| Partner Name | Commlec Electrical PTY LTD |
|---|
| State | NSW |
|---|
| Date of Visit | 20/09/2024 |
|---|
| Technician's Name | Mitch Sattler |
|---|
| Which Company are you working for? | Sturdie Trade Services |
|---|
| Sturdie Job Number | 50F0015/0420 |
|---|
| Email | Email hidden; Javascript is required. |
|---|
| The Good Guys Site in NSW | kotara |
|---|
|
|
|---|
| Location Name | Kotara |
|---|
| |
|---|
| HTML Block |
|
|---|
| Test Period | Biennial Test (once every two years) |
|---|
| Push Button Test | - Carry out push button test for correct operation
|
|---|
| Carry out push button test for correct operation | |
|---|
| HTML Block |
|
|---|
| Carry out test with RCD Tester | Carry out push button test and record the results below. |
|---|
| RCD Details (Biennial) | | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
| DBT12B |
2 |
Y |
0.029 |
0.019 |
P |
|
|
|
4 |
Y |
0.029 |
0.018 |
P |
|
|
|
5 |
Y |
0.028 |
0.018 |
P |
|
|
|
6 |
Y |
0.028 |
0.019 |
P |
|
|
|
7 |
Y |
0.028 |
0.018 |
P |
|
|
|
8 |
Y |
0.028 |
0.018 |
P |
|
|
|
9 |
Y |
0.029 |
0.019 |
P |
|
|
|
10 |
Y |
0.028 |
0.019 |
P |
|
|
|
11 |
Y |
0.029 |
0.019 |
P |
|
|
|
12 |
Y |
0.028 |
0.019 |
P |
|
|
|
13 |
Y |
0.029 |
0.018 |
P |
|
|
|
14 |
Y |
0.028 |
0.019 |
P |
|
|
|
15 |
Y |
0.028 |
0.018 |
P |
|
|
|
16 |
Y |
0.029 |
0.018 |
P |
|
|
|
17 |
Y |
0.028 |
0.018 |
P |
|
|
|
18 |
Y |
0.037 |
0.018 |
P |
|
|
|
19 |
Y |
0.028 |
0.038 |
P |
|
|
|
20 |
Y |
0.029 |
0.027 |
P |
|
|
|
21 |
Y |
0.023 |
0.034 |
P |
|
|
|
22 |
Y |
0.029 |
0.028 |
P |
|
|
|
23 |
Y |
0.029 |
0.019 |
P |
|
|
|
24 |
Y |
0.029 |
0.018 |
P |
|
|
|
25 |
Y |
0.028 |
0.018 |
P |
|
|
|
26 |
Y |
0.028 |
0.018 |
P |
|
|
|
27 |
Y |
0.028 |
0.018 |
P |
|
|
|
28 |
Y |
0.029 |
0.018 |
P |
|
|
|
29 |
Y |
0.029 |
0.019 |
P |
|
|
|
30 |
Y |
0.029 |
0.019 |
P |
|
|
|
31 |
Y |
0.025 |
0.035 |
P |
|
|
|
32 |
Y |
0.044 |
0.018 |
P |
|
|
|
33 |
Y |
0.028 |
0.038 |
P |
|
|
|
34 |
Y |
0.028 |
0.038 |
P |
|
|
|
35 |
Y |
0.024 |
0.034 |
P |
|
|
|
36 |
Y |
0.048 |
0.038 |
P |
|
|
|
40 |
Y |
0.025 |
0.020 |
P |
|
|
|
42 |
Y |
0.025 |
0.034 |
P |
|
|
|
44 |
Y |
0.044 |
0.038 |
P |
|
|
|
46 |
Y |
0.044 |
0.037 |
P |
|
|
| DBT12C |
2 |
Y |
0.027 |
0.033 |
P |
|
|
|
4 |
Y |
0.029 |
0.034 |
P |
|
|
|
5 |
Y |
0.024 |
0.034 |
P |
|
|
|
6 |
Y |
0.024 |
0.034 |
P |
|
|
|
7 |
Y |
0.044 |
0.057 |
P |
|
|
|
8 |
Y |
0.048 |
0.054 |
P |
|
|
|
9 |
Y |
0.043 |
0.057 |
P |
|
|
|
10 |
Y |
0.024 |
0.033 |
P |
|
|
|
11 |
Y |
0.024 |
0.034 |
P |
|
|
|
12 |
Y |
0.044 |
0.033 |
P |
|
|
|
13 |
Y |
0.020 |
0.034 |
P |
|
|
|
14 |
Y |
0.028 |
0.033 |
P |
|
|
|
15 |
Y |
0.024 |
0.034 |
P |
|
|
|
16 |
Y |
0.044 |
0.033 |
P |
|
|
|
17 |
Y |
0.044 |
0.055 |
P |
|
|
|
18 |
Y |
0.024 |
0.039 |
P |
|
|
|
19 |
Y |
0.020 |
0.038 |
P |
|
|
|
20 |
Y |
0.024 |
0.033 |
P |
|
|
|
21 |
Y |
0.047 |
0.038 |
P |
|
|
|
22 |
Y |
0.024 |
0.034 |
P |
|
|
|
23 |
Y |
0.044 |
0.054 |
P |
|
|
|
24 |
Y |
0.047 |
0.056 |
P |
|
|
|
25 |
Y |
0.048 |
0.053 |
P |
|
|
|
26 |
Y |
0.044 |
0.034 |
P |
|
|
|
27 |
Y |
0.046 |
0.035 |
P |
|
|
|
28 |
Y |
0.044 |
0.054 |
P |
|
|
|
29 |
Y |
0.044 |
0.034 |
P |
|
|
|
30 |
Y |
0.023 |
0.033 |
P |
|
|
|
31 |
Y |
0.047 |
0.038 |
P |
|
|
|
32 |
Y |
0.048 |
0.033 |
P |
|
|
|
33 |
Y |
0.023 |
0.033 |
P |
|
|
|
34 |
Y |
0.044 |
0.033 |
P |
|
|
|
35 |
Y |
0.048 |
0.034 |
P |
|
|
|
36 |
Y |
0.044 |
0.035 |
P |
|
|
|
38 |
Y |
0.033 |
0.042 |
P |
|
|
|
39 |
Y |
0.045 |
0.035 |
P |
|
|
|
40 |
Y |
0.044 |
0.034 |
P |
|
|
|
41 |
Y |
0.027 |
0.039 |
P |
|
|
|
42 |
Y |
0.027 |
0.017 |
P |
|
|
|
44 |
Y |
0.028 |
0.038 |
P |
|
|
|
45 |
Y |
0.044 |
0.038 |
P |
|
|
|
46 |
Y |
0.031 |
0.040 |
P |
|
|
|
47 |
Y |
0.044 |
0.033 |
P |
|
|
|
48 |
Y |
0.047 |
0.034 |
P |
|
|
|
49 |
Y |
0.025 |
0.035 |
P |
|
|
|
50 |
Y |
0.028 |
0.018 |
P |
|
|
|
51 |
Y |
0.048 |
0.038 |
P |
|
|
|
52 |
Y |
0.044 |
0.057 |
P |
|
|
|
53 |
Y |
0.028 |
0.037 |
P |
|
|
|
55 |
Y |
0.028 |
0.033 |
P |
|
|
|
59 |
Y |
0.025 |
0.038 |
P |
|
|
| DBT12D |
1 |
Y |
0.015 |
0.025 |
P |
|
|
|
2 |
Y |
0.016 |
0.027 |
P |
|
|
|
3 |
Y |
0.014 |
0.023 |
P |
|
|
|
4 |
Y |
0.013 |
0.023 |
P |
|
|
|
5 |
Y |
0.019 |
0.029 |
P |
|
|
|
6 |
Y |
0.019 |
0.028 |
P |
|
|
|
7 |
Y |
0.016 |
0.023 |
P |
|
|
|
8 |
Y |
0.013 |
0.024 |
P |
|
|
|
9 |
Y |
0.018 |
0.028 |
P |
|
|
|
10 |
Y |
0.019 |
0.026 |
P |
|
|
|
11 |
Y |
0.018 |
0.027 |
P |
|
|
|
12 |
Y |
0.020 |
0.028 |
P |
|
|
|
15 |
Y |
0.022 |
0.032 |
P |
|
|
|
16 |
Y |
0.025 |
0.016 |
P |
|
|
|
18 |
Y |
0.031 |
0.023 |
P |
|
|
|
20 |
Y |
0.031 |
0.022 |
P |
|
|
|
21 |
Y |
0.026 |
0.017 |
P |
|
|
|
22 |
Y |
0.026 |
0.016 |
P |
|
|
|
23 |
Y |
0.028 |
0.021 |
P |
|
|
|
24 |
Y |
0.029 |
0.019 |
P |
|
|
|
25 |
Y |
0.029 |
0.020 |
P |
|
|
|
26 |
Y |
0.024 |
0.015 |
P |
|
|
|
27 |
Y |
0.024 |
0.016 |
P |
|
|
|
28 |
Y |
0.029 |
0.018 |
P |
|
|
|
30 |
Y |
0.025 |
0.015 |
P |
|
|
|
32 |
Y |
0.033 |
0.023 |
P |
|
|
| DBT12E |
1 |
Y |
0.018 |
0.026 |
P |
|
|
|
3 |
Y |
0.017 |
0.020 |
P |
|
|
|
5 |
Y |
0.018 |
0.020 |
P |
|
|
|
7 |
Y |
0.016 |
0.024 |
P |
|
|
|
9 |
Y |
0.018 |
0.020 |
P |
|
|
|
11 |
Y |
0.018 |
0.028 |
P |
|
|
|
13 |
Y |
0.016 |
0.025 |
P |
|
|
|
15 |
Y |
0.015 |
0.024 |
P |
|
|
|
17 |
Y |
0.016 |
0.026 |
P |
|
|
|
19 |
Y |
0.025 |
0.018 |
P |
|
|
|
21 |
Y |
0.018 |
0.029 |
P |
|
|
|
|---|
| THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
|---|
| SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
|---|
| Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
|---|
| Timers | - Check timers for correct operation and timing
|
|---|
| Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
|---|
| HTML Block |
|
|---|
| EMERGENCY LIGHTS | | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| T12C |
1 |
S |
Y |
Y |
Y |
P |
|
|
|
|
2 |
S |
Y |
Y |
Y |
P |
|
|
|
|
6 |
S |
Y |
Y |
Y |
P |
|
|
|
|
7 |
S |
Y |
Y |
Y |
P |
|
|
|
|
11 |
S |
Y |
Y |
Y |
P |
|
|
|
|
12 |
S |
Y |
Y |
Y |
P |
|
|
|
|
13 |
S |
Y |
Y |
Y |
P |
|
|
|
|
14 |
S |
Y |
Y |
Y |
P |
|
|
|
|
15 |
S |
Y |
Y |
Y |
P |
|
|
|
|
17 |
S |
Y |
Y |
Y |
P |
|
|
|
|
18 |
S |
Y |
Y |
Y |
P |
|
|
|
|
20 |
S |
Y |
N |
Y |
F |
Failed 90min Test |
Y |
N |
|
23 |
R |
Y |
Y |
Y |
P |
|
|
|
|
24 |
R |
Y |
Y |
Y |
P |
|
|
|
|
25 |
R |
Y |
Y |
Y |
P |
|
|
|
|
26 |
R |
Y |
Y |
Y |
P |
|
|
|
|
28 |
R |
Y |
Y |
Y |
P |
|
|
|
|
29 |
R |
Y |
Y |
Y |
P |
|
|
|
|
30 |
S |
Y |
Y |
Y |
P |
|
|
|
|
31 |
R |
Y |
Y |
Y |
P |
|
|
|
|
33 |
S |
Y |
Y |
Y |
P |
|
|
|
|
35 |
R |
Y |
Y |
Y |
P |
|
|
|
|
40 |
S |
Y |
Y |
Y |
P |
|
|
|
|
41 |
S |
Y |
Y |
Y |
P |
|
|
|
|
42 |
S |
Y |
Y |
Y |
P |
|
|
|
|
43 |
S |
Y |
Y |
Y |
P |
|
|
|
|
44 |
S |
Y |
Y |
Y |
P |
|
|
|
|
45 |
S |
Y |
Y |
Y |
P |
|
|
|
|
46 |
S |
Y |
Y |
Y |
P |
|
|
|
|
47 |
S |
Y |
Y |
Y |
P |
|
|
|
|
51 |
S |
Y |
Y |
Y |
P |
|
|
|
|
52 |
S |
Y |
Y |
Y |
P |
|
|
|
|
54 |
R |
Y |
Y |
Y |
P |
|
|
|
|
55 |
R |
Y |
Y |
Y |
P |
|
|
|
|
57 |
R |
Y |
Y |
Y |
P |
|
|
|
|
58 |
R |
Y |
Y |
Y |
P |
|
|
|
|
59 |
R |
Y |
Y |
Y |
P |
|
|
|
|
60 |
R |
Y |
Y |
Y |
P |
|
|
|
|
61 |
R |
Y |
Y |
Y |
P |
|
|
|
|
62 |
R |
Y |
Y |
Y |
P |
|
|
|
|
63 |
R |
Y |
Y |
Y |
P |
|
|
|
|
64 |
R |
Y |
Y |
Y |
P |
|
|
|
|
65 |
R |
Y |
Y |
Y |
P |
|
|
|
|
67 |
R |
Y |
Y |
Y |
P |
|
|
|
|
69 |
R |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| HTML Block |
|
|---|
| EXIT LIGHTS | | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| T12C |
3 |
Y |
Y |
Y |
P |
|
|
|
|
4 |
Y |
Y |
Y |
P |
|
|
|
|
5 |
Y |
Y |
Y |
P |
|
|
|
|
8 |
Y |
Y |
Y |
P |
|
|
|
|
9 |
Y |
Y |
Y |
P |
|
|
|
|
10 |
Y |
Y |
Y |
P |
|
|
|
|
16 |
Y |
Y |
Y |
P |
|
|
|
|
19 |
Y |
Y |
Y |
P |
|
|
|
|
21 |
Y |
Y |
Y |
P |
|
|
|
|
22 |
Y |
Y |
Y |
P |
|
|
|
|
27 |
Y |
Y |
Y |
P |
|
|
|
|
32 |
Y |
Y |
Y |
P |
|
|
|
|
34 |
Y |
Y |
Y |
P |
|
|
|
|
36 |
Y |
Y |
Y |
P |
|
|
|
|
37 |
Y |
Y |
Y |
P |
|
|
|
|
38 |
Y |
Y |
Y |
P |
|
|
|
|
39 |
Y |
Y |
Y |
P |
|
|
|
|
48 |
Y |
Y |
Y |
P |
|
|
|
|
49 |
Y |
Y |
Y |
P |
|
|
|
|
50 |
Y |
Y |
Y |
P |
|
|
|
|
53 |
Y |
Y |
Y |
P |
|
|
|
|
56 |
Y |
Y |
Y |
P |
|
|
|
|
66 |
Y |
Y |
Y |
P |
|
|
|
|
68 |
Y |
Y |
Y |
P |
|
|
|
|
70 |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
|---|
| General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
|---|
| HTML Block |
|
|---|
| General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
|---|
| HTML Block |
|
|---|
| Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
|---|
| Lighting Report | | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
| Ci-C Fluoro |
Y |
| 2x36W Diffused |
Y |
| 400W Flood Light |
Y |
| 70mm Downlight |
Y |
| 1x18 T5 Diffused |
Y |
| 2x18W Waterproof T5 |
Y |
| 140mm Downlight |
Y |
| 18W Compact Fluoro |
Y |
| 250W Square Diffused |
Y |
| 36W Lamps |
Y |
| Square Recessed Fluoro |
Y |
| Hi Bay |
Y |
|
|---|
| Are there any Warranty items needing to be repaired? | No |
|---|
| LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
| Light Control Switchboard Door + DBT12E Switchboard Door |
BOH loading dock |
4 |
Locks on switch board door have broken off so unable to close door on switchboards |
Y |
N |
N |
|
| LED Hibay |
Over F+P washing machines |
1 |
Not working |
Y |
N |
N |
A scissor lift was required. |
| Downlight |
TV’s + fridges |
4 |
Not working |
Y |
N |
N |
|
| Motion Sensor |
Upstairs office |
1 |
Sensor has broken off its base and is unable to be screwed back up |
Y |
N |
N |
|
| Surface Mount Emergency Light |
#20 |
1 |
Failed 90 min Test |
Y |
N |
N |
|
|
|---|
| Site Status Selector | Store now fully compliant |
|---|
| Next Test Due in 6 months | 20/03/2025 |
|---|
| |
|---|
| |