Partner NameTransit Electrical Pty Ltd
StateWA
Date of Visit05/08/2024
Technician's NameConnor Stevens
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number50F0023/0136
EmailEmail hidden; Javascript is required.
The Good Guys Site in WAjoondalup

Location NameJoondalup
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB01 R1 Y P
W1 Y P
B1 Y P
R2 Y P
W2 Y P
B2 Y P
R3 Y P
W3 Y P
B3 Y P
R4 Y P
W4 Y P
B4 Y P
R6 Y P
W6 Y P
B6 Y P
R7 Y P
W7 Y P
B7 Y P
R8 Y P
W8 Y P
B8 Y P
R9 Y P
W9 Y P
B9 Y P
R10 Y P
W10 Y P
B10 Y P
R11 Y P
W11 Y P
B11 Y P
R12 Y P
W12 Y P
B12 Y P
R13 Y P
W13 Y P
B13 Y P
R14 Y P
W14 Y P
B14 Y P
R15 Y P
W15 Y P
B15 Y P
R16 Y P
W16 Y P
B16 N F Failed push button Test Y
R17 Y P
W17 Y P
B17 Y P
R18 Y P
W18 Y P
B18 Y P
R19 Y P
W19 Y P
B19 Y P
R20 Y P
W20 Y P
B20 Y P
R21 Y P
W21 Y P
B21 Y P
R22 Y P
W22 Y P
W23 Y P
B23 Y P
W26 Y P
B26 Y P
R28 Y P
W28 Y P
DB02 W1 Y P
B1 Y P
W2 Y P
B2 Y P
R3 Y P
W3 Y P
B3 Y P
R4 Y P
W4 Y P
B4 Y P
R5 Y P
W5 Y P
B5 Y P
R6 Y P
W6 Y P
B6 Y P
R7 Y P
W7 Y P
B7 Y P
R8 Y P
W8 Y P
B8 Y P
R9 Y P
R10 Y P
W10 Y P
B10 Y P
R12 Y P
W12 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB01 2 S Y Y Y P
DB01 3 S Y Y Y P
DB01 4 S Y Y Y P
DB01 5 S Y Y Y P
DB01 6 S Y Y Y P
DB01 7 S Y Y Y P
DB01 8 S Y Y Y P
DB01 9 S Y Y Y P
DB01 12 R Y Y Y P
DB01 13 R Y Y Y P
DB01 14 R Y Y Y P
DB01 15 R Y Y Y P
DB01 16 R Y Y Y P
DB01 17 R Y Y Y P
DB01 18 R Y Y Y P
DB01 19 R Y Y Y P
DB01 20 R Y Y Y P
DB01 22 R Y Y Y P
DB01 23 R Y Y Y P
DB01 27 S Y Y Y P
DB01 28 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
SUB BOARD 1 1 Y Y Y P
DB01 10 N N N F Failed 90 Minute Test Y N
DB01 11 N N N F Failed 90 Minute Test Y N
DB01 21 Y Y Y P
DB01 24 Y Y Y P
DB01 25 N N N F Failed 90 Minute Test Y N
DB01 29 Y Y Y P
DB01 30 Y Y Y P
DB01 31 Y Y Y P
DB01 32 Y Y Y P
DB01 33 Y Y Y P
DB01 34 Y Y Y P
DB01 35 Y Y Y P
DB01 36 Y Y Y P
DB01 37 Y Y Y P
DB01 38 Y Y Y P
DB01 39 Y Y Y P
DB01 40 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Jumbo Exit Y
LED Hibays Y
Davis LED Batten Y
400w Defused Low Bay Y
Exit Lights Y
Surface Mount Emergency Lights Y
Recessed Emergency Lights Y
LED Rectangular Shoplight Y
LED Linkables Y
LED Downlights Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
DB01 B16 BOH 1 Failed Push Button Test Y N N Job has been completed under Parent Job ID: 2268705. RCBO has been replaced
DB01 W19 Haier Oven Display 1 Causing circuit to trip N N N Have narrowed fault down to Ovens within Display. Have left plug that powers them unplugged above Display with Out of Service Tag attached. 2 x ovens are faulty and require to be replaced
DB02 R4 Oven Displays 1 Intermitten Tripping N N N Lewis from Compliance advised he'll pass this information onto the Merch Displays Team to address
Kitchen Aid Drivers Kitchen Aid Displays 2 1 x Display Flickering, 1 x not illuminated Y N N Job has been completed under Job Parent ID: 2268705. 2 x drivers have been replaced
Exit #10 Small Appliances exit door 1 Failed 90 Minute Test Y N N
Exit #11 Small Appliances exit door 1 Failed 90 Minute Test Y N N
Jumbo Exit #25 BOH 1 Failed 90 Minute Test Y N N
Hibay BOH 1 Not Illuminated Y N N Scissor Lift was required
Hibays Shop Floor laundry section and Small Appliances 2 Not Illuminated Y N N Scissor Lift was required
Lights Cash Office 2 Keep flickering on and off Y N N
Site Status SelectorStore now fully compliant
Next Test Due in 6 months05/02/2025