Partner NameBuilt Services
StateSA
Date of Visit19/07/2024
Technician's NameGlenn Rowe
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number50F0021/0054
EmailEmail hidden; Javascript is required.
The Good Guys Site in SAgepps_cross

Location NameGepps Cross
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB-1 1 Y 040 029 P
2 Y 030 031 P
3 Y 038 034 P
4 Y 040 040 P
5 Y 027 030 P
6 Y 045 045 P
7 Y 059 060 P
8 Y 099 103 P
9 Y 049 060 P
10 Y 061 144 P
11 Y 044 044 P
12 Y 045 045 P
13 Y 029 020 P
14 Y 050 053 P
15 Y 074 042 P
16 Y 044 044 P
17 Y 074 049 P
18 Y 045 045 P
19 Y 039 039 P
20 Y 049 048 P
21 Y 039 039 P
22 Y 042 042 P
23 Y 040 039 P
24 Y 044 041 P
25 Y 039 039 P
26 Y 101 109 P
28 Y 040 039 P
29 Y 030 030 P
31 Y 037 036 P
32 Y 044 044 P
33 Y 145 158 P
34 Y 029 032 P
35 Y 057 057 P
37 Y 026 022 P
38 Y 036 036 P
39 Y 031 042 P
40 Y 038 046 P
41 Y 047 121 P
42 Y 038 038 P
45 Y 039 039 P
46 Y 032 022 P
47 Y 038 038 P
48 Y 031 023 P
49 Y 022 023 P
50 Y 023 020 P
51 Y 028 037 P
52 Y 031 023 P
53 Y 028 028 P
54 Y 045 026 P
56 Y 025 020 P
58 Y 030 041 P
60 Y 031 053 P
MBD,T46 R2 Y 044 043 P
W2 Y 043 043 P
B2 Y 044 043 P
R3 Y 045 046 P
R4 Y 042 042 P
W4 Y 041 041 P
B4 Y 042 042 P
W5 Y 040 039 P
B5 Y 134 155 P
R6 Y 043 043 P
W6 Y 040 040 P
B6 Y 043 043 P
R7 Y 042 042 P
W7 Y 032 032 P
B7 Y 039 039 P
R8 Y 182 181 P
W8 Y 188 180 P
B8 Y 179 177 P
R10 Y 040 040 P
W10 Y 040 040 P
B10 Y 043 043 P
R12 Y 040 040 P
W12 Y 043 042 P
B12 Y 057 058 P
R13 Y 039 039 P
W13 Y 040 040 P
B13 Y 041 056 P
R14 Y 043 043 P
W14 Y 033 032 P
B14 Y 043 036 P
R15 Y 040 045 P
W15 Y 049 051 P
B15 Y 041 044 P
R16 Y 039 030 P
W16 Y 042 042 P
B16 Y 047 047 P
R17 Y 048 048 P
W17 Y 053 055 P
B17 Y 031 039 P
R18 Y 044 044 P
W18 Y 049 074 P
B18 Y 040 053 P
R20 Y 043 059 P
W20 Y 052 053 P
B20 Y 040 041 P
R22 Y 048 054 P
W22 Y 194 194 P
B22 Y 048 048 P
R24 Y 078 103 P
W24 Y 075 067 P
B24 Y 056 056 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MDB T.46 6 R Y Y Y P
7 R Y Y Y P
11 "s 2 x 36w diffused battens Y Y Y P
12 "s 2 x 36w diffused battens Y Y Y P
13 "s 2 x 36w diffused battens Y Y Y P
14 "s 2 x 36w diffused battens Y Y Y P
15 "s 2 x 36w diffused battens Y Y Y P
16 "s 2 x 36w diffused battens Y Y Y P
17 "s 2 x 36w diffused battens Y Y Y P
18 "s 2 x 36w diffused battens Y Y Y P
19 "s 2 x 36w diffused battens Y Y Y P
20 "s 2 x 36w diffused battens Y Y Y P
21 "s 2 x 36w diffused battens Y Y Y P
22 "s 2 x 36w diffused battens Y Y Y P
24 "s 2 x 36w diffused battens Y Y Y P
25 "s 2 x 36w diffused battens Y Y Y P
27 "s 2 x 36w diffused battens Y Y Y P
28 "s 2 x 36w diffused battens Y Y Y P
29 "s 2 x 36w diffused battens Y Y Y P
31 R Y Y Y P
32 R Y Y Y P
33 "s 2 x 36w diffused battens Y Y Y P
34 "s 2 x 36w diffused battens Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB T.46 1 Y Y Y P
2 Y Y Y P
3 Y Y Y P
4 Y Y Y P
5 Y Y Y P
8 Y Y Y P
9 Y Y Y P
23 Y Y Y P
26 Y Y Y P
30 Y Y Y P
33 Y Y Y P
34 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Hibay Lights Y
2 x 36W Diffused Y
9W Downlights Y
Are there any Warranty items needing to be repaired?No
Site Status SelectorStore now fully compliant
Next Test Due in 6 months19/01/2025