Partner NameBuilt Electrical Australia
StateNSW
Date of Visit25/07/2023
Technician's NamePeter Hay
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number50F0015/0074
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWblacktown

Location NameBlacktown
HTML Block
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Initial/12 Months)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
Db1 17 Y P
Db1 18 Y P
Db1 19 Y P
Db1 20 Y P
Db1 21 Y P
Db1 22 Y P
Db1 23 Y P
Db1 24 Y P
Db1 25 Y P
Db1 26 Y P
Db1 27 Y P
Db1 28 Y P
Db1 29 Y P
Db1 32 Y P
Db1 34 Y P
Db1 36 Y P
Db1b 1 Y P
Db1b 2 Y P
Db1b 3 Y P
Db1b 4 Y P
Db1b 5 Y P
Db1b 6 Y P
Db1b 7 Y P
Db1b 8 Y P
Db1b 9 Y P
Db1b 10 Y P
Db1b 11 Y P
Db2 3 Y P
Db2 5 Y P
Db2 6 Y P
Db2 7 Y P
Db2 10 Y P
Db2 12 Y P
Db2 14 Y P
Db2 22 Y P
Db2 24 Y P
Db3 4 Y P
Db3 6 Y P
Db3 8 Y P
Db3 10 Y P
Db3 15 Y P
Db3 16 Y P
Db3 18 Y P
Db3 20 Y P
Db3 22 Y P
Db3 28 Y P
Db3 30 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
1 S Y Y Y P
2 S Y Y Y P
3 S Y Y Y P
4 R Y Y Y P
5 S Y Y Y P
6 S Y Y Y P
7 S Y Y Y P
8 S Y Y Y P
9 S Y Y Y P
10 S Y Y Y P
11 S Y Y Y P
12 S Y Y Y P
13 S Y Y Y P
14 R Y Y Y P
15 R Y Y Y P
16 R Y Y Y P
17 S Y Y Y P
18 S Y Y Y P
19 S Y Y Y P
20 S Y Y Y P
21 S Y Y Y P
22 S Y Y Y P
23 S Y Y Y P
24 S Y Y Y P
25 S Y Y Y P
26 S Y Y Y P
27 S Y Y Y P
28 R Y N Y F Failed 90 min test Y N
29 R Y Y Y P
30 R Y Y Y P
31 R Y Y Y P
32 R Y Y Y P
33 R Y Y Y P
34 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
1 Y Y Y P
2 Y Y Y P
3 Y Y Y P
4 Y Y Y P
5 Y Y Y P
6 Y Y Y P
7 Y Y Y P
8 Y Y Y P
9 Y Y Y P
10 Y Y Y P
11 Y Y Y P
12 Y Y Y P
13 Y Y Y P
14 Y Y Y P
15 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
LED high bay ufo's Y
4ft battens Y
2ft battens (toilets) Y
92mm downlights Y
LED linkables (kitchen wall bays) Y
LED slim wall bay Light boxes Y
70mm downlights (tv section) Y
160mm downlight (foyer) Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Db1 Adjacent sales counter 1 Rcd upgrade required N TBA TBA Added to fortnightly repairs list.
Db2 TV section 1 Rcd upgrade required N TBA TBA Added to fortnightly repairs list.
Db3 Boh office 1 Rcd upgrade required N TBA TBA Added to fortnightly repairs list.
Sony sound bars wall bay Audio 1 Flickering light N N TBA Supplier funded stand. Please raise a new work order if you would like Sturdie to repair.
Ultimate ears display Bluetooth speakers 1 Flickering light N N TBA Supplier funded stand. Please raise a new work order if you would like Sturdie to repair.
Samsung TV display TV section 1 Dropper need to be relocated N N N Observation only. Scissor lift requried.
Wall bay LED light boxes Fridges 2 Faulty N N TBA Supplier funded stand. Please raise a new work order if you would like Sturdie to repair.
Webber display Kitchen section 1 No power dropper N N N Observation only. Scissor lift requried.
Technika wall bay Kitchens 1 Batten faulty Y N N
92mm downlights Ovens display 4 Not illuminated Y N N
Smeg wall bay Kitchen 1 2 x Battens faulty Y N N
Dishwasher island display lighting Kitchen 3 Pendant lights not illuminated Y N N
Solt/dishwasher display Kitchen 2 Lighting not illuminated N N TBA Supplier funded stand. Please raise a new work order if you would like Sturdie to repair.
Asko kitchen wall bay Kitchen 1 Not powered Y N N
Westinghouse kitchen wall bay Kitchen 1 4 x battens not illuminated Y N N
4ft Batten Cash Office 1 Hanging down. Held in by1 side only Y N N Reattached light to ceiling.
Db2 Schedule TV section 1 Not accurate N TBA TBA Added to fortnightly repairs list.
Site Status SelectorStore now fully compliant
Next Test Due in 6 months25/01/2024