Partner NameBuilt Electrical Australia
StateNSW
Date of Visit29/09/2023
Technician's NamePeter Hay
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number50F0015/0088
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWchatswood

Location NameChatswood
HTML Block
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Initial/12 Months)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
Db1 1 Y P
Db1 2 Y P
Db1 3 Y P
Db1 4 Y P
Db1 5 Y P
Db1 6 Y P
Db1 7 Y P
Db1 8 Y P
Db1 9 Y P
Db1 10 Y P
Db1 11 Y P
Db1 12 Y P
Db1 13 Y P
Db1 14 Y P
Db1 15 Y P
Db1 16 Y P
Db1 17 Y P
Db1 18 Y P
Db1 19 Y P
Db1 20 Y P
Db1 21 Y P
Db1 22 Y P
Db1 23 Y P
Db1 24 Y P
Db1 25 Y P
Db1 26 Y P
Db1 27 Y P
Db1 28 Y P
Db1 29 Y P
Db1 30 Y P
Db1 31 Y P
Db1 32 Y P
Db1 33 Y P
Db1 34 Y P
Db1 36 Y P
Db1 37 Y P
Db1 38 Y P
Db1 39 Y P
Db1 40 Y P
Db1 41 Y P
Db1 42 Y P
Db1 43 Y P
Db1 44 Y P
Db1 46 Y P
Db1 47 Y P
Db1 48 Y P
Db2 1 Y P
Db2 2 Y P
Db2 3 Y P
Db2 4 Y P
Db2 5 Y P
Db2 6 Y P
Db2 7 Y P
Db2 8 Y P
Db2 9 Y P
Db2 10 Y P
Db2 11 Y P
Db2 12 Y P
Db2 13 Y P
Db2 14 Y P
Db2 15 Y P
Db2 16 Y P
Db2 17 Y P
Db2 18 Y P
Db2 19 Y P
Db2 20 Y P
Db2 21 Y P
Db2 22 Y P
Db2 23 Y P
Db2 24 Y P
Db2 25 Y P
Db2 26 Y P
Db2 27 Y P
Db2 28 Y P
Db2 29 Y P
Db2 30 Y P
Db2 31 Y P
Db2 32 Y P
Db2 33 Y P
Db2 34 Y P
Db2 35 Y P
Db2 36 Y P
Db2 37 Y P
Db2 38 Y P
Db2 39 Y P
Db2 40 Y P
Db2 41 Y P
Db2 42 Y P
Db2 43 Y P
Db2 44 Y P
Db2 45 Y P
Db2 46 Y P
Db2 47 Y P
Db2 48 Y P
Db2 49 Y P
Db2 50 Y P
Db2 51 Y P
Db2 52 Y P
Db2 53 Y P
Db2 54 Y P
Db2 55 Y P
Db2 56 Y P
Db2 57 Y P
Db2 58 Y P
Db2 59 Y P
Db2 60 Y P
Db2 61 Y P
Db2 62 Y P
Db2 63 Y P
Db2 64 Y P
Db2 65 Y P
Db2 66 Y P
Db2 67 Y P
Db2 68 Y P
Db2 69 Y P
Db2 70 Y P
Db2 71 Y P
Db2 72 Y P
Db2 73 Y P
Db2 74 Y P
Db2 75 Y P
Db2 76 Y P
Db2 77 Y P
Db2 78 Y P
Db2 79 Y P
Db2 80 Y P
Db2 81 Y P
Db2 82 Y P
Db2 83 Y P
Db2 84 Y P
Db2 85 Y P
Db2 86 Y P
Db2 87 Y P
Db2 88 Y P
Db2 89 Y P
Db2 90 Y P
Db2 91 Y P
Db2 92 Y P
Db2 93 Y P
Db2 94 Y P
Db2 95 Y P
Db3 1 Y P
Db3 2 Y P
Db3 3 Y P
Db3 4 Y P
Db3 5 Y P
Db3 6 Y P
Db3 7 Y P
Db3 8 Y P
Db3 10 Y P
Db3 11 Y P
Db3 13 Y P
Db3 14 Y P
Db3 16 Y P
Db3 18 Y P
Db3 28 Y P
Db4 4,5,6 Y P
Db4 10 Y P
Db4 11 Y P
Db4 12 Y P
Db5 1 Y P
Db5 2 Y P
Db5 4 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 T/Sw 1 S Y Y Y P
DB1 T/Sw 2 S Y Y Y P
DB1 T/Sw 3 S Y Y Y P
DB1 T/Sw 5 S Y Y Y P
DB1 T/Sw 6 S Y Y Y P
DB1 T/Sw 8 S Y Y Y P
DB1 T/Sw 9 S Y Y Y P
DB1 T/Sw 11 S Y Y Y P
DB1 T/Sw 12 S Y Y Y P
DB1 T/Sw 15 S Y Y Y P
DB1 T/Sw 19 S Y Y Y P
DB1 T/Sw 21 S Y Y Y P
DB1 T/Sw 22 S Y Y Y P
DB1 T/Sw 26 S Y Y Y P
DB1 T/Sw 27 S Y Y Y P
DB1 T/Sw 30 S Y Y Y P
DB1 T/Sw 32 S Y Y Y P
DB1 T/Sw 33 S Y Y Y P
DB1 T/Sw 34 S Y Y Y P
DB1 T/Sw 35 S Y Y Y P
DB1 T/Sw 40 S Y Y Y P
DB1 T/Sw 41 S Y Y Y P
DB1 T/Sw 43 S Y Y Y P
DB1 T/Sw 46 S Y Y Y P
DB1 T/Sw 47 S Y Y Y P
DB1 T/Sw 48 S Y Y Y P
DB1 T/Sw 49 S Y Y Y P
DB1 T/Sw 50 R Y Y Y P
DB1 T/Sw 52 R Y Y Y P
DB1 T/Sw 54 R Y Y Y P
DB1 T/Sw 55 R Y Y Y P
DB1 T/Sw 57 R Y Y Y P
DB1 T/Sw 58 R Y Y Y P
DB1 T/Sw 59 R Y Y Y P
DB1 T/Sw 62 R Y Y Y P
DB1 T/Sw 64 S - 4ft Y Y Y P
DB1 T/Sw 65 S - 4ft Y Y Y P
DB1 T/Sw 66 S - 4ft Y Y Y P
DB1 T/Sw 68 R Y Y Y P
DB1 T/Sw 69 R Y Y Y P
DB1 T/Sw 71 R Y Y Y P
DB1 T/Sw 72 R Y Y Y P
DB1 T/Sw 74 R Y Y Y P
DB1 T/Sw 76 S Y Y Y P
DB1 T/Sw 77 S - 4ft Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 T/Sw 4 Y Y Y P
DB1 T/Sw 7 Y Y Y P
DB1 T/Sw 10 Y Y Y P
DB1 T/Sw 13 Y Y N F Jack chain support damaged. Y N
DB1 T/Sw 14 Y Y Y P
DB1 T/Sw 16 Y Y Y P
DB1 T/Sw 17 Y Y Y P
DB1 T/Sw 18 Y Y Y P
DB1 T/Sw 20 Y Y Y P
DB1 T/Sw 23 Y Y Y P
DB1 T/Sw 24 Y Y Y P
DB1 T/Sw 25 Y Y Y P
DB1 T/Sw 28 Y Y Y P
DB1 T/Sw 29 Y Y Y P
DB1 T/Sw 31 Y Y Y P
DB1 T/Sw 36 Y Y Y P
DB1 T/Sw 37 Y Y Y P
DB1 T/Sw 38 Y Y Y P
DB1 T/Sw 39 Y Y Y P
DB1 T/Sw 42 Y Y Y P
DB1 T/Sw 44 Y Y Y P
DB1 T/Sw 45 Y Y Y P
DB1 T/Sw 51 Y Y Y P
DB1 T/Sw 53 Y Y Y P
DB1 T/Sw 56 Y Y Y P
DB1 T/Sw 60 Y Y Y P
DB1 T/Sw 61 Y Y Y P
DB1 T/Sw 63 Y Y Y P
DB1 T/Sw 67 Y Y Y P
DB1 T/Sw 70 Y Y Y P
DB1 T/Sw 73 Y Y Y P
DB1 T/Sw 75 Y Y Y P
DB1 T/Sw 78 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Hi Bay Ufo's Y
1200x300mm led panels Y
4ft battens Y
Track mounted spot lights Y
Track mounted linear lights Y
Track mounted wall washers Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Exit light #13 1 Jack chain support damaged Y N N Jack chain support damaged. Cable dislodged from outlet. Repaired jack chain. Plugged back into socket
Site Status SelectorStore now fully compliant
Next Test Due in 6 months29/03/2024