Partner NameTransit Electrical Pty Ltd
StateWA
Date of Visit08/10/2024
Technician's NameBayley Woodroffe
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number50F0023/0161
EmailEmail hidden; Javascript is required.
The Good Guys Site in WAosborne_park

Location NameOsborne Park
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DBT1 W9 Y P
B9 Y P
W10 Y P
B10 Y P
R11 Y P
W11 Y P
B11 Y P
R12 Y P
W12 Y P
B12 Y P
R13 N F Push button didn’t trip rcbo Y
W13 Y P
B13 Y P
R14 Y P
W14 Y P
B14 Y P
R15 Y P
W15 Y P
B15 Y P
R16 Y P
W16 Y P
B16 Y P
R17 Y P
W17 Y P
B17 Y P
R18 Y P
W18 Y P
B18 Y P
R19 Y P
Sub Board 1 R1 Y P
W1 Y P
B1 Y P
R2 Y P
W2 Y P
B2 Y P
R4 Y P
W4 Y P
B4 Y P
R5 Y P
W5 Y P
B5 Y P
R6 Y P
W6 Y P
B6 Y P
R7 Y P
R8 Y P
W8 Y P
B8 Y P
R10 Y P
W10 Y P
B10 Y P
R12 Y P
W12 Y P
B12 Y P
Sub Board 2 R2 Y P
W2 Y P
B2 Y P
W3 N F Push button didn’t trip rcbo Y
B3 N/A F Won’t turn on, keeps tripping Y
R4 Y P
W4 Y P
B4 Y P
R5 N F Push button didn’t trip rcbo Y
B5 Y P
R6 Y P
W6 Y P
B6 Y P
R8 Y P
W8 Y P
B8 Y P
W9 Y P
R10 Y P
B10 Y P
W13 Y P
B13 Y P
R14 Y P
W14 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DBT1 2 R Y Y Y P
3 R Y Y Y P
4 R Y Y Y P
5 S - Twin LED Y Y Y P
6 S - Twin LED Y Y Y P
7 S - Twin LED Y Y Y P
9 S - Twin LED Y Y Y P
10 S - Twin LED Y Y Y P
12 S - Twin LED Y Y Y P
14 R Y Y Y P
15 R Y Y Y P
16 S - Twin LED Y Y Y P
17 S - Twin batten type Y Y Y P
19 R Y Y Y P
20 S - Twin batten type Y Y Y P
21 S - Twin LED Y Y Y P
22 S - Twin LED Y Y Y P
25 S - Twin LED Y Y Y P
26 S - Twin LED Y Y Y P
27 S - LED Y Y Y P
30 R Y Y Y P
32 S - Twin LED Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DBT1 1 Y Y Y P
8 Y Y Y P
11 Y Y Y P
13 Y Y Y P
18 Y Y Y P
23 Y Y Y P
24 Y N Y F Failed em light test Y N
28 Y Y Y P
29 Y Y Y P
31 Y N Y F Failed em light test Y N
33 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
LED Hibays Y
16y 18w Lights Y
Oyster Lights Y
LED Diffused Batten Y
LED Down Lights Y
Exit Lights Y
Spitfire Emergency Lights Y
26y 36w Emergency Battens Diffused Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
RCBO R13 DBT1 1 Push button didn’t trip RCBO Y N N
RCBO W3 + R5 Sub board 2 2 Push button didn’t trip rcbo Y N N
Exit Light #24 Microwaves 1 Failed emergency light test Y N N Scissor Lift was required
Exit Light #31 Upstairs office 1 Failed em light test Y N N
RCBO B3 Sub board 2 1 Keeps tripping at LG and Fisher & Paykel Fridge Wall Displays, won’t turn on Y N N Upon liaising with Store Manager, tripping has stopped and Wall Displays are operating as intended. If any issues arise, please send through work order to further investigate
Site Status SelectorStore now fully compliant
Next Test Due in 6 months08/04/2025