Partner Name | Built Electrical Australia |
---|
State | NSW |
---|
Date of Visit | 17/07/2023 |
---|
Technician's Name | Peter Hay |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 50F0015/0073 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in NSW | tempe |
---|
|
|
---|
Location Name | Tempe |
---|
| |
---|
HTML Block |
|
---|
Test Period | 12 Monthly (90 minutes) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Initial/12 Months) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
Db1 |
1 |
Y |
P |
|
|
Db1 |
2 |
Y |
P |
|
|
Db1 |
3 |
Y |
P |
|
|
Db1 |
4 |
Y |
P |
|
|
Db1 |
5 |
Y |
P |
|
|
Db1 |
6 |
Y |
P |
|
|
Db1 |
7 |
Y |
P |
|
|
Db1 |
8 |
Y |
P |
|
|
Db1 |
9 |
Y |
P |
|
|
Db1 |
10 |
Y |
P |
|
|
Db1 |
11 |
Y |
P |
|
|
Db1 |
12 |
Y |
P |
|
|
Db1 |
13 |
Y |
P |
|
|
Db1 |
14 |
Y |
P |
|
|
Db1 |
15 |
Y |
P |
|
|
Db1 |
16 |
Y |
P |
|
|
Db1 |
17 |
Y |
P |
|
|
Db1 |
18 |
Y |
P |
|
|
Db1 |
19 |
Y |
P |
|
|
Db1 |
20 |
Y |
P |
|
|
Db1 |
21 |
Y |
P |
|
|
Db1 |
22 |
Y |
P |
|
|
Db1 |
23 |
Y |
P |
|
|
Db1 |
24 |
Y |
P |
|
|
Db1 |
26 |
Y |
P |
|
|
Db2 |
? |
Y |
P |
|
|
Db2 |
? |
Y |
P |
|
|
Db2 |
? |
Y |
P |
|
|
Db2 |
? |
Y |
P |
|
|
Db2 |
? |
Y |
P |
|
|
Db2 |
? |
Y |
P |
|
|
Db2a |
17 |
Y |
P |
|
|
Db2a |
19 |
Y |
P |
|
|
Db2a |
21 |
Y |
P |
|
|
Db2a |
23 |
Y |
P |
|
|
Db2a |
25 |
Y |
P |
|
|
Db2a |
27 |
Y |
P |
|
|
Db2a |
29 |
Y |
P |
|
|
Db2a |
30 |
Y |
P |
|
|
Db2a |
31 |
Y |
P |
|
|
Db2a |
32 |
Y |
P |
|
|
Db2a |
33 |
Y |
P |
|
|
Db2a |
34 |
Y |
P |
|
|
Db2a |
35 |
Y |
P |
|
|
Db2a |
36 |
Y |
P |
|
|
Db2a |
37 |
Y |
P |
|
|
Db2a |
38 |
Y |
P |
|
|
Db2a |
39 |
Y |
P |
|
|
Db2a |
40 |
Y |
P |
|
|
Db2a |
41 |
Y |
P |
|
|
Db2a |
42 |
Y |
P |
|
|
Db2a |
43 |
Y |
P |
|
|
Db2a |
44 |
Y |
P |
|
|
Db2a |
45 |
Y |
P |
|
|
Db2a |
46 |
Y |
P |
|
|
Db2a |
47 |
Y |
P |
|
|
Db2a |
48 |
Y |
P |
|
|
Db2a |
49 |
Y |
P |
|
|
Db2a |
50 |
Y |
P |
|
|
Db2a |
51 |
Y |
P |
|
|
Db2a |
52 |
Y |
P |
|
|
Db2a |
53 |
Y |
P |
|
|
Db2a |
54 |
Y |
P |
|
|
Db2a |
55 |
Y |
P |
|
|
Db2a |
56 |
Y |
P |
|
|
Db2a |
57 |
Y |
P |
|
|
Db2a |
58 |
Y |
P |
|
|
Db2a |
59 |
Y |
P |
|
|
Db2a |
60 |
Y |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
HTML Block |
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
LED High Bays 150W |
Y |
LED Downlight 210mm 31W S9075DP WH |
Y |
Ledline 4ft 40W SLD4000CW |
Y |
LED Strip Display Signs DC24V |
Y |
LED Downlight 11W S9071CP WH |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
DB Labels |
DBA + DB2 |
2 |
Labelling incorrect or missing |
N |
TBA |
TBA |
Added to fortnightly repairs list. |
Kitchen wall bays |
Trading floor |
3 |
Not illuminated |
Y |
N |
N |
3 battens and 2 x gu10 lamps replaced |
Sony TV wall bay |
TV area |
1 |
No power |
Y |
N |
N |
Domestic power board had tripped. |
Blue LED strip light |
Hisense TV wall bay |
1 |
Flickering |
N |
N |
N |
Replaced driver. Still flickering. Disconnected driver. Please contact vendor to repair. |
Free standing tv display |
TV area |
1 |
No power dropper or soft wiring |
N |
TBA |
TBA |
Observation only. Added to fortnightly repairs list. |
Electrolux vacuums end cap |
Vacuums |
1 |
No power |
N |
TBA |
TBA |
Supplier funded stand. Please raise new work order if you would like Sturdie to repair. |
Vintec fridge display |
Fridges |
1 |
No power dropper |
N |
TBA |
TBA |
Observation only. Added to fortnightly repairs list. |
LED flat panel wall bay light boxes |
Bar fridges |
2 |
Faulty |
N |
TBA |
TBA |
Please contact vendor to repair. |
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 17/01/2024 |
---|
| |
---|
| |