Partner NameSturdie Trade Services
StateVIC
Date of Visit13/11/2023
Technician's NameNathan McBain
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number50F0017/0113
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICballarat

Location NameBallarat
HTML Block
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Initial/12 Months)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
Sub board 1 09 Y P
Sub board 1 11 Y P
Sub board 1 12 Y P
Sub board 1 15 Y P
Sub board 1 17 Y P
Sub board 1 31 Y P
Sub board 1 32 Y P
Sub board 1 40 Y P
Sub board 1 42 Y P
Sub board 1 44 Y P
Sub board 1 46 Y P
Sub board 1 47 Y P
Sub board 1 48 Y P
Sub board 1 50 Y P
Sub board 1 54 Y P
Sub board 1 57 Y P
Sub board 1A 01 Y P
Sub board 1A 04 Y P
Sub board 1A 05 Y P
Sub board 1A 07 Y P
Sub board 1A 10 Y P
Sub board 1A 13 Y P
Sub board 1A 16 Y P
Sub board 1A 22 Y P
Sub board 1A 27 Y P
Sub board 1A 29 Y P
Sub board 1A 31 Y P
Sub board 1A 32 Y P
Sub board 1A 33 Y P
Sub board 1A 34 Y P
Sub board 1A 35 Y P
Sub board 1A 36 Y P
Sub board 1A 37 Y P
Sub board 1A 38 Y P
Sub board 1A 39 Y P
Sub board 1A 40 Y P
Sub board 1A 41 Y P
Sub board 1A 42 Y P
Sub board 1A 43 Y P
Sub board 1A 44 Y P
Sub board 1A 45 Y P
Sub board 1A 46 Y P
Sub board 1A 47 Y P
Sub board 1A 48 Y P
Sub board 2 20 Y P
Sub board 2 24 Y P
Sub board 2 26 Y P
Sub board 2 28 Y P
Sub board 2 40 Y P
Sub board 2 42 Y P
Sub board 2 44 Y P
Sub board 2 46 Y P
Sub board 2 48 Y P
Sub board 2A 04 Y P
Sub board 2A 06 Y P
Sub board 2A 08 Y P
Sub board 2A 10 Y P
Sub board 2A 12 Y P
Sub board 2A 14 Y P
Sub board 2A 16 Y P
Sub board 2A 18 Y P
Sub board 2A 20 Y P
Sub board 2A 22 Y P
Sub board 2A 24 Y P
Sub board 2A 28 Y P
Sub board 2A 29 Y P
Sub board 2A 30 Y P
Sub board 2A 31 Y P
Sub board 2A 32 Y P
Sub board 2A 33 Y P
Sub board 2A 34 Y P
Sub board 2A 35 Y P
Sub board 2A 36 Y P
Sub board 2A 37 Y P
Sub board 2A 38 Y P
Sub board 2A 39 Y P
Sub board 2A 40 Y P
Sub board 2A 41 Y P
Sub board 2A 42 Y P
Sub board 2A 43 Y P
Sub board 2A 44 Y P
Sub board 2A 45 Y P
Sub board 2A 46 Y P
Sub board 2A 47 Y P
Sub board 2A 48 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
1 R Y Y Y P
2 R Y Y Y P
3 R Y Y Y P
4 S Y Y Y P
5 R Y Y Y P
6 R Y Y Y P
7 S Y Y Y P
8 R Y Y Y P
9 R Y Y Y P
10 R Y Y Y P
11 R Y Y Y P
12 S Y Y Y P
13 R Y Y Y P
14 R Y Y Y P
15 R Y Y Y P
16 S Y Y Y P
17 R Y Y Y P
18 R Y Y Y P
19 R Y Y Y P
20 R Y Y Y P
21 R Y Y Y P
22 S Y Y Y P
23 S Y Y Y P
24 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
1 Y Y Y P
2 Y Y Y P
3 Y Y Y P
4 Y Y Y P
5 Y Y Y P
6 Y Y Y P
7 Y Y Y P
8 Y Y Y P
9 Y Y Y P
10 Y Y Y P
11 Y Y Y P
12 N N Y F Failed 90min discharge test Y N
13 Y Y Y P
14 Y Y Y P
15 Y Y Y P
16 Y Y Y P
17 Y Y Y P
18 Y Y Y P
19 Y N Y F Failed 90min discharge test Y N
20 Y Y Y P
21 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Downlight Male toilet 1 Failed to illuminate Y N N
Test and tag Store 80+ Test and Tag in-date, next test due 26 Feb 2024 N N N Observation
Exit light No. 12 Boh upstairs storeroom 1 Failed 90min discharge test Y N N
Damaged ceiling tiles Fridges (29) / Front entrance (6) / Laundry (9) / Televisions (5) 56 Water damaged N N N Observation
Exit light No. 19 Boh downstairs storeroom 1 Failed 90min discharge test Y N N
Emergency lighting layout Site folder 1 Emergency lighting layout requires updating Y N N Updated emergency lighting layout
Site Status SelectorStore now fully compliant
Next Test Due in 6 months13/05/2024