Partner NameBuilt Electrical Australia
StateNSW
Date of Visit17/05/2023
Technician's NamePeter Hay
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number50F0001/0051
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWwarrawong

Location NameWarrawong
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
MSB GEN L&P 1 Y P
MSB GEN L&P 2 Y P
MSB GEN L&P 3 Y P
MSB GEN L&P 4 Y P
MSB GEN L&P 8 Y P
MSB GEN L&P 9 Y P
MSB GEN L&P 10 Y P
MSB GEN L&P 11 Y P
MSB GEN L&P 12 Y P
MSB GEN L&P 16 Y P
MSB GEN L&P 17 Y P
MSB GEN L&P 18 Y P
MSB GEN L&P 19 Y P
MSB GEN L&P 20 Y P
MSB GEN L&P 21 Y P
MSB GEN L&P 22 Y P
MSB GEN L&P 23 Y P
MSB GEN L&P 24 Y P
MSB GEN L&P 25 Y P
MSB GEN L&P 26 Y P
MSB GEN L&P 27 Y P
MSB GEN L&P 28 Y P
MSB GEN L&P 29 Y P
MSB GEN L&P 30 Y P
MSB GEN L&P 31 Y P
MSB GEN L&P 32 Y P
MSB GEN L&P 33 Y P
MSB GEN L&P 37 Y P
MSB GEN L&P 38 Y P
MSB GEN L&P 39 Y P
MSB GEN L&P 40 Y P
MSB GEN L&P 41 Y P
MSB GEN L&P 42 Y P
MSB GEN L&P 43 Y P
MSB GEN L&P 44 Y P
MSB GEN L&P 45 Y P
MSB GEN L&P 46 Y P
MSB GEN L&P 47 Y P
MSB GEN L&P 48 Y P
MSB GEN L&P 52 Y P
MSB GEN L&P 53 Y P
MSB GEN L&P 54 Y P
MSB GEN L&P 55 Y P
MSB GEN L&P 56 Y P
MSB GEN L&P 57 Y P
MSB GEN L&P 58 Y P
MSB GEN L&P 59 Y P
MSB GEN L&P 60 Y P
MSB GEN L&P 61 Y P
MSB GEN L&P 62 Y P
MSB GEN L&P 63 Y P
MSB GEN L&P 64 Y P
MSB GEN L&P 65 Y P
MSB GEN L&P 66 Y P
MSB GEN L&P 67 Y P
MSB GEN L&P 71 Y P
MSB GEN L&P 72 Y P
MSB SELLING AREA A 1 Y P
MSB SELLING AREA A 2 Y P
MSB SELLING AREA A 3 Y P
MSB SELLING AREA A 4 Y P
MSB SELLING AREA A 5 Y P
MSB SELLING AREA A 6 Y P
MSB SELLING AREA A 7 Y P
MSB SELLING AREA A 8 Y P
MSB SELLING AREA A 9 Y P
MSB SELLING AREA A 10 Y P
MSB SELLING AREA A 11 Y P
MSB SELLING AREA A 12 Y P
MSB SELLING AREA A 13 Y P
MSB SELLING AREA A 14 Y P
MSB SELLING AREA B 1 Y P
MSB SELLING AREA B 2 Y P
MSB SELLING AREA B 3 Y P
MSB SELLING AREA B 4 Y P
MSB SELLING AREA B 5 Y P
MSB SELLING AREA B 6 Y P
MSB SELLING AREA B 7 Y P
MSB SELLING AREA B 8 Y P
MSB SELLING AREA B 9 Y P
MSB SELLING AREA B 10 Y P
MSB SELLING AREA B 11 Y P
MSB SELLING AREA B 12 Y P
MSB SELLING AREA B 13 Y P
MSB SELLING AREA B 14 Y P
MSB EXTERNAL LIGHTING 1 Y P
MSB EXTERNAL LIGHTING 2 Y P
MSB EXTERNAL LIGHTING 3 Y P
MSB EXTERNAL LIGHTING 4 Y P
MSB EXTERNAL LIGHTING 7 Y P
DB1 1 Y P
DB1 2 Y P
DB1 3 Y P
DB1 4 Y P
DB1 5 Y P
DB1 6 Y P
DB1 7 Y P
DB1 8 Y P
DB1 9 Y P
DB1 10 Y P
DB1 11 Y P
DB1 12 Y P
DB1 13 Y P
DB1 14 Y P
DB1 15 Y P
DB1 16 Y P
DB1 17 Y P
DB1 18 Y P
DB1 19 Y P
DB1 20 Y P
DB1 21 Y P
DB1 22 Y P
DB1 23 Y P
DB1 24 Y P
DB1 26 Y P
DB1 27 Y P
DB1 29 Y P
DB1 31 Y P
DB1 28,30,32 Y P
DB2 1 Y P
DB2 2 Y P
DB2 3 Y P
DB2 4 Y P
DB2 5 Y P
DB2 6 Y P
DB2 7 Y P
DB2 8 Y P
DB2 9 Y P
DB2 10 Y P
DB2 11 Y P
DB2 12 Y P
DB2 13 Y P
DB2 14 Y P
DB2 15 Y P
DB2 16 Y P
DB2 17 Y P
DB2 18 Y P
DB2 19 Y P
DB2 20 Y P
DB2 21 Y P
DB2 22 Y P
DB2 23 Y P
DB2 24 Y P
DB2 25 Y P
DB2 26 Y P
DB2 27 Y P
DB2 28 Y P
DB2 29 Y P
DB2 30 Y P
DB2 31 Y P
DB2 32 Y P
DB2 33 Y P
DB2 35 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB 1 S Y Y Y P
2 S Y Y Y P
3 S Y Y Y P
4 S Y N Y F Failed 90 min test Y N
5 S Y Y Y P
6 S Y Y Y P
7 S Y Y Y P
8 S Y N Y F Failed 90 min test Y N
9 S Y Y Y P
10 S Y Y Y P
11 S Y Y Y P
12 S Y Y Y P
13 S Y Y Y P
14 S Y Y Y P
15 S Y Y Y P
16 S Y Y Y P
17 S Y Y Y P
18 S Y Y Y P
19 S Y Y Y P
20 S Y Y Y P
21 R Y Y Y P
22 R Y Y Y P
23 R Y Y Y P
24 R Y Y Y P
25 R Y Y Y P
26 R Y Y Y P
27 R Y Y Y P
28 R Y Y Y P
29 S Y Y Y P
30 R Y Y Y P
31 S Y Y Y P
32 S Y Y Y P
33 R Y Y Y P
34 S Y Y Y P
35 R Y Y Y P
36 R Y Y Y P
38 R Y Y Y P
39 R Y Y Y P
40 R Y Y Y P
41 R Y Y Y P
44 R Y Y Y P
45 R N/A N/A N/A F No light installed N/A N
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB 1 Y Y Y P
2 Y Y Y P
3 Y Y Y P
4 Y Y Y P
5 Y Y Y P
6 Y Y Y P
7 Y Y Y P
8 Y Y Y P
9 Y Y Y P
10 Y Y Y P
11 Y Y Y P
12 Y Y Y P
13 Y Y Y P
14 Y Y Y P
15 Y Y Y P
16 Y Y Y P
17 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
LED High bays Y
LED 4ft wide body batten Y
Fluoro wall bay Light boxes Y
70mm LED down lights Y
92mm LED down lights Y
External pole floor lights Y
External wall flood lights Y
External eave surface down lights Y
External bunker lights Y
External awning up flood lights Y
Vibe 900ml LED linkable batten Y
Sal 1200ml LED linkable batten Y
Sal 900ml LED linkable batten Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
LED batten (SAL) Kitchen wall bay 3 Not illuminated Y N N Replaced with 6 x VIBE linkables.
External lighting control Main switch board 1 Logo sign not energising N TBA TBA Added to fortnightly repairs list.
Downlight External 1 Missing N TBA TBA Added to fortnightly repairs list.
External pole lights Adjacent main road 2 Not illuminated N TBA TBA Added to fortnightly repairs list.
External awning up flood light Entrance awning 2 Don't appear to be illuminated. Check with store after dark. N TBA TBA Added to fortnightly repairs list.
General Power Outlet Kitchen 1 Not working Y N N
Ceiling not repaired Mezzanine level 2 Cash office and managers office ceilings still not repaired. Exposed wiring. N/A N/A N/A Please advise once repairs complete so we can restore lighting.
External awning ceiling Adj carpark near entrance 1 Not repaired. Exposed wiring. N/A N/A N/A Observation only.
Asko LED strip light Kitchen wall bay 1 Low level strip flickering Y N N
Recessed emergency light #45 1 No ceiling to attach to N/A N/A N/A Please advise once ceiling repairs complete so we can re-install the emergency light.
Surface mount emergency light #4 1 Failed 90 min test Y N N
Surface mount emergency light #8 1 Failed 90 min test Y N N
Site Status SelectorStore now fully compliant
Next Test Due in 6 months17/11/2023