Partner NameBuilt Electrical Australia
StateNSW
Date of Visit18/10/2023
Technician's NamePeter Hay
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number50F0015/0093
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWauburn

Location NameAuburn
HTML Block
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Initial/12 Months)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB G07A 1 Y P
DB G07A 3 Y P
DB G07A 5 Y P
DB G07A 7 Y P
DB G07A 9 Y P
DB G07A 11 Y P
DB G07A 13 Y P
DB G07A 15 Y P
DB G07A 17 Y P
DB G07A 19 Y P
DB G07A 20 Y P
DB G07A 21 Y P
DB G07A 23 Y P
DB G07A 25 Y P
DB G07A 26 Y P
DB G07A 27 Y P
DB G07A 28 Y P
DB G07A 29 Y P
DB G07A 30 Y P
DB G07A 31 Y P
DB G07A 32 Y P
DB G07A 33 Y P
DB G07A 34 Y P
DB G07A 35 Y P
DB G07A 36 Y P
DB G07A 37 Y P
DB G07A 38 Y P
DB G07A 39 Y P
DB G07A 40 Y P
DB G07A 42 Y P
DB G07A 44 Y P
DB G07A 46 Y P
DB G07A 48 Y P
DB G07A 50 Y P
DB G07A 52 Y P
DB G07A 54 Y P
DB G07A 56 Y P
DB G07A 58 Y P
DB G07A 60 Y P
DB G08 12 Y P
DB G08 24 Y P
DB G08 37 Y P
DB G08 38 Y P
DB G08 39 Y P
DB G08 40 Y P
DB G08 42 Y P
DB G08 43 Y P
DB G08 44 Y P
DB G08 45 Y P
DB G08 46 Y P
DB G08 47 Y P
DB G07 1 Y P
DB G07 3 Y P
DB G07 11 Y P
DB G07 12 Y P
DB G07 18 Y P
DB G07 19 Y P
DB G07 23 Y P
DB G07 34 Y P
DB G07 35 Y P
DB G07 36 Y P
DB G07 41 Y P
DB G07 42 Y P
DB G07 43 Y P
DB G07 44 Y P
DB G07 48 Y P
DB G07C 7 Y P
DB G07C 8 Y P
DB G07C 8 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
1 S Y Y Y P
2 S - 4ft Y Y Y P
3 S - 4ft Y Y Y P
4 S Y Y Y P
5 S Y Y Y P
6 S Y Y Y P
7 S Y Y Y P
8 S Y Y Y P
9 S Y Y Y P
10 S Y Y Y P
11 S Y Y Y P
12 S - 4ft Y Y Y P
13 S - 4ft Y Y Y P
14 S - 4ft Y Y Y P
15 S - 4ft Y Y Y P
16 S - 4ft Y Y Y P
17 S - 4ft Y N Y F Failed 90 min test Y N
18 S - 4ft Y Y Y P
19 R Y Y Y P
20 R Y Y Y P
21 R Y Y Y P
22 R Y Y Y P
23 R Y Y Y P
24 R Y Y Y P
25 R Y Y Y P
26 R Y Y Y P
27 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
1 Y Y Y P
2 Y Y Y P
3 Y N Y F Disconnected Y N
4 Y Y Y P
5 Y Y Y P
6 Y Y Y P
7 Y Y Y P
8 Y Y Y P
9 Y Y Y P
10 Y Y Y P
11 Y Y Y P
12 Y Y Y P
13 Y Y Y P
14 Y Y Y P
15 Y Y Y P
16 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
UFO High Bays Y
70mm LED Downlight Y
Rectangular Shop Lights Y
Wallbay flat panel light boxes Y
4ft battens Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
High bay Washing machines 1 Not illuminated Y N N
Display sign Westinghouse washing machines 1 Not illuminated N N N Supplied funded stand. Please send through a new work order if you wish for Sturdie to repair.
Display sign Solt washing machines 1 Partially illuminated N N N Supplied funded stand. Please send through a new work order if you wish for Sturdie to repair.
Displays TV wall 5 Intermittently tripping N TBA TBA Added to fortnightly repairs list.
Display Miele, westinghouse & Haier washing machines 3 Intermittently tripping N TBA TBA Added to fortnightly repairs list.
Display LG washing machines 1 Tripping daily N TBA TBA Added to fortnightly repairs list.
Column GPO's Trading floor centre aisle 4 Damaged Y N N
Display sign Miele dishwashers 1 Partially illuminated N N N Supplied funded stand. Please send through a new work order if you wish for Sturdie to repair.
Display sign Miele washing machines 1 Partially illuminated N N N Supplied funded stand. Please send through a new work order if you wish for Sturdie to repair.
Surface mount emergency batten #17 1 Failed 90 min test Y N N
Exit light #3 1 Disconnected from the base Y N N
Site Status SelectorStore now fully compliant
Next Test Due in 6 months18/04/2024