Partner NameTransit Electrical Pty Ltd
StateWA
Date of Visit19/04/2024
Technician's NameConnor Stevens
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number50F0023/0109
EmailEmail hidden; Javascript is required.
The Good Guys Site in WAmalaga

Location NameMalaga
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB 01 3W Y P
DB 01 3B Y P
DB 01 5R Y P
DB 01 5W Y P
DB 01 5B Y P
DB 01 6B Y P
DB 01 7R Y P
DB 01 8B Y P
DB 01 9R Y P
DB 01 9W Y P
DB 01 10R Y P
DB 01 10W Y P
DB 01 10B Y P
DB 01 11R Y P
DB 01 11W Y P
DB 01 11B Y P
DB 01 12R Y P
DB 01 12W Y P
DB 01 12B Y P
DB 01 13R Y P
DB 01 13W Y P
DB 01 R14 Y P
DB 01 15R Y P
DB 01 15W Y P
DB 01 19R Y P
DB 01 19W Y P
DB 01 20W Y P
DB 01 20B Y P
DB 01 23R Y P
DB 01 23W Y P
DB 01 24W Y P
DB 01 24B Y P
DB 01 26RWB Y P
DB 01 27R Y P
DB 01 30R Y P
DB 01 31R Y P
DB 01 31B Y P
DB 01 32R Y P
DB 01 32W Y P
DB 01 32B Y P
DB 01 33R Y P
DB 01 33W Y P
DB 01 33B Y P
DB 01 34R Y P
DB 01 34W Y P
DB 01 34B Y P
DB 02 3W Y P
DB 02 3B Y P
DB 02 5R Y P
DB 02 5W Y P
DB 02 5B Y P
DB 02 6R Y P
DB 02 6W Y P
DB 02 6B Y P
DB 02 7R Y P
DB 02 7W Y P
DB 02 7B Y P
DB 02 8R Y P
DB 02 8W Y P
DB 02 8B Y P
DB 02 9R Y P
DB 02 9W Y P
DB 02 9B Y P
DB 02 10R Y P
DB 02 13W Y P
DB 02 17R Y P
DB 02 18W Y P
DB 02 - B 1W Y P
DB 02 - B 1R Y P
DB 02 - B 1B Y P
DB 02 - B 2R Y P
DB 02 - B 2W Y P
DB 02 - B 3R Y P
DB 02 - B 11RWB Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 01 2 R Y Y Y P
DB 01 3 S Y Y Y P
DB 01 4 S Y Y Y P
DB 01 5 S Y Y Y P
DB 01 6 S Y Y Y P
DB 01 7 S Y Y Y P
DB 01 8 S Y Y Y P
DB 01 9 S Y Y Y P
DB 01 10 Twin tubed batten Y Y Y P
DB 01 11 S Y Y Y P
DB 01 12 Twin tubed batten Y Y Y P
DB 02 13 R Y Y Y P
DB 02 14 R Y Y Y P
DB 02 15 R Y Y Y P
DB 02 17 R Y Y Y P
DB 02 19 R Y Y Y P
DB 02 20 R Y Y Y P
DB 02 22 S Y Y Y P
DB 02 23 S Y Y Y P
DB 02 24 S Y Y Y P
DB 02 25 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 01 1 Y Y Y P
DB 01 16 Y Y Y P
DB 02 18 Y Y Y P
DB 02 21 Y Y Y P
DB 02 22 Y Y Y P
DB 02 26 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
400w Low Bay Y
LED Low Bay Y
40w Oyster Light Y
LED Batten Lights y
LED Hibays Y
Exit Y
Emergency Surface Mount Y
Emergency Recessed Y
LED Track Lighting Y
LED Spot Lights Y
LED Bunker Light Y
Par 38 Twin Spots Y
LED Downlight Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
SAL Bronx Wall Lights Front Entry 3 2x Strobing, 1x Flickering N Y TBA All three are next to each other. Quote #998 sent to compliance for consideration
Kitchen Aid Small Appliances 1 Strobing Y N N Faulty power supply
Awning Flood Lights Front Entry 6 Not Illuminated N Y TBA Out of the 11 Flood Lights 6 have failed and aren't illuminated. Recommend replacing all 11 as remaining 5 are old and close to end of life. Quote #998 sent to compliance for consideration
SAL Bronx Wall Rear Loading Dock 4 Not Illuminated N Y TBA Quote #998 sent to compliance for consideration
Batten Screw Globe Front Awning 1 Not Illuminated N Y TBA Recommend replacing all 30 as the remaining are yellowing. Quote #998 sent to compliance for consideration
Site Status SelectorStore now fully compliant
Next Test Due in 6 months17/10/2024