State | NSW |
---|
Date of Visit | 30/09/2024 |
---|
Technician's Name | Stuart Pearson |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 50F0015/0423 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in NSW | port_macquarie |
---|
|
|
---|
Location Name | Port Macquarie |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
DB |
1 |
Y |
25.9 |
18.9 |
P |
|
|
DB |
2 |
Y |
26.9 |
37.9 |
P |
|
|
DB |
8 |
Y |
27.9 |
18.9 |
P |
|
|
DB |
9 |
Y |
26.9 |
19.9 |
P |
|
|
DB |
10 |
Y |
26.9 |
19.9 |
P |
|
|
DB |
11 |
Y |
27.9 |
19.9 |
P |
|
|
DB |
12 |
Y |
27.9 |
18.9 |
P |
|
|
DB |
16 |
Y |
27.9 |
37.9 |
P |
|
|
DB |
17 |
Y |
27.9 |
22.9 |
P |
|
|
DB |
18 |
Y |
22.9 |
18.9 |
P |
|
|
DB |
19 |
Y |
22.9 |
17.9 |
P |
|
|
DB |
20 |
Y |
22.9 |
17.9 |
P |
|
|
DB |
21 |
Y |
27.9 |
18.9 |
P |
|
|
DB |
22 |
Y |
189.9 |
189.9 |
P |
|
|
DB |
23 |
Y |
23.9 |
19.9 |
P |
|
|
DB |
24 |
Y |
22.9 |
18.9 |
P |
|
|
DB |
25 |
Y |
22.9 |
32.9 |
P |
|
|
DB |
26 |
Y |
22.9 |
19.9 |
P |
|
|
DB |
27 |
Y |
27.9 |
24.9 |
P |
|
|
DB |
28 |
Y |
27.9 |
37.9 |
P |
|
|
DB |
29 |
Y |
27.9 |
18.9 |
P |
|
|
DB |
34 |
Y |
22.9 |
32.9 |
P |
|
|
DB |
35 |
Y |
27.9 |
19.9 |
P |
|
|
DB |
36 |
Y |
27.9 |
37.9 |
P |
|
|
DB |
37 |
Y |
22.9 |
16.9 |
P |
|
|
DB |
38 |
Y |
26.9 |
37.9 |
P |
|
|
DB |
39 |
Y |
27.9 |
37.9 |
P |
|
|
DB |
40 |
Y |
22.9 |
19.9 |
P |
|
|
DB |
41 |
Y |
28.9 |
19.9 |
P |
|
|
DB |
43 |
Y |
27.9 |
18.9 |
P |
|
|
DB |
44 |
Y |
27.9 |
22.9 |
P |
|
|
DB |
45 |
Y |
27.9 |
36.9 |
P |
|
|
DB |
46 |
Y |
27.9 |
19.9 |
P |
|
|
DB |
47 |
Y |
27.9 |
18.9 |
P |
|
|
DB |
48 |
Y |
27.9 |
19.9 |
P |
|
|
DB |
49 |
Y |
27.9 |
19.9 |
P |
|
|
DB |
52 |
Y |
28.9 |
37.9 |
P |
|
|
DB |
53 |
Y |
31.9 |
42.9 |
P |
|
|
DB |
54 |
Y |
27.9 |
18.9 |
P |
|
|
DB |
55 |
Y |
22.9 |
19.9 |
P |
|
|
DB |
56 |
Y |
27.9 |
19.9 |
P |
|
|
DB |
57 |
Y |
22.9 |
18.9 |
P |
|
|
DB |
61 |
Y |
28.9 |
37.9 |
P |
|
|
DB |
62 |
Y |
27.9 |
27.9 |
P |
|
|
DB |
63 |
Y |
31.9 |
23.9 |
P |
|
|
DB |
64 |
Y |
27.9 |
18.9 |
P |
|
|
DB |
65 |
Y |
28.9 |
37.9 |
P |
|
|
DB |
66 |
Y |
28.9 |
22.9 |
P |
|
|
DB |
67 |
Y |
27.9 |
19.9 |
P |
|
|
DB |
68 |
Y |
22.9 |
18.9 |
P |
|
|
DB |
69 |
Y |
23.9 |
18.9 |
P |
|
|
DB |
70 |
Y |
27.9 |
37.9 |
P |
|
|
DB |
71 |
Y |
27.9 |
18.9 |
P |
|
|
DB |
72 |
Y |
28.9 |
19.9 |
P |
|
|
DB |
73 |
Y |
27.9 |
18.9 |
P |
|
|
DB |
74 |
Y |
23.9 |
19.9 |
P |
|
|
DB |
75 |
Y |
27.9 |
37.9 |
P |
|
|
DB |
76 |
Y |
28.9 |
37.9 |
P |
|
|
DB |
80, 81, 82 |
Y |
27.9 |
37.9 |
P |
|
|
DB |
83 |
Y |
26.9 |
19.9 |
P |
|
|
DB |
84 |
Y |
26.9 |
18.9 |
P |
|
|
DB |
85 |
Y |
27.9 |
28.9 |
P |
|
|
DB |
86 |
Y |
28.9 |
18.9 |
P |
|
|
DB |
87 |
Y |
27.9 |
37.9 |
P |
|
|
DB |
88 |
Y |
22.9 |
18.9 |
P |
|
|
DB |
89 |
Y |
22.9 |
18.9 |
P |
|
|
DB |
90 |
Y |
22.9 |
37.9 |
P |
|
|
DB |
91 |
Y |
27.9 |
23.9 |
P |
|
|
DB |
92 |
Y |
23.9 |
18.9 |
P |
|
|
DB |
94 |
Y |
22.9 |
18.9 |
P |
|
|
DB |
95 |
Y |
28.9 |
38.9 |
P |
|
|
DB |
97 |
Y |
22.9 |
18.9 |
P |
|
|
DB |
98 |
Y |
28.9 |
18.9 |
P |
|
|
DB |
99 |
Y |
28.9 |
37.9 |
P |
|
|
DB |
100 |
Y |
27.9 |
33.9 |
P |
|
|
DB |
101 |
Y |
22.9 |
37.9 |
P |
|
|
DB |
102 |
Y |
27.9 |
18.9 |
P |
|
|
DB |
103 |
Y |
25.9 |
18.9 |
P |
|
|
DB |
104 |
Y |
26.9 |
18.9 |
P |
|
|
DB |
105 |
Y |
27.9 |
18.9 |
P |
|
|
DB |
106 |
Y |
26.9 |
18.9 |
P |
|
|
DB |
107 |
Y |
26.9 |
18.9 |
P |
|
|
DB |
108 |
Y |
26.9 |
18.9 |
P |
|
|
DB |
109 |
Y |
27.9 |
18.9 |
P |
|
|
DB |
110 |
Y |
27.9 |
18.9 |
P |
|
|
DB |
111 |
Y |
27.9 |
18.9 |
P |
|
|
DB |
112 |
Y |
27.9 |
19.9 |
P |
|
|
DB |
113 |
Y |
22.9 |
37.9 |
P |
|
|
DB |
114 |
Y |
27.9 |
19.9 |
P |
|
|
DB |
115 |
Y |
27.9 |
18.9 |
P |
|
|
DB |
116 |
Y |
27.9 |
18.9 |
P |
|
|
DB |
117 |
Y |
27.9 |
37.9 |
P |
|
|
DB |
118 |
Y |
27.9 |
19.9 |
P |
|
|
DB |
119 |
Y |
22.9 |
19.9 |
P |
|
|
DB |
120 |
Y |
27.9 |
37.9 |
P |
|
|
DB |
121 |
Y |
27.9 |
18.9 |
P |
|
|
DB |
122 |
Y |
183.9 |
178.9 |
P |
|
|
DB |
123 |
Y |
25.9 |
35.9 |
P |
|
|
DB |
124 |
Y |
178.9 |
183.9 |
P |
|
|
DB |
125 |
Y |
27.9 |
18.9 |
P |
|
|
DB |
126 |
Y |
27.9 |
23.9 |
P |
|
|
DB |
127 |
Y |
26.9 |
19.9 |
P |
|
|
DB |
128 |
Y |
28.9 |
18.9 |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB |
1B |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
2B |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
3B |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
4B |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
5B |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
6B |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
7B |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
8B |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
9B |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
10B |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
11B |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
12B |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
13B |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
14B |
R |
Y |
Y |
Y |
P |
|
|
|
DB |
15B |
R |
Y |
Y |
Y |
P |
|
|
|
DB |
16B |
R |
Y |
Y |
Y |
P |
|
|
|
DB |
1 |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
2 |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
3 |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
4 |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
5 |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
6 |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
7 |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
8 |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
9 |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
10 |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
11 |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
12 |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
13 |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
14 |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
15 |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
16 |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
17 |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
18 |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
19 |
S |
Y |
Y |
Y |
P |
|
|
|
DB |
20 |
S |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB |
1B |
Y |
Y |
Y |
P |
|
|
|
DB |
2B |
Y |
Y |
Y |
P |
|
|
|
DB |
3B |
Y |
Y |
Y |
P |
|
|
|
DB |
4B |
Y |
Y |
Y |
P |
|
|
|
DB |
5B |
Y |
Y |
Y |
P |
|
|
|
DB |
6B |
Y |
Y |
Y |
P |
|
|
|
DB |
7B |
Y |
Y |
Y |
P |
|
|
|
DB |
8B |
Y |
Y |
Y |
P |
|
|
|
DB |
1 |
Y |
Y |
Y |
P |
|
|
|
DB |
2 |
Y |
Y |
Y |
P |
|
|
|
DB |
3 |
Y |
Y |
Y |
P |
|
|
|
DB |
4 |
Y |
Y |
Y |
P |
|
|
|
DB |
5 |
Y |
Y |
Y |
P |
|
|
|
DB |
6 |
Y |
Y |
Y |
P |
|
|
|
DB |
7 |
Y |
Y |
Y |
P |
|
|
|
DB |
8 |
Y |
Y |
Y |
P |
|
|
|
DB |
9 |
Y |
Y |
Y |
P |
|
|
|
DB |
10 |
Y |
Y |
Y |
P |
|
|
|
DB |
11 |
Y |
Y |
Y |
P |
|
|
|
DB |
12 |
Y |
Y |
Y |
P |
|
|
|
DB |
13 |
Y |
Y |
Y |
P |
|
|
|
DB |
14 |
Y |
Y |
Y |
P |
|
|
|
DB |
15 |
Y |
Y |
Y |
P |
|
|
|
DB |
16 |
Y |
Y |
Y |
P |
|
|
|
DB |
17 |
Y |
Y |
Y |
P |
|
|
|
DB |
18 |
Y |
Y |
Y |
P |
|
|
|
DB |
19 |
Y |
Y |
Y |
P |
|
|
|
DB |
20 |
Y |
Y |
Y |
P |
|
|
|
DB |
21 |
Y |
Y |
Y |
P |
|
|
|
DB |
22 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
200W Square Fluoro |
Y |
200W High Bay Fluoro |
Y |
36W Single Fluoro with LED Tubes |
Y |
2x36W Fluoro Fittings with LED Tubes |
Y |
2x28W Fluoro Fitting |
Y |
18W Fluoro Fitting |
Y |
30W Fluoro Fitting |
Y |
36W Emergency Maintained Fluoro |
Y |
LED Exit Light |
Y |
Twin Halogen Spot Emergency Floodlight |
Y |
LED Spitfire |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
Em/Ex Light Floor Plan |
Maintenance Folder |
1 |
Roughly drawn old plan |
Y |
N |
N |
New Ex/Em light floor plan placed in store. |
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 30/03/2025 |
---|
| |
---|
| |