Partner NameBuilt Electrical Australia
StateVIC
Date of Visit10/08/2023
Technician's NameAnthony Zammit
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number50F0017/0125
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICmaribyrnong

Location NameMaribyrnong
HTML Block
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Initial/12 Months)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB1-A 1 Y P
DB1-A 2 Y P
DB1-A 3 Y P
DB1-A 5 Y P
DB1-A 7 Y P
DB1-A 8 Y P
DB1-A 9 Y P
DB1-A 10 Y P
DB1-A 11 Y P
DB1-A 17 Y P
DB1-A 19 Y P
DB1-A 21 Y P
DB1-A 27 Y P
DB1-A 29 Y P
DB1-A 31 Y P
DB1-B 1 Y P
DB1-B 2 Y P
DB1-B 3 Y P
DB1-B 4 Y P
DB1-B 5 Y P
DB1-B 6 Y P
DB1-B 7 Y P
DB1-B 8 Y P
DB1-B 9 Y P
DB1-B 10 Y P
DB1-B 11 Y P
DB1-B 12 Y P
DB1-B 13 Y P
DB1-B 14 Y P
DB1-B 15 Y P
DB1-B 16 Y P
DB1-B 17 Y P
DB1-B 18 Y P
DB1-B 19 Y P
DB1-B 20 Y P
DB1-B 21 Y P
DB1-B 22 Y P
DB1-B 23 Y P
DB1-B 24 Y P
DB1-B 25 Y P
DB1-B 26 Y P
DB1-B 27 Y P
DB1-B 28 Y P
DB1-B 29 Y P
DB1-B 30 Y P
DB1-B 31 Y P
DB1-B 32 Y P
DB1-B 33 Y P
DB1-B 34 Y P
DB1-B 35 Y P
DB1-B 36 Y P
DB1-B 37 Y P
DB1-B 38 Y P
DB1-B 39 Y P
DB1-B 40 Y P
DB1-B 41 Y P
DB1-B 42 Y P
DB1-B 43 Y P
DB1-B 44 Y P
DB1-B 45 Y P
DB1-B 46 Y P
DB1-B 47 Y P
DB1-B 48 Y P
DB1-B 49 Y P
DB1-B 50 Y P
DB1-B 52 Y P
DB1-B 54 Y P
DB2 1 Y P
DB2 2 Y P
DB2 3 Y P
DB2 4 Y P
DB2 5 Y P
DB2 6 Y P
DB2 7 Y P
DB2 8 Y P
DB2 9 Y P
DB2 10 Y P
DB2 11 Y P
DB2 12 Y P
DB2 13 Y P
DB2 14 Y P
DB2 15 Y P
DB2 16 Y P
DB2 17 Y P
DB2 18 Y P
DB2 19 Y P
DB2 20 Y P
DB2 21 Y P
DB2 22 Y P
DB2 23 Y P
DB2 24 Y P
DB2 25 Y P
DB2 26 Y P
DB2 27 Y P
DB2 28 Y P
DB2 29 Y P
DB2 30 Y P
DB2 31 Y P
DB2 32 Y P
DB2 33 Y P
DB2 34 Y P
DB2 35 Y P
DB2 36 Y P
DB2 37 Y P
DB2 38 Y P
DB2 39 Y P
DB2 40 Y P
DB2 41 Y P
DB2 42 Y P
DB2 44 Y P
DB2 46 Y P
DB2 48 Y P
DB2 49 Y P
DB2 50 Y P
DB2 51 Y P
DB2 52 Y P
DB2 53 Y P
DB2 54 Y P
DB2 55 Y P
DB2 56 Y P
DB2 57 Y P
DB2 58 Y P
DB2 59 Y P
DB2 60 Y P
DB2 62 Y P
DB2 64 Y P
DB2 66 Y P
DB2 67 Y P
DB2 68 Y P
DB2 69 Y P
DB2 70 Y P
DB2 71 Y P
DB2 72 Y P
DB2 73 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-2 2 R Y Y Y P
DB-2 6 S Y Y Y P
DB-2 7 S Y Y Y P
Db-2 9 S Y Y Y P
DB-2 11 S Y Y Y P
DB-2 13 S Y Y Y P
DB-2 14 S Y Y Y P
DB-2 17 S Y Y Y P
DB-2 18 S Y Y Y P
DB-2 19 S Y Y Y P
DB-2 20 R Y Y Y P
DB-2 22 R Y Y Y P
DB-2 23 S N N Y F Failed to illuminate Y N
DB-2 24 S Y Y Y P
DB-2 26 S Y Y Y P
DB-2 27 S Y Y Y P
DB-2 28 S Y Y Y P
DB-2 29 S Y Y Y P
DB-3 30 S Y Y Y P
DB-3 31 S Y Y Y P
DB-3 32 S Y Y Y P
DB-3 36 R Y Y Y P
DB-3 39 R Y Y Y P
DB-3 40 S Y Y Y P
DB-3 42 R Y Y Y P
DB-3 43 R Y Y Y P
DB-3 44 R Y Y Y P
DB-2 46 R Y Y Y P
DB-2 47 R Y Y Y P
DB-2 48 R Y Y Y P
DB-2 49 R Y Y Y P
DB-2 50 R Y Y Y P
DB-2 51 R Y Y Y P
DB-2 52 S Y Y Y P
DB-2 53 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-2 1 Y Y Y P
DB-2 3 Y Y Y P
DB-2 4 Y Y Y P
DB-2 5 Y Y Y P
DB-2 8 Y Y Y P
DB-2 10 Y Y Y P
DB-2 12 Y Y Y P
DB-2 15 Y Y Y P
DB-2 16 Y Y Y P
DB-2 21 Y Y Y P
DB-2 23 Y Y Y P
DB-2 25 Y Y Y P
DB-3 33 Y Y Y P
DB-3 34 Y Y Y P
DB-3 35 Y Y Y P
DB-3 36 Y Y Y P
DB-3 37 Y Y Y P
DB-3 41 Y Y Y P
DB-3 45 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
LED highbay Y
LED down lights Y
T5 bare batten twin Y
T5 single defused Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Surface mount emergency light #23 Above Kinsman display 1 Failed to illuminate / failed 90min emergency battery test Y N N
LED high-bay Shop floor 13 Failed to illuminate correctly N N N Being completed under Work Order 1461572
70mm LED downlight TV zone 1 Failed to illuminate Y N N
Switchboard legend DB2 AND DB1 3 Update to new format. Update circuits N TBA TBA Added to fortnightly repairs report
Site Status SelectorStore now fully compliant
Next Test Due in 6 months10/02/2024