Partner NameSturdie Trade Services
StateVIC
Date of Visit09/03/2023
Technician's NameMatt Setches
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number71137
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICbayswater

Location NameBayswater
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
MSB- Section1 20 Y P
21 Y P
23 Y P
27 Y P
33 Y P
MSB-S ection 2 8 Y P
10 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
21 Y P
22 Y P
23 Y P
24 Y P
25 Y P
26 Y P
27 Y P
28 Y P
29 Y P
30 Y P
31 Y P
32 Y P
33 Y P
34 Y P
35 Y P
36 Y P
37 Y P
DB-02 1 Y P
3 Y P
4 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
17 Y P
DB-01 Section 1 1 Y P
2 Y P
3 Y P
4 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
21 Y P
22 Y P
23 Y P
24 Y P
25 Y P
26 Y P
27 Y P
28 Y P
29 Y P
30 Y P
33 Y P
35 Y P
DB-01 Section 2 1 Y P
2 Y P
3 Y P
4 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
21 Y P
22 Y P
23 Y P
24 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 1 S Y Y Y P
DB1 2 S Y N Y F Failed discharge test Y N
DB1 3 S Y Y Y P
DB1 4 S Y Y Y P
DB1 5 S Y Y Y P
DB1 6 S Y Y Y P
DB1 7 S Y Y Y P
DB1 8 S Y Y Y P
DB1 9 S Y Y Y P
DB1 10 S Y Y Y P
DB1 11 S Y Y Y P
DB1 12 R Y Y Y P
DB1 13 R Y Y Y P
DB1 14 R Y Y Y P
DB1 15 R Y Y Y P
DB1 16 R Y Y Y P
DB1 17 R Y Y Y P
DB1 18 R Y Y Y P
DB1 19 R Y Y Y P
DB1 20 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 1 Y Y Y P
DB1 2 Y Y Y P
DB1 3 Y Y Y P
DB1 4 Y Y Y P
DB1 5 Y Y Y P
DB1 6 Y Y Y P
DB1 7 Y Y Y P
DB1 8 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Induction high bay lights Y
LED high bay lights Y
Emergency single 36w battern Y
Emergency recessed lights Y
Bardic Exit lights Y
70mm downlights Y
36W single fluorescent bare battern Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Power supply Light boxes 50+ Not tested and tagged N N N Observation- Power supplies to overhead light displays have not been test and tagged.
28W Lamp Upstairs office 1 Failed to luminate Y N N
70mm Led downlight Tv's 1 Failed to luminate Y N N
Hi-bay Grooming 1 Failed to luminate Y N N
Emergency light No. 2 Entrance to store 1 Failed discharge test Y N N
LED driver Television light display 1 Failed to luminate Y N N
LED driver Wall brackets 1 Failed to luminate Y N N
LED driver Sound bars 1 Failed to luminate Y N N
LED driver Smart speakers 1 Failed to luminate Y N N
LED driver Smart home 1 Failed to luminate Y N N
LED driver Monitors 1 Failed to luminate Y N N
LED driver Wearables 1 Failed to luminate Y N N
LED driver Accessories 1 Failed to luminate Y N N
LED driver Mobile plans 1 Failed to luminate Y N N
Site Status SelectorStore now fully compliant
Next Test Due in 6 months08/09/2023