Partner NameBuilt Electrical Australia
StateNSW
Date of Visit10/05/2023
Technician's NamePeter Hay
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number70980
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWpenrith

Location NamePenrith
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
Db1 1 Y P
Db1 2 Y P
Db1 3 Y P
Db1 4 Y P
Db1 5 Y P
Db1 6 Y P
Db1 7 Y P
Db1 8 Y P
Db1 9 Y P
Db1 10 Y P
Db1 11 Y P
Db1 12 Y P
Db1 15 Y P
Db1 16 Y P
Db1 39 Y P
Db1 40 Y P
Db1 42 Y P
Db1 43 Y P
Db1 44 Y P
Db1 45 Y P
Db1 46 Y P
Db1 47 Y P
Db1 48 Y P
Db1 49 Y P
Db1 69 Y P
Db1 70 Y P
Db1 71 Y P
Db1 76 Y P
Db1 77 Y P
Db1 78 Y P
Db1 79 Y P
Db1 80 Y P
Db1 81 Y P
Db1 82 Y P
Db1 83 Y P
Db1 84 Y P
Db1 85 Y P
Db1 86 Y P
Db1 87 Y P
Db1 88 Y P
Db1 89 Y P
Db1 90 Y P
Db1 91 Y P
Db1 92 Y P
Db1 93 Y P
Db1 94 Y P
Db1 95 Y P
Db1 99 Y P
Db1 100 Y P
Db1 101 Y P
Db1 102 Y P
Db1 103 Y P
Db1 104 Y P
Db1 105 Y P
Db1 106 Y P
Db1 111 Y P
Db1 112 Y P
Db1 113 Y P
Db1 114 Y P
Db1 115 Y P
Db1 116 Y P
Db1 117 Y P
Db1 118 Y P
Db1 119 Y P
Db1 120 Y P
Db1 121 Y P
Db1 122 Y P
Db1 123 Y P
Db1 124 Y P
Db1 125 Y P
Db1 127 Y P
Db1 128 Y P
Db1 129 Y P
Db1 130 Y P
Db1 131 Y P
Db1 135 Y P
Db1 136 Y P
Db1 137 Y P
Db1 138 Y P
Db1 139 Y P
Db1 140 Y P
Db1 141 Y P
Db1 142 Y P
Db1 143 Y P
Db1 144 Y P
Db1 145 Y P
Db1a 1 Y P
Db1a 2 Y P
Db1a 7 Y P
Db1a 8 Y P
Db1a 9 Y P
Db1a 10 Y P
Db1a 11 Y P
Db1a 12 Y P
Db1a 13 Y P
Db1a 14 Y P
Db1a 15 Y P
Db1a 19 Y P
Db1a 20 Y P
Db1a 21 Y P
Db1a 31 Y P
Db1a 32 Y P
Db1a 33 Y P
Db1a 34 Y P
Db1a 35 Y P
Db1a 36 Y P
Db1a 41 Y P
Db1a 42 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
Db1 1 R Y Y Y P
Db1 2 R Y Y Y P
Db1 3 R Y Y Y P
Db1 4 R Y Y Y P
Db1 5 R Y Y Y P
Db1 6 R Y Y Y P
Db1 7 R Y Y Y P
Db1 8 R Y Y Y P
Db1 9 R Y Y Y P
Db1 10 R Y Y Y P
Db1 11 R Y Y Y P
Db1 12 R Y Y Y P
Db1 13 R Y Y Y P
Db1 14 R Y Y Y P
Db1 15 R Y Y Y P
Db1 16 R Y Y Y P
Db1a 17 S Y Y Y P
Db1a 18 S Y Y Y P
Db1a 19 S Y Y Y P
Db1a 20 S Y Y Y P
Db1a 21 S Y Y Y P
Db1a 22 S Y Y Y P
Db1a 23 4ft maintained batten Y Y Y P
Db1a 24 S Y Y Y P
Db1a 25 4ft maintained batten Y Y Y P
Db1a 26 S Y Y Y P
Db1a 27 S Y Y Y P
Db1a 28 S Y Y Y P
Db1a 29 S Y Y Y P
Db1a 30 S Y Y Y P
Db1a 31 S Y Y Y P
Db1a 32 S Y Y Y P
Db1a 33 S Y Y Y P
Db1a 34 S Y Y Y P
Db1a 35 S Y Y Y P
Db1a 36 S Y Y Y P
Db1 37 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
Db1 1 Y Y Y P
Db1 2 Y Y Y P
Db1 3 Y Y Y P
Db1 4 Y Y Y P
Db1 5 Y Y Y P
Db1 6 Y Y Y P
Db1 7 Y Y Y P
Db1 8 Y Y Y P
Db1 9 Y Y Y P
Db1 10 Y Y Y P
Db1 11 Y Y N F Suspension wires damaged. Light hanging by live electrical cable Y N
Db1 12 Y Y Y P
Db1 13 Y Y Y P
Db1 14 Y Y Y P
Db1 15 Y Y Y P
Db1 16 Y Y Y P
Db1 17 Y Y Y P
Db1a 18 Y N Y F Failed 90 min test Y N
Db1a 1920 Y Y Y P
Db1a 21 Y Y Y P
Db1a 22 Y Y Y P
Db1a 23 Y Y Y P
Db1 24 Y Y Y P
Db1a 25 Y Y Y P
Db1a 26 Y Y Y P
Db1a 27 Y Y Y P
Db1a 28 Y Y Y P
Db1a 29 Y Y Y P
Db1a 30 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
5ft led tube on fluro ballast Y
4ft led batten Y
2ft led batten Y
Led ufo high bay Y
1200x300mm led panel Y
600 x 600 led panel Y
External flood lights Y
Led downlight foyer s9523tc Y
Vibe 900mm led linkable battens Y
Led flat panel wall bay light boxes Y
Are there any Warranty items needing to be repaired?No
Geotag photo(s)
  • Have you sent the Geotag photo(s) to maintenance@sturdie.com.au, referring to the Store Location in the email, e.g. Canberra City?
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
4ft LED batten Male toilet 1 Not illuminated Y N N
5ft LED tubes Trading floor 12 Not illuminted Y N N
Square LED panel External adjacent fire door 1 Vandalised Y N N Placed back into position.
Cfl downlight Foyer/entrance 3 Not illuminated Y N N
Cfl downlight Foyer/entrance 1 Dimly lit. On its way out. Last remaining old style cfl downlight onsite Y N N
LED High bay BOH 2 Not illuminated Y N N
LED flat panel light box driver and wiring Aircon 1 Double sided taped to back of light box. Not secured with cable ties. Live cabling within customers reach. Y N N Not installed properly by others . Secured driver and cabling.
Ceiling tile Kinsman 1 Had been removed and not put back Y N N Placed back into position.
Exit light #11 1 Suspension wires damaged. Y N N
Exit light #18 1 Failed 90 min test Y N N
Site Status SelectorStore now fully compliant
Next Test Due in 6 months10/11/2023