Partner NameBuilt Electrical Australia
StateNSW
Date of Visit14/07/2023
Technician's NamePeter Hay
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number50F0015/0072
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWcampbelltown

Location NameCampbelltown
HTML Block
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Initial/12 Months)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
Db15 1 Y P
Db15 3 Y P
Db15 5 Y P
Db15 7 Y P
Db15 8 Y P
Db15 9 Y P
Db15 10 Y P
Db15 11 Y P
Db15 12 Y P
Db15 13 Y P
Db15 14 Y P
Db15 15 Y P
Db15 16 Y P
Db15 17 Y P
Db15 18 Y P
Db15 19 Y P
Db15 20 Y P
Db15 21 Y P
Db15 23 Y P
Db15 25 Y P
Db15 28 Y P
Db15 39 Y P
Db15 41 Y P
Db15 43 Y P
Db15 44 Y P
Db15 45 Y P
Db15 46 Y P
Db15 47 Y P
Db15 48 Y P
Db15 49 Y P
Db15 50 Y P
Db15 51 Y P
Db15 52 Y P
Db15 53 Y P
Db15 54 Y P
Db15 55 Y P
Db15 56 Y P
Db15 57 Y P
Db15 58 Y P
Db15 59 Y P
Db15 60 Y P
Db1 1 Y P
Db1 2 Y P
Db1 3 Y P
Db1 4 Y P
Db1 5 Y P
Db1 6 Y P
Db1 7 Y P
Db1 8 Y P
Db1 9 Y P
Db1 10 Y P
Db1 11 Y P
Db1 12 Y P
Db1 13 Y P
Db1 14 Y P
Db1 15 Y P
Db1 16 Y P
Db1 17 Y P
Db1 18 Y P
Db1 20 Y P
Db1 22 Y P
Db1 24 Y P
Db1 25 Y P
Db1 26 Y P
Db1 27 Y P
Db1 28 Y P
Db1 30 Y P
Db1 32 Y P
Db1 34 Y P
Db14 3 Y P
Db14 5 Y P
Db14 7 Y P
Db14 8 Y P
Db14 9 Y P
Db14 10 Y P
Db14 11 Y P
Db14 12 Y P
Db14 14 Y P
Db14 16 Y P
Db14 18 Y P
Db14 20 Y P
Db14 22 Y P
Db13 7 Y P
Db13 8 Y P
Db13 9 Y P
Db13 10 Y P
Db13 11 Y P
Db13 12 Y P
Db13 13 Y P
Db13 14 Y P
Db13 15 Y P
Db13 16 Y P
Db13 17 Y P
Db13 18 Y P
Db13 19 Y P
Db13 20 Y P
Db13 21 Y P
Db13 22 Y P
Db13 23 Y P
Db13 24 Y P
Db13 26 Y P
Db13 28 No test No test Locked out/tagged out
Db13 30 Y P
Db13 32 Y P
Db13 34 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB15 1 S Y Y Y P
2 S Y Y Y P
3 S Y Y Y P
4 S Y Y Y P
5 S Y Y Y P
6 S Y Y Y P
7 S Y Y Y P
8 S Y Y Y P
9 S Y Y Y P
10 S Y Y Y P
11 S Y Y Y P
12 R Y N Y F Failed 90 min test Y N
13 S Y Y Y P
14 S Y Y Y P
15 S Y Y Y P
16 S Y Y Y P
17 S Y Y Y P
18 S Y Y Y P
19 S Y Y Y P
20 R Y N Y F Failed 90 min test Y N
21 R Y N Y P
22 R Y Y Y P
23 R Y Y Y P
24 R Y Y Y P
25 R Y Y Y P
26 R Y Y Y P
27 R Y Y Y F Failed 90 Min Test Y N
28 S Y Y Y F Circuit fault Y N
29 S Y Y Y F Circuit fault Y N
30 S N N N F Missing Y N
31 S N N N F Missing Y N
32 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB15 1 Y Y Y P
2 Y Y Y P
3 Y Y Y P
4 Y Y Y P
5 Y Y Y P
6 Y Y Y P
7 Y Y Y P
8 Y Y Y P
9 Y Y Y P
10 Y Y Y P
11 Y Y Y P
12 Y Y Y P
13 Y Y Y P
14 Y Y Y P
15 Y Y Y P
16 Y Y Y P
17 Y Y Y F Circuit fault. Y N
18 Y Y Y P
19 Y Y Y F Circuit fault. Y N
20 Y Y Y P
21 Y Y Y P
22 Y Y Y P
23 Y Y Y P
24 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
High bay ufo Y
LED wall bay Light boxes Y
4ft wide body batten Y
Track lighting wall washers Y
50mm downlights (tv section) Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Bosch Display Near store entrance 1 Tripping CB due to faulty washing machine. Y N N
Surface mount emergency lights BOH 28 + 29 Fault on emergency circuit. Y N N
Exit lights BOH 17 + 19 Fault on emergency lighting circuit. Y N N
Fridge display LG/Samsung 2 Intermittent fault. N N TBA Could not find any faults whilst on site. Tripping is intermittent. If it occurs again, please raise a new work order to further fault find.
4Ft batten BOH entrance 1 Not illuminated Y N N
Recessed emergency light #12 1 Failed 90 min test Y N N
Recessed emergency light #20 1 Failed 90 min test Y N N
Recessed emergency light #27 1 Failed 90 Min Test Y N N
Surface mount emergency light #30 1 Missing Y N N
Surface mount emergency light #31 1 Missing Y N N
Junction box Shop floor 2 Unprotected cabling found on shop floor. Y N N
Site Status SelectorStore now fully compliant
Next Test Due in 6 months12/01/2024