Partner NameSturdie Trade Services
StateVIC
Date of Visit27/09/2023
Technician's NameAmazigh Tari
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number50F0017/0091
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICmoorabbin

Location NameMoorabbin
HTML Block
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Initial/12 Months)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
Db-9A2 2 Y P
Db-9A2 4 Y P
Db-9A2 6 Y P
Db-9A2 7 Y P
Db-9A2 8 Y P
Db-9A2 9 Y P
Db-9A2 10 Y P
Db-9A2 11 Y P
Db-9A2 12 Y P
Db-9A2 13 Y P
Db-9A2 14 Y P
Db-9A2 15 Y P
Db-9A2 16 Y P
Db-9A2 17 Y P
Db-9A2 18 Y P
Db-9A2 19 Y P
Db-9A2 20 Y P
Db-9A2 21 Y P
Db-9A2 22 Y P
Db-9A2 23 Y P
Db-9A2 24 Y P
Db-9A2 25 Y P
Db-9A2 26 Y P
Db-9A2 27 Y P
Db-9A2 28 Y P
Db-9A2 29 Y P
Db-9A2 30 Y P
Db-9A2 32 Y P
Db-9A2 34 Y P
Db-9A2 36 Y P
Db-T9A1 7 Y P
Db-T9A1 8 Y P
Db-T9A1 9 Y P
Db-T9A1 10 Y P
Db-T9A1 11 Y P
Db-T9A1 12 Y P
Db-T9A1 13 Y P
Db-T9A1 14 Y P
Db-T9A1 15 Y P
Db-T9A1 16 Y P
Db-T9A1 17 Y P
Db-T9A1 18 Y P
Db-T9A1 19 Y P
Db-T9A1 20 Y P
Db-T9A1 21 Y P
Db-T9A1 22 Y P
Db-T9A1 23 Y P
Db-T9A1 24 Y P
Db-T9A1 25 Y P
Db-T9A1 26 Y P
Db-T9A1 27 Y P
Db-T9A1 28 Y P
Db-T9A1 29 Y P
Db-T9A1 30 Y P
Db-T9A1 31 Y P
Db-T9A1 32 Y P
Db-T9A1 33 Y P
Db-T9A1 34 Y P
Db-T9A1 35 Y P
Db-T9A1 36 Y P
Db-T9A1 37 Y P
Db-T9A1 38 Y P
Db-T9A1 39 Y P
Db-T9A1 40 Y P
Db-T9A1 41 Y P
Db-T9A1 42 Y P
Db-T9A1 44 Y P
Db-T9A1 46 Y P
Db-T9A1 48 Y P
Db-T9A1 Lights 1 Y P
Db-T9A1 Lights 2 Y P
Db-T9A1 Lights 3 Y P
Db-T9A1 Lights 4 Y P
Db-T9A1 Lights 5 Y P
Db-T9A1 Lights 6 Y P
Db-T9A1 Lights 7 Y P
Db-T9A1 Lights 8 Y P
Db-T9A1 Lights 9 Y P
Db-T9A1 Lights 10 Y P
Db-T9A1 Lights 11 Y P
Db-T9A1 Lights 12 Y P
Db-T9A1 Lights 13 Y P
Db-T9A1 Lights 14 Y P
Db-T9A1 Lights 15 Y P
Db-T9A1 Lights 16 Y P
Db-T9A1 Lights 17 Y P
Db-T9A1 Lights 18 Y P
Db-T9A1 Lights 19 Y P
Db-T9A1 Lights 20 Y P
Db-T9A1 Lights 21 Y P
Db-T9A1 Lights 22 Y P
Db-T9A1 Lights 23 Y P
Db-T9A1 Lights 24 Y P
Db-T9A1 Lights 26 Y P
Db-T9A3 1 Y P
Db-T9A3 2 Y P
Db-T9A3 3 Y P
Db-T9A3 4 Y P
Db-T9A3 5 Y P
Db-T9A3 6 Y P
Db-T9A3 7 Y P
Db-T9A3 8 Y P
Db-T9A3 9 Y P
Db-T9A3 10 Y P
Db-T9A3 11 Y P
Db-T9A3 12 Y P
Db-T9A3 13 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-T9A1 2 R Y Y Y P
DB-T9A1 5 R Y Y Y P
DB- T9A1 6 R Y Y Y P
DB-T9A1 7 R Y Y Y P
DB-T9A1 8 R Y Y Y P
DB-T9A1 10 S Y Y Y P
DB-T9A1 11 S Y Y Y P
DB-T9A1 12 S Y Y Y P
DB-T9A1 16 R Y Y Y P
DB-T9A1 18 S Y Y Y P
DB-T9A1 19 S Y Y Y P
DB-T9A1 21 S Y Y Y P
DB-T9A1 22 S Y Y Y P
DB-T9A1 23 S Y Y Y P
DB-T9A1 24 S Y Y Y P
DB-T9A1 28 R Y Y Y P
DB-T9A1 29 R Y Y Y P
DB-T9A1 30 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-T9A1 1 Y Y Y P
DB- T9A1 3 Y Y Y P
DB- T9A1 4 Y Y Y P
DB-T9A1 9 Y Y Y P
DB-T9A1 13 Y Y Y P
DB-T9A1 14 Y Y Y P
DB-T9A1 15 Y Y Y P
DB-T9A1 17 Y Y Y P
DB-T9A1 20 Y Y Y P
DB-T9A1 25 Y Y Y P
DB-T9A1 26 Y Y Y P
DB-T9A1 27 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Hi-bay lights LED Y
36W diffuser LED Y
Square Hi-bay lights LED Y
72mm downlight Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
High bay light Cooktops 1 Failed to illuminate Y N N
Test & tag Store 80+ Tested 3/5/23 due 3/5/24 N N N Observation
Blue LED strip Tv's 1 x 5 metre strip + driver Flickering Y N N
Site Status SelectorStore now fully compliant
Next Test Due in 6 months27/03/2024