Partner Name | Built Electrical Australia |
---|
State | NSW |
---|
Date of Visit | 29/09/2023 |
---|
Technician's Name | Peter Hay |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 50F0015/0088 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in NSW | chatswood |
---|
|
|
---|
Location Name | Chatswood |
---|
| |
---|
HTML Block |
|
---|
Test Period | 12 Monthly (90 minutes) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Initial/12 Months) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
Db1 |
1 |
Y |
P |
|
|
Db1 |
2 |
Y |
P |
|
|
Db1 |
3 |
Y |
P |
|
|
Db1 |
4 |
Y |
P |
|
|
Db1 |
5 |
Y |
P |
|
|
Db1 |
6 |
Y |
P |
|
|
Db1 |
7 |
Y |
P |
|
|
Db1 |
8 |
Y |
P |
|
|
Db1 |
9 |
Y |
P |
|
|
Db1 |
10 |
Y |
P |
|
|
Db1 |
11 |
Y |
P |
|
|
Db1 |
12 |
Y |
P |
|
|
Db1 |
13 |
Y |
P |
|
|
Db1 |
14 |
Y |
P |
|
|
Db1 |
15 |
Y |
P |
|
|
Db1 |
16 |
Y |
P |
|
|
Db1 |
17 |
Y |
P |
|
|
Db1 |
18 |
Y |
P |
|
|
Db1 |
19 |
Y |
P |
|
|
Db1 |
20 |
Y |
P |
|
|
Db1 |
21 |
Y |
P |
|
|
Db1 |
22 |
Y |
P |
|
|
Db1 |
23 |
Y |
P |
|
|
Db1 |
24 |
Y |
P |
|
|
Db1 |
25 |
Y |
P |
|
|
Db1 |
26 |
Y |
P |
|
|
Db1 |
27 |
Y |
P |
|
|
Db1 |
28 |
Y |
P |
|
|
Db1 |
29 |
Y |
P |
|
|
Db1 |
30 |
Y |
P |
|
|
Db1 |
31 |
Y |
P |
|
|
Db1 |
32 |
Y |
P |
|
|
Db1 |
33 |
Y |
P |
|
|
Db1 |
34 |
Y |
P |
|
|
Db1 |
36 |
Y |
P |
|
|
Db1 |
37 |
Y |
P |
|
|
Db1 |
38 |
Y |
P |
|
|
Db1 |
39 |
Y |
P |
|
|
Db1 |
40 |
Y |
P |
|
|
Db1 |
41 |
Y |
P |
|
|
Db1 |
42 |
Y |
P |
|
|
Db1 |
43 |
Y |
P |
|
|
Db1 |
44 |
Y |
P |
|
|
Db1 |
46 |
Y |
P |
|
|
Db1 |
47 |
Y |
P |
|
|
Db1 |
48 |
Y |
P |
|
|
Db2 |
1 |
Y |
P |
|
|
Db2 |
2 |
Y |
P |
|
|
Db2 |
3 |
Y |
P |
|
|
Db2 |
4 |
Y |
P |
|
|
Db2 |
5 |
Y |
P |
|
|
Db2 |
6 |
Y |
P |
|
|
Db2 |
7 |
Y |
P |
|
|
Db2 |
8 |
Y |
P |
|
|
Db2 |
9 |
Y |
P |
|
|
Db2 |
10 |
Y |
P |
|
|
Db2 |
11 |
Y |
P |
|
|
Db2 |
12 |
Y |
P |
|
|
Db2 |
13 |
Y |
P |
|
|
Db2 |
14 |
Y |
P |
|
|
Db2 |
15 |
Y |
P |
|
|
Db2 |
16 |
Y |
P |
|
|
Db2 |
17 |
Y |
P |
|
|
Db2 |
18 |
Y |
P |
|
|
Db2 |
19 |
Y |
P |
|
|
Db2 |
20 |
Y |
P |
|
|
Db2 |
21 |
Y |
P |
|
|
Db2 |
22 |
Y |
P |
|
|
Db2 |
23 |
Y |
P |
|
|
Db2 |
24 |
Y |
P |
|
|
Db2 |
25 |
Y |
P |
|
|
Db2 |
26 |
Y |
P |
|
|
Db2 |
27 |
Y |
P |
|
|
Db2 |
28 |
Y |
P |
|
|
Db2 |
29 |
Y |
P |
|
|
Db2 |
30 |
Y |
P |
|
|
Db2 |
31 |
Y |
P |
|
|
Db2 |
32 |
Y |
P |
|
|
Db2 |
33 |
Y |
P |
|
|
Db2 |
34 |
Y |
P |
|
|
Db2 |
35 |
Y |
P |
|
|
Db2 |
36 |
Y |
P |
|
|
Db2 |
37 |
Y |
P |
|
|
Db2 |
38 |
Y |
P |
|
|
Db2 |
39 |
Y |
P |
|
|
Db2 |
40 |
Y |
P |
|
|
Db2 |
41 |
Y |
P |
|
|
Db2 |
42 |
Y |
P |
|
|
Db2 |
43 |
Y |
P |
|
|
Db2 |
44 |
Y |
P |
|
|
Db2 |
45 |
Y |
P |
|
|
Db2 |
46 |
Y |
P |
|
|
Db2 |
47 |
Y |
P |
|
|
Db2 |
48 |
Y |
P |
|
|
Db2 |
49 |
Y |
P |
|
|
Db2 |
50 |
Y |
P |
|
|
Db2 |
51 |
Y |
P |
|
|
Db2 |
52 |
Y |
P |
|
|
Db2 |
53 |
Y |
P |
|
|
Db2 |
54 |
Y |
P |
|
|
Db2 |
55 |
Y |
P |
|
|
Db2 |
56 |
Y |
P |
|
|
Db2 |
57 |
Y |
P |
|
|
Db2 |
58 |
Y |
P |
|
|
Db2 |
59 |
Y |
P |
|
|
Db2 |
60 |
Y |
P |
|
|
Db2 |
61 |
Y |
P |
|
|
Db2 |
62 |
Y |
P |
|
|
Db2 |
63 |
Y |
P |
|
|
Db2 |
64 |
Y |
P |
|
|
Db2 |
65 |
Y |
P |
|
|
Db2 |
66 |
Y |
P |
|
|
Db2 |
67 |
Y |
P |
|
|
Db2 |
68 |
Y |
P |
|
|
Db2 |
69 |
Y |
P |
|
|
Db2 |
70 |
Y |
P |
|
|
Db2 |
71 |
Y |
P |
|
|
Db2 |
72 |
Y |
P |
|
|
Db2 |
73 |
Y |
P |
|
|
Db2 |
74 |
Y |
P |
|
|
Db2 |
75 |
Y |
P |
|
|
Db2 |
76 |
Y |
P |
|
|
Db2 |
77 |
Y |
P |
|
|
Db2 |
78 |
Y |
P |
|
|
Db2 |
79 |
Y |
P |
|
|
Db2 |
80 |
Y |
P |
|
|
Db2 |
81 |
Y |
P |
|
|
Db2 |
82 |
Y |
P |
|
|
Db2 |
83 |
Y |
P |
|
|
Db2 |
84 |
Y |
P |
|
|
Db2 |
85 |
Y |
P |
|
|
Db2 |
86 |
Y |
P |
|
|
Db2 |
87 |
Y |
P |
|
|
Db2 |
88 |
Y |
P |
|
|
Db2 |
89 |
Y |
P |
|
|
Db2 |
90 |
Y |
P |
|
|
Db2 |
91 |
Y |
P |
|
|
Db2 |
92 |
Y |
P |
|
|
Db2 |
93 |
Y |
P |
|
|
Db2 |
94 |
Y |
P |
|
|
Db2 |
95 |
Y |
P |
|
|
Db3 |
1 |
Y |
P |
|
|
Db3 |
2 |
Y |
P |
|
|
Db3 |
3 |
Y |
P |
|
|
Db3 |
4 |
Y |
P |
|
|
Db3 |
5 |
Y |
P |
|
|
Db3 |
6 |
Y |
P |
|
|
Db3 |
7 |
Y |
P |
|
|
Db3 |
8 |
Y |
P |
|
|
Db3 |
10 |
Y |
P |
|
|
Db3 |
11 |
Y |
P |
|
|
Db3 |
13 |
Y |
P |
|
|
Db3 |
14 |
Y |
P |
|
|
Db3 |
16 |
Y |
P |
|
|
Db3 |
18 |
Y |
P |
|
|
Db3 |
28 |
Y |
P |
|
|
Db4 |
4,5,6 |
Y |
P |
|
|
Db4 |
10 |
Y |
P |
|
|
Db4 |
11 |
Y |
P |
|
|
Db4 |
12 |
Y |
P |
|
|
Db5 |
1 |
Y |
P |
|
|
Db5 |
2 |
Y |
P |
|
|
Db5 |
4 |
Y |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB1 T/Sw |
1 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
2 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
3 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
5 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
6 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
8 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
9 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
11 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
12 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
15 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
19 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
21 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
22 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
26 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
27 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
30 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
32 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
33 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
34 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
35 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
40 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
41 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
43 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
46 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
47 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
48 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
49 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
50 |
R |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
52 |
R |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
54 |
R |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
55 |
R |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
57 |
R |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
58 |
R |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
59 |
R |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
62 |
R |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
64 |
S - 4ft |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
65 |
S - 4ft |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
66 |
S - 4ft |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
68 |
R |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
69 |
R |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
71 |
R |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
72 |
R |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
74 |
R |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
76 |
S |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
77 |
S - 4ft |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB1 T/Sw |
4 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
7 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
10 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
13 |
Y |
Y |
N |
F |
Jack chain support damaged. |
Y |
N |
DB1 T/Sw |
14 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
16 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
17 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
18 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
20 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
23 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
24 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
25 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
28 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
29 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
31 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
36 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
37 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
38 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
39 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
42 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
44 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
45 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
51 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
53 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
56 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
60 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
61 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
63 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
67 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
70 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
73 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
75 |
Y |
Y |
Y |
P |
|
|
|
DB1 T/Sw |
78 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
Hi Bay Ufo's |
Y |
1200x300mm led panels |
Y |
4ft battens |
Y |
Track mounted spot lights |
Y |
Track mounted linear lights |
Y |
Track mounted wall washers |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
Exit light |
#13 |
1 |
Jack chain support damaged |
Y |
N |
N |
Jack chain support damaged. Cable dislodged from outlet. Repaired jack chain. Plugged back into socket |
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 29/03/2024 |
---|
| |
---|
| |