Partner Name | Built Electrical Australia |
---|
State | NSW |
---|
Date of Visit | 18/10/2023 |
---|
Technician's Name | Peter Hay |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 50F0015/0093 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in NSW | auburn |
---|
|
|
---|
Location Name | Auburn |
---|
| |
---|
HTML Block |
|
---|
Test Period | 12 Monthly (90 minutes) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Initial/12 Months) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
DB G07A |
1 |
Y |
P |
|
|
DB G07A |
3 |
Y |
P |
|
|
DB G07A |
5 |
Y |
P |
|
|
DB G07A |
7 |
Y |
P |
|
|
DB G07A |
9 |
Y |
P |
|
|
DB G07A |
11 |
Y |
P |
|
|
DB G07A |
13 |
Y |
P |
|
|
DB G07A |
15 |
Y |
P |
|
|
DB G07A |
17 |
Y |
P |
|
|
DB G07A |
19 |
Y |
P |
|
|
DB G07A |
20 |
Y |
P |
|
|
DB G07A |
21 |
Y |
P |
|
|
DB G07A |
23 |
Y |
P |
|
|
DB G07A |
25 |
Y |
P |
|
|
DB G07A |
26 |
Y |
P |
|
|
DB G07A |
27 |
Y |
P |
|
|
DB G07A |
28 |
Y |
P |
|
|
DB G07A |
29 |
Y |
P |
|
|
DB G07A |
30 |
Y |
P |
|
|
DB G07A |
31 |
Y |
P |
|
|
DB G07A |
32 |
Y |
P |
|
|
DB G07A |
33 |
Y |
P |
|
|
DB G07A |
34 |
Y |
P |
|
|
DB G07A |
35 |
Y |
P |
|
|
DB G07A |
36 |
Y |
P |
|
|
DB G07A |
37 |
Y |
P |
|
|
DB G07A |
38 |
Y |
P |
|
|
DB G07A |
39 |
Y |
P |
|
|
DB G07A |
40 |
Y |
P |
|
|
DB G07A |
42 |
Y |
P |
|
|
DB G07A |
44 |
Y |
P |
|
|
DB G07A |
46 |
Y |
P |
|
|
DB G07A |
48 |
Y |
P |
|
|
DB G07A |
50 |
Y |
P |
|
|
DB G07A |
52 |
Y |
P |
|
|
DB G07A |
54 |
Y |
P |
|
|
DB G07A |
56 |
Y |
P |
|
|
DB G07A |
58 |
Y |
P |
|
|
DB G07A |
60 |
Y |
P |
|
|
DB G08 |
12 |
Y |
P |
|
|
DB G08 |
24 |
Y |
P |
|
|
DB G08 |
37 |
Y |
P |
|
|
DB G08 |
38 |
Y |
P |
|
|
DB G08 |
39 |
Y |
P |
|
|
DB G08 |
40 |
Y |
P |
|
|
DB G08 |
42 |
Y |
P |
|
|
DB G08 |
43 |
Y |
P |
|
|
DB G08 |
44 |
Y |
P |
|
|
DB G08 |
45 |
Y |
P |
|
|
DB G08 |
46 |
Y |
P |
|
|
DB G08 |
47 |
Y |
P |
|
|
DB G07 |
1 |
Y |
P |
|
|
DB G07 |
3 |
Y |
P |
|
|
DB G07 |
11 |
Y |
P |
|
|
DB G07 |
12 |
Y |
P |
|
|
DB G07 |
18 |
Y |
P |
|
|
DB G07 |
19 |
Y |
P |
|
|
DB G07 |
23 |
Y |
P |
|
|
DB G07 |
34 |
Y |
P |
|
|
DB G07 |
35 |
Y |
P |
|
|
DB G07 |
36 |
Y |
P |
|
|
DB G07 |
41 |
Y |
P |
|
|
DB G07 |
42 |
Y |
P |
|
|
DB G07 |
43 |
Y |
P |
|
|
DB G07 |
44 |
Y |
P |
|
|
DB G07 |
48 |
Y |
P |
|
|
DB G07C |
7 |
Y |
P |
|
|
DB G07C |
8 |
Y |
P |
|
|
DB G07C |
8 |
Y |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
|
1 |
S |
Y |
Y |
Y |
P |
|
|
|
|
2 |
S - 4ft |
Y |
Y |
Y |
P |
|
|
|
|
3 |
S - 4ft |
Y |
Y |
Y |
P |
|
|
|
|
4 |
S |
Y |
Y |
Y |
P |
|
|
|
|
5 |
S |
Y |
Y |
Y |
P |
|
|
|
|
6 |
S |
Y |
Y |
Y |
P |
|
|
|
|
7 |
S |
Y |
Y |
Y |
P |
|
|
|
|
8 |
S |
Y |
Y |
Y |
P |
|
|
|
|
9 |
S |
Y |
Y |
Y |
P |
|
|
|
|
10 |
S |
Y |
Y |
Y |
P |
|
|
|
|
11 |
S |
Y |
Y |
Y |
P |
|
|
|
|
12 |
S - 4ft |
Y |
Y |
Y |
P |
|
|
|
|
13 |
S - 4ft |
Y |
Y |
Y |
P |
|
|
|
|
14 |
S - 4ft |
Y |
Y |
Y |
P |
|
|
|
|
15 |
S - 4ft |
Y |
Y |
Y |
P |
|
|
|
|
16 |
S - 4ft |
Y |
Y |
Y |
P |
|
|
|
|
17 |
S - 4ft |
Y |
N |
Y |
F |
Failed 90 min test |
Y |
N |
|
18 |
S - 4ft |
Y |
Y |
Y |
P |
|
|
|
|
19 |
R |
Y |
Y |
Y |
P |
|
|
|
|
20 |
R |
Y |
Y |
Y |
P |
|
|
|
|
21 |
R |
Y |
Y |
Y |
P |
|
|
|
|
22 |
R |
Y |
Y |
Y |
P |
|
|
|
|
23 |
R |
Y |
Y |
Y |
P |
|
|
|
|
24 |
R |
Y |
Y |
Y |
P |
|
|
|
|
25 |
R |
Y |
Y |
Y |
P |
|
|
|
|
26 |
R |
Y |
Y |
Y |
P |
|
|
|
|
27 |
R |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
|
1 |
Y |
Y |
Y |
P |
|
|
|
|
2 |
Y |
Y |
Y |
P |
|
|
|
|
3 |
Y |
N |
Y |
F |
Disconnected |
Y |
N |
|
4 |
Y |
Y |
Y |
P |
|
|
|
|
5 |
Y |
Y |
Y |
P |
|
|
|
|
6 |
Y |
Y |
Y |
P |
|
|
|
|
7 |
Y |
Y |
Y |
P |
|
|
|
|
8 |
Y |
Y |
Y |
P |
|
|
|
|
9 |
Y |
Y |
Y |
P |
|
|
|
|
10 |
Y |
Y |
Y |
P |
|
|
|
|
11 |
Y |
Y |
Y |
P |
|
|
|
|
12 |
Y |
Y |
Y |
P |
|
|
|
|
13 |
Y |
Y |
Y |
P |
|
|
|
|
14 |
Y |
Y |
Y |
P |
|
|
|
|
15 |
Y |
Y |
Y |
P |
|
|
|
|
16 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
UFO High Bays |
Y |
70mm LED Downlight |
Y |
Rectangular Shop Lights |
Y |
Wallbay flat panel light boxes |
Y |
4ft battens |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
High bay |
Washing machines |
1 |
Not illuminated |
Y |
N |
N |
|
Display sign |
Westinghouse washing machines |
1 |
Not illuminated |
N |
N |
N |
Supplied funded stand. Please send through a new work order if you wish for Sturdie to repair. |
Display sign |
Solt washing machines |
1 |
Partially illuminated |
N |
N |
N |
Supplied funded stand. Please send through a new work order if you wish for Sturdie to repair. |
Displays |
TV wall |
5 |
Intermittently tripping |
N |
TBA |
TBA |
Added to fortnightly repairs list. |
Display |
Miele, westinghouse & Haier washing machines |
3 |
Intermittently tripping |
N |
TBA |
TBA |
Added to fortnightly repairs list. |
Display |
LG washing machines |
1 |
Tripping daily |
N |
TBA |
TBA |
Added to fortnightly repairs list. |
Column GPO's |
Trading floor centre aisle |
4 |
Damaged |
Y |
N |
N |
|
Display sign |
Miele dishwashers |
1 |
Partially illuminated |
N |
N |
N |
Supplied funded stand. Please send through a new work order if you wish for Sturdie to repair. |
Display sign |
Miele washing machines |
1 |
Partially illuminated |
N |
N |
N |
Supplied funded stand. Please send through a new work order if you wish for Sturdie to repair. |
Surface mount emergency batten |
#17 |
1 |
Failed 90 min test |
Y |
N |
N |
|
Exit light |
#3 |
1 |
Disconnected from the base |
Y |
N |
N |
|
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 18/04/2024 |
---|
| |
---|
| |