Partner NameSturdie Trade Services
StateVIC
Date of Visit15/08/2023
Technician's NameNathan McBain
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number50F0017/0083
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICgeelong

Location NameGeelong
HTML Block
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Initial/12 Months)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB1 SEC A 01 Y P
DB1 SEC A 03 Y P
DB1 SEC A 05 Y P
DB1 SEC A 07 Y P
DB1 SEC A 09 Y P
DB1 SEC A 11 Y P
DB1 SEC A 13 Y P
DB1 SEC A 15 Y P
DB1 SEC A 17 Y P
DB1 SEC A 19 Y P
DB1 SEC A 21 Y P
DB1 SEC A 23 Y P
DB1 SEC A 25 Y P
DB1 SEC A 26 Y P
DB1 SEC A 27 Y P
DB1 SEC A 29 Y P
DB1 SEC A 34 Y P
DB1 SEC A 36 Y P
DB1 SEC A 38 Y P
DB1 SEC A 44 Y P
DB1 SEC A 46 Y P
DB1 SEC A 48 Y P
DB1 SEC B 01 Y P
DB1 SEC B 02 Y P
DB1 SEC B 03 Y P
DB1 SEC B 05 Y P
DB1 SEC B 06 Y P
DB1 SEC B 07 Y P
DB1 SEC B 08 Y P
DB1 SEC B 09 Y P
DB1 SEC B 10 Y P
DB1 SEC B 11 Y P
DB1 SEC B 12 Y P
DB1 SEC B 13 Y P
DB1 SEC B 14 Y P
DB1 SEC B 15 Y P
DB1 SEC B 16 Y P
DB1 SEC B 17 Y P
DB1 SEC B 18 Y P
DB1 SEC B 19 Y P
DB1 SEC B 20 Y P
DB1 SEC B 21 Y P
DB1 SEC B 22 Y P
DB1 SEC B 23 Y P
DB1 SEC B 24 Y P
DB1 SEC B 25 Y P
DB1 SEC B 26 Y P
DB1 SEC B 27 Y P
DB1 SEC B 29 Y P
DB1 SEC B 31 Y P
DB1 SEC B 33 Y P
DB1 SEC B 35 Y P
DB2 03 Y P
DB2 05 Y P
DB2 07 Y P
DB2 09 Y P
DB2 11 Y P
DB2 13 Y P
DB2 15 Y P
DB2 17 Y P
DB2 19 Y P
DB2 21 Y P
DB2 23 Y P
DB2 25 Y P
DB2 27 Y P
DB2 29 Y P
DB2 31 Y P
DB2 32 Y P
DB2 33 Y P
DB2 34 Y P
DB2 35 Y P
DB2 36 Y P
DB2 37 Y P
DB2 39 Y P
DB2 41 Y P
DB2 42 Y P
DB2 43 Y P
DB2 44 Y P
DB2 45 Y P
DB2 46 Y P
DB2 47 Y P
DB2 48 Y P
DB2 49 Y P
DB2 50 Y P
DB2 51 Y P
DB2 52 Y P
DB2 53 Y P
DB2 54 Y P
DB2 55 Y P
DB2 56 Y P
DB2 58 Y P
DB2 60 Y P
DB3 01 Y P
DB3 03 Y P
DB3 05 Y P
DB3 14 Y P
DB3 23 Y P
DB3 24 Y P
DB3 25 Y P
DB3 26 Y P
DB3 27 Y P
DB3 28 Y P
DB3 29 Y P
DB3 30 Y P
DB3 31 Y P
DB3 32 Y P
DB3 33 Y P
DB3 34 Y P
DB3 35 Y P
DB3 36 Y P
DB3 37 Y P
DB3 38 Y P
DB3 40 Y P
DB3 42 Y P
DB3 45 Y P
DB3 47 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-1 1 S Y Y Y P
DB-1 2 R Y Y Y P
DB-1 3 S Y Y Y P
DB-1 4 S Y Y Y P
DB-1 5 S Y Y Y P
DB-1 6 S Y Y Y P
DB-1 7 S Y Y Y P
DB-1 8 S Y Y Y P
DB-1 9 S Y Y Y P
DB-1 10 S Y Y Y P
DB-1 19 R Y Y Y P
DB-1 11 S Y Y Y P
DB-1 12 S Y N Y F FAILED 90MIN DISCHARGE TEST Y N
DB-1 13 S Y Y Y P
DB-1 14 S Y N Y F FAILED 90MIN DISCHARGE TEST Y N
DB-1 15 S Y Y Y P
DB-1 16 S Y Y Y P
DB-1 17 S Y Y Y P
DB-1 18 S Y Y Y P
DB-1 19 S Y Y Y P
DB-1 20 S Y Y Y P
DB-1 21 S Y Y Y P
DB-1 22 R Y Y Y P
DB-1 23 R Y Y Y P
DB-1 24 S Y Y Y P
DB-1 25 S Y Y Y P
DB-1 26 S Y Y Y P
DB-1 27 S Y Y Y P
DB-1 28 S Y Y Y P
DB-1 29 S Y Y Y P
DB-1 30 S Y Y Y P
DB-1 31 S Y Y Y P
DB-1 32 S Y Y Y P
DB-1 33 S Y Y Y P
DB-1 34 S Y Y Y P
DB-1 35 S Y Y Y P
DB-1 36 S Y Y Y P
DB-1 37 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-1 1 Y Y Y P
DB-1 2 Y Y Y P
DB-1 3 Y Y Y P
DB-1 4 Y Y Y P
DB-1 5 Y Y Y P
DB-1 6 Y Y Y P
DB-1 7 Y Y Y P
DB-1 8 Y Y Y P
DB-1 9 Y Y Y P
DB-1 10 Y Y Y P
DB-1 11 Y Y Y P
DB-1 12 Y Y Y P
DB-1 13 Y Y Y P
DB-1 14 Y Y Y P
DB-1 15 Y Y Y P
DB-1 16 Y N Y F FAILED 90MIN DISCHARGE TEST Y N
DB-1 17 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Hi-Bay Y
36W Twin batten lights Y
50W halogen down lights Y
90MM LED Downlight Y
Clevertronics Exit Y
Davis Maintained emergency led batten Y
Clevertronics Surface mount emergency Y
Clervertronics Recessed emergency Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
TEST AND TAG STORE 80+ TEST AND TAG IN-DATE, NEXT TEST DUE 02 MARCH 2024 N N N OBSERVATION
HIBAY BOH 1 FAILED TO ILLUMINATE Y N N
FLOODLIGHTS EXTERNAL STORE FRONT 7 FAILED TO ILLUMINATE N N N COMPLETED ON APPROVED QUOTED WORKS # 0132
EM (14) MEZZ FLOOR BOH 1 FAILED 90MIN DISCHARGE TEST Y N N
EM (12) MEZZ FLOOR BOH 1 FAILED 90MIN DISCHARGE TEST Y N N
EX (16) UNDER MEZZ FLOOR BOH 1 FAILED 90MIN DISCHARGE TEST Y N N
35W LED BATTEN UNDER MEZZ FLOOR 1 DAMAGE DIFFUSER Y N N
Site Status SelectorStore now fully compliant
Next Test Due in 6 months15/02/2024