Carry out push button test and record the results below.
RCD Details (Biennial)
Distribution Board No.
Circuit No.
Push Button (YorN)
0 Degrees
180 Degrees
Pass / Fail (PorF)
Fault?
Repaired on Site (YorN)
DB01
R1
Y
P
W1
Y
P
B1
Y
P
R2
Y
P
W2
Y
P
B2
Y
P
R3
Y
P
W3
Y
P
B3
Y
P
R4
Y
P
W4
Y
P
B4
Y
P
R6
Y
P
W6
Y
P
B6
Y
P
R7
Y
P
W7
Y
P
B7
Y
P
R8
Y
P
W8
Y
P
B8
Y
P
R9
Y
P
W9
Y
P
B9
Y
P
R10
Y
P
W10
Y
P
B10
Y
P
R11
Y
P
W11
Y
P
B11
Y
P
R12
Y
P
W12
Y
P
B12
Y
P
R13
Y
P
W13
Y
P
B13
Y
P
R14
Y
P
W14
Y
P
B14
Y
P
R15
Y
P
W15
Y
P
B15
Y
P
R16
Y
P
W16
Y
P
B16
N
F
Failed push button Test
Y
R17
Y
P
W17
Y
P
B17
Y
P
R18
Y
P
W18
Y
P
B18
Y
P
R19
Y
P
W19
Y
P
B19
Y
P
R20
Y
P
W20
Y
P
B20
Y
P
R21
Y
P
W21
Y
P
B21
Y
P
R22
Y
P
W22
Y
P
W23
Y
P
B23
Y
P
W26
Y
P
B26
Y
P
R28
Y
P
W28
Y
P
DB02
W1
Y
P
B1
Y
P
W2
Y
P
B2
Y
P
R3
Y
P
W3
Y
P
B3
Y
P
R4
Y
P
W4
Y
P
B4
Y
P
R5
Y
P
W5
Y
P
B5
Y
P
R6
Y
P
W6
Y
P
B6
Y
P
R7
Y
P
W7
Y
P
B7
Y
P
R8
Y
P
W8
Y
P
B8
Y
P
R9
Y
P
R10
Y
P
W10
Y
P
B10
Y
P
R12
Y
P
W12
Y
P
THERMOGRAPHIC TEST RESULTS
THERMOGRAPHIC TEST RESULTS
SF43 Exit/Emergency
SF43 EXIT/EMERGENCY LIGHTING
Exit/Emergency Light Checklist
Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
Check timers for correct operation and timing
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No.
ID No.
Surface mounted or recessed? (SorR)
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
DB01
2
S
Y
Y
Y
P
DB01
3
S
Y
Y
Y
P
DB01
4
S
Y
Y
Y
P
DB01
5
S
Y
Y
Y
P
DB01
6
S
Y
Y
Y
P
DB01
7
S
Y
Y
Y
P
DB01
8
S
Y
Y
Y
P
DB01
9
S
Y
Y
Y
P
DB01
12
R
Y
Y
Y
P
DB01
13
R
Y
Y
Y
P
DB01
14
R
Y
Y
Y
P
DB01
15
R
Y
Y
Y
P
DB01
16
R
Y
Y
Y
P
DB01
17
R
Y
Y
Y
P
DB01
18
R
Y
Y
Y
P
DB01
19
R
Y
Y
Y
P
DB01
20
R
Y
Y
Y
P
DB01
22
R
Y
Y
Y
P
DB01
23
R
Y
Y
Y
P
DB01
27
S
Y
Y
Y
P
DB01
28
S
Y
Y
Y
P
HTML Block
EXIT LIGHTS
Distribution Board No.
ID No.
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
SUB BOARD 1
1
Y
Y
Y
P
DB01
10
N
N
N
F
Failed 90 Minute Test
Y
N
DB01
11
N
N
N
F
Failed 90 Minute Test
Y
N
DB01
21
Y
Y
Y
P
DB01
24
Y
Y
Y
P
DB01
25
N
N
N
F
Failed 90 Minute Test
Y
N
DB01
29
Y
Y
Y
P
DB01
30
Y
Y
Y
P
DB01
31
Y
Y
Y
P
DB01
32
Y
Y
Y
P
DB01
33
Y
Y
Y
P
DB01
34
Y
Y
Y
P
DB01
35
Y
Y
Y
P
DB01
36
Y
Y
Y
P
DB01
37
Y
Y
Y
P
DB01
38
Y
Y
Y
P
DB01
39
Y
Y
Y
P
DB01
40
Y
Y
Y
P
SF44 General Lighting & Works
SF44 GENERAL LIGHTING & WORKS
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
HTML Block
General Operation/Additional items
Check with Store Manager to ensure there are no other issues
Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au
Yes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten)
Existing (YorN)
Jumbo Exit
Y
LED Hibays
Y
Davis LED Batten
Y
400w Defused Low Bay
Y
Exit Lights
Y
Surface Mount Emergency Lights
Y
Recessed Emergency Lights
Y
LED Rectangular Shoplight
Y
LED Linkables
Y
LED Downlights
Y
Are there any Warranty items needing to be repaired?
No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
DB01 B16
BOH
1
Failed Push Button Test
Y
N
N
Job has been completed under Parent Job ID: 2268705. RCBO has been replaced
DB01 W19
Haier Oven Display
1
Causing circuit to trip
N
N
N
Have narrowed fault down to Ovens within Display. Have left plug that powers them unplugged above Display with Out of Service Tag attached. 2 x ovens are faulty and require to be replaced
DB02 R4
Oven Displays
1
Intermitten Tripping
N
N
N
Lewis from Compliance advised he'll pass this information onto the Merch Displays Team to address
Kitchen Aid Drivers
Kitchen Aid Displays
2
1 x Display Flickering, 1 x not illuminated
Y
N
N
Job has been completed under Job Parent ID: 2268705. 2 x drivers have been replaced
Exit #10
Small Appliances exit door
1
Failed 90 Minute Test
Y
N
N
Exit #11
Small Appliances exit door
1
Failed 90 Minute Test
Y
N
N
Jumbo Exit #25
BOH
1
Failed 90 Minute Test
Y
N
N
Hibay
BOH
1
Not Illuminated
Y
N
N
Scissor Lift was required
Hibays
Shop Floor laundry section and Small Appliances
2
Not Illuminated
Y
N
N
Scissor Lift was required
Lights
Cash Office
2
Keep flickering on and off
Y
N
N
Site Status Selector
Store now fully compliant
Next Test Due in 6 months
05/02/2025