| Partner Name | Transit Electrical Pty Ltd |
|---|
| State | WA |
|---|
| Date of Visit | 22/04/2024 |
|---|
| Technician's Name | Connor Stevens |
|---|
| Which Company are you working for? | Sturdie Trade Services |
|---|
| Sturdie Job Number | 50F0023/0114 |
|---|
| Email | Email hidden; Javascript is required. |
|---|
| The Good Guys Site in WA | cockburn |
|---|
|
|
|---|
| Location Name | Cockburn |
|---|
| |
|---|
| HTML Block |
|
|---|
| Test Period | 6 Monthly (90 minutes) |
|---|
| Push Button Test | - Carry out push button test for correct operation
|
|---|
| Carry out push button test for correct operation | |
|---|
| HTML Block |
|
|---|
| Carry out test with RCD Tester | Carry out push button test and record the results below. |
|---|
| THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
|---|
| RCD Details (6 Month) | | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
| DB 01 Chassis 1 |
1R |
Y |
P |
|
|
| DB 01 |
1W |
Y |
P |
|
|
|
1B |
Y |
P |
|
|
|
3R |
Y |
P |
|
|
|
3W |
Y |
P |
|
|
|
3B |
Y |
P |
|
|
|
5R |
Y |
P |
|
|
|
5W |
Y |
P |
|
|
|
5B |
Y |
P |
|
|
|
7R |
Y |
P |
|
|
|
7W |
Y |
P |
|
|
|
7B |
Y |
P |
|
|
|
9R |
Y |
P |
|
|
|
9W |
Y |
P |
|
|
|
9B |
Y |
P |
|
|
|
11R |
Y |
P |
|
|
|
11W |
Y |
P |
|
|
|
11B |
Y |
P |
|
|
|
13R |
Y |
P |
|
|
|
13W |
Y |
P |
|
|
|
13B |
Y |
P |
|
|
|
15R |
Y |
P |
|
|
|
15B |
Y |
P |
|
|
|
2R |
Y |
P |
|
|
|
2W |
Y |
P |
|
|
|
2B |
Y |
P |
|
|
|
4R |
Y |
P |
|
|
|
4W |
Y |
P |
|
|
|
4B |
Y |
P |
|
|
|
6R |
Y |
P |
|
|
|
6W |
Y |
P |
|
|
|
6B |
Y |
P |
|
|
|
8R |
Y |
P |
|
|
|
8W |
Y |
P |
|
|
|
8B |
Y |
P |
|
|
|
10B |
Y |
P |
|
|
|
12R |
Y |
P |
|
|
|
12W |
Y |
P |
|
|
|
12B |
Y |
P |
|
|
|
14R |
Y |
P |
|
|
|
14W |
Y |
P |
|
|
|
14B |
Y |
P |
|
|
| DB 01 Chassis 2 |
17R |
Y |
P |
|
|
|
17W |
Y |
P |
|
|
|
17B |
Y |
P |
|
|
|
RWB19, RW21 |
Y |
P |
|
|
|
21B |
Y |
P |
|
|
|
31R |
Y |
P |
|
|
|
31W |
Y |
P |
|
|
|
31B |
Y |
P |
|
|
|
18R |
Y |
P |
|
|
|
18W |
Y |
P |
|
|
|
18B |
Y |
P |
|
|
|
20R |
Y |
P |
|
|
|
20W |
Y |
P |
|
|
|
20B |
Y |
P |
|
|
|
22R |
Y |
P |
|
|
|
22W |
Y |
P |
|
|
|
22B |
Y |
P |
|
|
| DB 02 |
1R |
Y |
P |
|
|
|
1W |
Y |
P |
|
|
|
1B |
Y |
P |
|
|
|
3R |
Y |
P |
|
|
|
3W |
Y |
P |
|
|
|
3B |
Y |
P |
|
|
|
5R |
Y |
P |
|
|
|
5W |
Y |
P |
|
|
|
5B |
Y |
P |
|
|
|
7W |
Y |
P |
|
|
|
7B |
Y |
P |
|
|
|
RWB9, RW11 |
Y |
P |
|
|
|
RWB13, RW15 |
Y |
P |
|
|
|
2R |
Y |
P |
|
|
|
2W |
Y |
P |
|
|
|
2B |
Y |
P |
|
|
|
4R |
Y |
P |
|
|
|
4W |
Y |
P |
|
|
|
4B |
Y |
P |
|
|
|
6R |
Y |
P |
|
|
|
6W |
Y |
P |
|
|
|
6B |
Y |
P |
|
|
|
8R |
Y |
P |
|
|
|
8W |
Y |
P |
|
|
|
10R |
Y |
P |
|
|
|
WB10, RWB12 |
Y |
P |
|
|
|
W14 |
Y |
P |
|
|
|
B14 |
Y |
P |
|
|
|
R16 |
Y |
P |
|
|
|
W16 |
Y |
P |
|
|
|
B16 |
Y |
P |
|
|
| DB 04 |
1R |
Y |
P |
|
|
|
1W |
Y |
P |
|
|
|
1B |
Y |
P |
|
|
|
3R |
Y |
P |
|
|
|
3W |
Y |
P |
|
|
|
3B |
Y |
P |
|
|
|
5R |
Y |
P |
|
|
|
5W |
Y |
P |
|
|
|
5B |
Y |
P |
|
|
|
2R |
Y |
P |
|
|
|
2W |
Y |
P |
|
|
|
2B |
Y |
P |
|
|
|
4R |
Y |
P |
|
|
|
4W |
Y |
P |
|
|
|
4B |
Y |
P |
|
|
|
6R |
Y |
P |
|
|
|
6W |
Y |
P |
|
|
|
6B |
Y |
P |
|
|
| DB 03 |
1 |
Y |
P |
|
|
|
3 |
Y |
P |
|
|
|
4 |
Y |
P |
|
|
|
6 |
Y |
P |
|
|
|
7 |
Y |
P |
|
|
|
8 |
Y |
P |
|
|
|
8B |
N |
F |
Failed push button test |
Y |
|
9 |
Y |
P |
|
|
|
11 |
Y |
P |
|
|
|
13 |
Y |
P |
|
|
|
15 |
Y |
P |
|
|
|
17 |
Y |
P |
|
|
|
19 |
Y |
P |
|
|
|
21 |
Y |
P |
|
|
|
22 |
Y |
P |
|
|
|
23 |
Y |
P |
|
|
|
24 |
Y |
P |
|
|
|
25 |
Y |
P |
|
|
|
26 |
Y |
P |
|
|
|
27 |
Y |
P |
|
|
|
28 |
Y |
P |
|
|
|
29 |
Y |
P |
|
|
|
30 |
Y |
P |
|
|
|
31 |
Y |
P |
|
|
|
32 |
Y |
P |
|
|
|
34 |
Y |
P |
|
|
|
36 |
Y |
P |
|
|
|
|---|
| SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
|---|
| Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
|---|
| Timers | - Check timers for correct operation and timing
|
|---|
| Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
|---|
| HTML Block |
|
|---|
| EMERGENCY LIGHTS | | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| DB 01 |
5 |
S |
Y |
Y |
Y |
P |
|
|
|
|
6 |
S |
Y |
Y |
Y |
P |
|
|
|
|
7 |
S |
Y |
Y |
Y |
P |
|
|
|
|
11 |
S |
Y |
Y |
Y |
P |
|
|
|
|
12 |
S |
Y |
Y |
Y |
P |
|
|
|
|
13 |
R |
Y |
Y |
Y |
P |
|
|
|
|
15 |
R |
Y |
Y |
Y |
P |
|
|
|
|
16 |
R |
Y |
Y |
Y |
P |
|
|
|
|
20 |
R |
Y |
Y |
Y |
P |
|
|
|
|
21 |
R |
Y |
Y |
Y |
P |
|
|
|
|
22 |
R |
Y |
Y |
Y |
P |
|
|
|
|
23 |
R |
Y |
Y |
Y |
P |
|
|
|
|
24 |
R |
Y |
Y |
Y |
P |
|
|
|
|
25 |
R |
Y |
Y |
Y |
P |
|
|
|
|
26 |
S |
Y |
Y |
Y |
P |
|
|
|
|
28 |
R |
Y |
Y |
Y |
P |
|
|
|
|
31 |
S |
Y |
Y |
Y |
P |
|
|
|
|
33 |
S |
Y |
Y |
Y |
P |
|
|
|
|
34 |
S |
Y |
Y |
Y |
P |
|
|
|
|
35 |
S |
Y |
Y |
Y |
P |
|
|
|
|
37 |
S |
Y |
Y |
Y |
P |
|
|
|
|
39 |
R |
Y |
Y |
Y |
P |
|
|
|
|
40 |
S |
Y |
Y |
Y |
P |
|
|
|
|
43 |
S |
Y |
Y |
Y |
P |
|
|
|
|
44 |
S |
Y |
Y |
Y |
P |
|
|
|
|
50 |
S |
Y |
Y |
Y |
P |
|
|
|
|
52 |
S |
Y |
Y |
Y |
P |
|
|
|
|
53 |
S |
Y |
Y |
Y |
P |
|
|
|
|
54 |
S |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| HTML Block |
|
|---|
| EXIT LIGHTS | | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| DB 01 |
1 |
Y |
Y |
Y |
P |
|
|
|
|
2 |
Y |
Y |
Y |
P |
|
|
|
|
3 |
Y |
Y |
Y |
P |
|
|
|
|
4 |
Y |
Y |
Y |
P |
|
|
|
|
8 |
Y |
Y |
Y |
P |
|
|
|
|
9 |
Y |
Y |
Y |
P |
|
|
|
|
10 |
Y |
Y |
Y |
P |
|
|
|
|
14 |
Y |
Y |
Y |
P |
|
|
|
| DB 03 |
17 |
Y |
Y |
Y |
P |
|
|
|
|
18 |
Y |
Y |
Y |
P |
|
|
|
|
19 |
Y |
Y |
Y |
P |
|
|
|
| DB 01 |
27 |
Y |
Y |
Y |
P |
|
|
|
|
28 |
Y |
Y |
Y |
P |
|
|
|
|
29 |
Y |
Y |
Y |
P |
|
|
|
|
30 |
Y |
Y |
Y |
P |
|
|
|
|
32 |
Y |
Y |
Y |
P |
|
|
|
|
36 |
Y |
Y |
Y |
P |
|
|
|
|
38 |
Y |
Y |
Y |
P |
|
|
|
|
41 |
Y |
Y |
Y |
P |
|
|
|
|
42 |
Y |
Y |
Y |
P |
|
|
|
|
45 |
Y |
Y |
Y |
P |
|
|
|
|
46 |
Y |
Y |
Y |
P |
|
|
|
|
47 |
Y |
Y |
Y |
P |
|
|
|
|
48 |
Y |
Y |
Y |
P |
|
|
|
|
49 |
Y |
Y |
Y |
P |
|
|
|
|
51 |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
|---|
| General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
|---|
| HTML Block |
|
|---|
| General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
|---|
| HTML Block |
|
|---|
| Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
|---|
| Lighting Report | | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
| 40w B27 batten globe |
Y |
| 250w MH flood light |
Y |
| 80w MH bunker light |
Y |
| 250w lowbay recessed |
Y |
| 80w MH shop light |
Y |
| 400w hibay |
Y |
| Emergency batten 2 by 36w |
Y |
| LED down light 10w |
Y |
| Bare batten tv wall |
Y |
| Exits |
Y |
| 400w lowbay |
Y |
| 1 by 36w defused batten |
Y |
| 100w LED flood light |
Y |
| Twin par 38 flood lightb |
Y |
| Oyster light 18w 4 pin plc lamp |
Y |
| 1 by 18w bare batten |
Y |
| Emergency spitfire |
Y |
|
|---|
| Are there any Warranty items needing to be repaired? | No |
|---|
| LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
| RCBO #8B |
DB 03 |
1 |
Failed push button test |
Y |
N |
N |
|
|
|---|
| Site Status Selector | Store now fully compliant |
|---|
| Next Test Due in 6 months | 21/10/2024 |
|---|
| |
|---|
| |