R Y Y Y P
20 R Y Y Y P
21 R Y Y Y P
24 R Y Y Y P
25 R Y Y Y P
26 R Y Y Y P
28 R Y Y Y P
32 R Y Y Y P
33 R Y Y Y P
34 R Y Y Y P
36 R Y Y Y P
38 R Y Y Y P
39 R Y Y Y P
40 R Y Y Y P
42 R Y Y Y P
43 R Y Y Y P
44 R Y Y Y P
45 R Y Y Y P
46 R Y Y Y P
47 R Y Y Y P
48 R Y Y Y P
49 R Y Y Y P
51 R Y Y Y P
54 S Y Y Y P
57 S Y Y Y P
58 S Y Y Y P
60 S Y Y Y P
63 S Y Y Y P
64 S Y N Y F FAILED 90MIN DISCHARGE TEST Y N
65 S Y Y Y P
66 S Y Y Y P
67 R Y Y Y P
69 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB4 3 Y Y Y P
10 Y Y Y P
13 Y Y Y P
31 Y Y Y P
35 Y Y Y P
37 Y Y Y P
41 Y Y Y P
50 Y Y Y P
53 Y Y Y P
56 N Y N F DAMAGED DIFFUSER Y N
59 Y Y Y P
61 Y Y Y P
62 Y Y Y P
68 Y Y Y P
70 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
LED PANEL LIGHT
HIGHBAY
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
TEST AND TAG STORE 1 TEST AND TAG IN-DATE, NEXT TEST DUE 10 FEB 2024 N N N OBSERVATION
CEILING TILES LAPTOPS(1) / KINSMAN(2) / MIXES(1) / HAIER OVENS(1) / BOSCH KITCHEN(1) / FRONT ENTRANCE(1) / SMEG APPLIANCES(1) / DYSON(1) / SCALES(1) / SEASONAL(5) 15 DAMAGED/WATER DAMAGE/LARGE HOLES N N N OBSERVATION. NOTE: SOME TILES HAVE EQUIPMENT MOUNTED
EM05 NEAR DB1 1 FAILED 90MIN EMERGENCY LIGHTING DISCHARGE TEST Y N N
EM64 BOH AISLE NEAR SINGLE MAN DOOR 1 FAILED 90MIN DISCHARGE TEST Y N N
EX56 BOH AISLE 1 DAMAGED Y N N
Site Status SelectorStore now fully compliant
Next Test Due in 6 months08/09/2023