Partner Name | Built Electrical Australia |
---|
State | NSW |
---|
Date of Visit | 10/05/2023 |
---|
Technician's Name | Peter Hay |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 70980 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in NSW | penrith |
---|
|
|
---|
Location Name | Penrith |
---|
| |
---|
HTML Block |
|
---|
Test Period | 6 Monthly (90 minutes) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
RCD Details (6 Month) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
Db1 |
1 |
Y |
P |
|
|
Db1 |
2 |
Y |
P |
|
|
Db1 |
3 |
Y |
P |
|
|
Db1 |
4 |
Y |
P |
|
|
Db1 |
5 |
Y |
P |
|
|
Db1 |
6 |
Y |
P |
|
|
Db1 |
7 |
Y |
P |
|
|
Db1 |
8 |
Y |
P |
|
|
Db1 |
9 |
Y |
P |
|
|
Db1 |
10 |
Y |
P |
|
|
Db1 |
11 |
Y |
P |
|
|
Db1 |
12 |
Y |
P |
|
|
Db1 |
15 |
Y |
P |
|
|
Db1 |
16 |
Y |
P |
|
|
Db1 |
39 |
Y |
P |
|
|
Db1 |
40 |
Y |
P |
|
|
Db1 |
42 |
Y |
P |
|
|
Db1 |
43 |
Y |
P |
|
|
Db1 |
44 |
Y |
P |
|
|
Db1 |
45 |
Y |
P |
|
|
Db1 |
46 |
Y |
P |
|
|
Db1 |
47 |
Y |
P |
|
|
Db1 |
48 |
Y |
P |
|
|
Db1 |
49 |
Y |
P |
|
|
Db1 |
69 |
Y |
P |
|
|
Db1 |
70 |
Y |
P |
|
|
Db1 |
71 |
Y |
P |
|
|
Db1 |
76 |
Y |
P |
|
|
Db1 |
77 |
Y |
P |
|
|
Db1 |
78 |
Y |
P |
|
|
Db1 |
79 |
Y |
P |
|
|
Db1 |
80 |
Y |
P |
|
|
Db1 |
81 |
Y |
P |
|
|
Db1 |
82 |
Y |
P |
|
|
Db1 |
83 |
Y |
P |
|
|
Db1 |
84 |
Y |
P |
|
|
Db1 |
85 |
Y |
P |
|
|
Db1 |
86 |
Y |
P |
|
|
Db1 |
87 |
Y |
P |
|
|
Db1 |
88 |
Y |
P |
|
|
Db1 |
89 |
Y |
P |
|
|
Db1 |
90 |
Y |
P |
|
|
Db1 |
91 |
Y |
P |
|
|
Db1 |
92 |
Y |
P |
|
|
Db1 |
93 |
Y |
P |
|
|
Db1 |
94 |
Y |
P |
|
|
Db1 |
95 |
Y |
P |
|
|
Db1 |
99 |
Y |
P |
|
|
Db1 |
100 |
Y |
P |
|
|
Db1 |
101 |
Y |
P |
|
|
Db1 |
102 |
Y |
P |
|
|
Db1 |
103 |
Y |
P |
|
|
Db1 |
104 |
Y |
P |
|
|
Db1 |
105 |
Y |
P |
|
|
Db1 |
106 |
Y |
P |
|
|
Db1 |
111 |
Y |
P |
|
|
Db1 |
112 |
Y |
P |
|
|
Db1 |
113 |
Y |
P |
|
|
Db1 |
114 |
Y |
P |
|
|
Db1 |
115 |
Y |
P |
|
|
Db1 |
116 |
Y |
P |
|
|
Db1 |
117 |
Y |
P |
|
|
Db1 |
118 |
Y |
P |
|
|
Db1 |
119 |
Y |
P |
|
|
Db1 |
120 |
Y |
P |
|
|
Db1 |
121 |
Y |
P |
|
|
Db1 |
122 |
Y |
P |
|
|
Db1 |
123 |
Y |
P |
|
|
Db1 |
124 |
Y |
P |
|
|
Db1 |
125 |
Y |
P |
|
|
Db1 |
127 |
Y |
P |
|
|
Db1 |
128 |
Y |
P |
|
|
Db1 |
129 |
Y |
P |
|
|
Db1 |
130 |
Y |
P |
|
|
Db1 |
131 |
Y |
P |
|
|
Db1 |
135 |
Y |
P |
|
|
Db1 |
136 |
Y |
P |
|
|
Db1 |
137 |
Y |
P |
|
|
Db1 |
138 |
Y |
P |
|
|
Db1 |
139 |
Y |
P |
|
|
Db1 |
140 |
Y |
P |
|
|
Db1 |
141 |
Y |
P |
|
|
Db1 |
142 |
Y |
P |
|
|
Db1 |
143 |
Y |
P |
|
|
Db1 |
144 |
Y |
P |
|
|
Db1 |
145 |
Y |
P |
|
|
Db1a |
1 |
Y |
P |
|
|
Db1a |
2 |
Y |
P |
|
|
Db1a |
7 |
Y |
P |
|
|
Db1a |
8 |
Y |
P |
|
|
Db1a |
9 |
Y |
P |
|
|
Db1a |
10 |
Y |
P |
|
|
Db1a |
11 |
Y |
P |
|
|
Db1a |
12 |
Y |
P |
|
|
Db1a |
13 |
Y |
P |
|
|
Db1a |
14 |
Y |
P |
|
|
Db1a |
15 |
Y |
P |
|
|
Db1a |
19 |
Y |
P |
|
|
Db1a |
20 |
Y |
P |
|
|
Db1a |
21 |
Y |
P |
|
|
Db1a |
31 |
Y |
P |
|
|
Db1a |
32 |
Y |
P |
|
|
Db1a |
33 |
Y |
P |
|
|
Db1a |
34 |
Y |
P |
|
|
Db1a |
35 |
Y |
P |
|
|
Db1a |
36 |
Y |
P |
|
|
Db1a |
41 |
Y |
P |
|
|
Db1a |
42 |
Y |
P |
|
|
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
Db1 |
1 |
R |
Y |
Y |
Y |
P |
|
|
|
Db1 |
2 |
R |
Y |
Y |
Y |
P |
|
|
|
Db1 |
3 |
R |
Y |
Y |
Y |
P |
|
|
|
Db1 |
4 |
R |
Y |
Y |
Y |
P |
|
|
|
Db1 |
5 |
R |
Y |
Y |
Y |
P |
|
|
|
Db1 |
6 |
R |
Y |
Y |
Y |
P |
|
|
|
Db1 |
7 |
R |
Y |
Y |
Y |
P |
|
|
|
Db1 |
8 |
R |
Y |
Y |
Y |
P |
|
|
|
Db1 |
9 |
R |
Y |
Y |
Y |
P |
|
|
|
Db1 |
10 |
R |
Y |
Y |
Y |
P |
|
|
|
Db1 |
11 |
R |
Y |
Y |
Y |
P |
|
|
|
Db1 |
12 |
R |
Y |
Y |
Y |
P |
|
|
|
Db1 |
13 |
R |
Y |
Y |
Y |
P |
|
|
|
Db1 |
14 |
R |
Y |
Y |
Y |
P |
|
|
|
Db1 |
15 |
R |
Y |
Y |
Y |
P |
|
|
|
Db1 |
16 |
R |
Y |
Y |
Y |
P |
|
|
|
Db1a |
17 |
S |
Y |
Y |
Y |
P |
|
|
|
Db1a |
18 |
S |
Y |
Y |
Y |
P |
|
|
|
Db1a |
19 |
S |
Y |
Y |
Y |
P |
|
|
|
Db1a |
20 |
S |
Y |
Y |
Y |
P |
|
|
|
Db1a |
21 |
S |
Y |
Y |
Y |
P |
|
|
|
Db1a |
22 |
S |
Y |
Y |
Y |
P |
|
|
|
Db1a |
23 |
4ft maintained batten |
Y |
Y |
Y |
P |
|
|
|
Db1a |
24 |
S |
Y |
Y |
Y |
P |
|
|
|
Db1a |
25 |
4ft maintained batten |
Y |
Y |
Y |
P |
|
|
|
Db1a |
26 |
S |
Y |
Y |
Y |
P |
|
|
|
Db1a |
27 |
S |
Y |
Y |
Y |
P |
|
|
|
Db1a |
28 |
S |
Y |
Y |
Y |
P |
|
|
|
Db1a |
29 |
S |
Y |
Y |
Y |
P |
|
|
|
Db1a |
30 |
S |
Y |
Y |
Y |
P |
|
|
|
Db1a |
31 |
S |
Y |
Y |
Y |
P |
|
|
|
Db1a |
32 |
S |
Y |
Y |
Y |
P |
|
|
|
Db1a |
33 |
S |
Y |
Y |
Y |
P |
|
|
|
Db1a |
34 |
S |
Y |
Y |
Y |
P |
|
|
|
Db1a |
35 |
S |
Y |
Y |
Y |
P |
|
|
|
Db1a |
36 |
S |
Y |
Y |
Y |
P |
|
|
|
Db1 |
37 |
S |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
Db1 |
1 |
Y |
Y |
Y |
P |
|
|
|
Db1 |
2 |
Y |
Y |
Y |
P |
|
|
|
Db1 |
3 |
Y |
Y |
Y |
P |
|
|
|
Db1 |
4 |
Y |
Y |
Y |
P |
|
|
|
Db1 |
5 |
Y |
Y |
Y |
P |
|
|
|
Db1 |
6 |
Y |
Y |
Y |
P |
|
|
|
Db1 |
7 |
Y |
Y |
Y |
P |
|
|
|
Db1 |
8 |
Y |
Y |
Y |
P |
|
|
|
Db1 |
9 |
Y |
Y |
Y |
P |
|
|
|
Db1 |
10 |
Y |
Y |
Y |
P |
|
|
|
Db1 |
11 |
Y |
Y |
N |
F |
Suspension wires damaged. Light hanging by live electrical cable |
Y |
N |
Db1 |
12 |
Y |
Y |
Y |
P |
|
|
|
Db1 |
13 |
Y |
Y |
Y |
P |
|
|
|
Db1 |
14 |
Y |
Y |
Y |
P |
|
|
|
Db1 |
15 |
Y |
Y |
Y |
P |
|
|
|
Db1 |
16 |
Y |
Y |
Y |
P |
|
|
|
Db1 |
17 |
Y |
Y |
Y |
P |
|
|
|
Db1a |
18 |
Y |
N |
Y |
F |
Failed 90 min test |
Y |
N |
Db1a |
1920 |
Y |
Y |
Y |
P |
|
|
|
Db1a |
21 |
Y |
Y |
Y |
P |
|
|
|
Db1a |
22 |
Y |
Y |
Y |
P |
|
|
|
Db1a |
23 |
Y |
Y |
Y |
P |
|
|
|
Db1 |
24 |
Y |
Y |
Y |
P |
|
|
|
Db1a |
25 |
Y |
Y |
Y |
P |
|
|
|
Db1a |
26 |
Y |
Y |
Y |
P |
|
|
|
Db1a |
27 |
Y |
Y |
Y |
P |
|
|
|
Db1a |
28 |
Y |
Y |
Y |
P |
|
|
|
Db1a |
29 |
Y |
Y |
Y |
P |
|
|
|
Db1a |
30 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
5ft led tube on fluro ballast |
Y |
4ft led batten |
Y |
2ft led batten |
Y |
Led ufo high bay |
Y |
1200x300mm led panel |
Y |
600 x 600 led panel |
Y |
External flood lights |
Y |
Led downlight foyer s9523tc |
Y |
Vibe 900mm led linkable battens |
Y |
Led flat panel wall bay light boxes |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
Geotag photo(s) | - Have you sent the Geotag photo(s) to maintenance@sturdie.com.au, referring to the Store Location in the email, e.g. Canberra City?
|
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
4ft LED batten |
Male toilet |
1 |
Not illuminated |
Y |
N |
N |
|
5ft LED tubes |
Trading floor |
12 |
Not illuminted |
Y |
N |
N |
|
Square LED panel |
External adjacent fire door |
1 |
Vandalised |
Y |
N |
N |
Placed back into position. |
Cfl downlight |
Foyer/entrance |
3 |
Not illuminated |
Y |
N |
N |
|
Cfl downlight |
Foyer/entrance |
1 |
Dimly lit. On its way out. Last remaining old style cfl downlight onsite |
Y |
N |
N |
|
LED High bay |
BOH |
2 |
Not illuminated |
Y |
N |
N |
|
LED flat panel light box driver and wiring |
Aircon |
1 |
Double sided taped to back of light box. Not secured with cable ties. Live cabling within customers reach. |
Y |
N |
N |
Not installed properly by others . Secured driver and cabling. |
Ceiling tile |
Kinsman |
1 |
Had been removed and not put back |
Y |
N |
N |
Placed back into position. |
Exit light |
#11 |
1 |
Suspension wires damaged. |
Y |
N |
N |
|
Exit light |
#18 |
1 |
Failed 90 min test |
Y |
N |
N |
|
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 10/11/2023 |
---|
| |
---|
| |