Partner Name | Transit Electrical Pty Ltd |
---|
State | WA |
---|
Date of Visit | 14/11/2024 |
---|
Technician's Name | Chris Ogden |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 23642 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in WA | mandurah |
---|
|
|
---|
Location Name | Mandurah |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
DB1 |
R1 |
Y |
|
|
P |
|
|
|
W1 |
Y |
|
|
P |
|
|
|
B1 |
Y |
|
|
P |
|
|
|
R2 |
Y |
|
|
P |
|
|
|
W2 |
Y |
|
|
P |
|
|
|
B2 |
Y |
|
|
P |
|
|
|
R3 |
Y |
|
|
P |
|
|
|
W3 |
Y |
|
|
P |
|
|
|
B3 |
Y |
|
|
P |
|
|
|
R4 |
Y |
|
|
P |
|
|
|
W4 |
Y |
|
|
P |
|
|
|
B4 |
Y |
|
|
P |
|
|
|
R5 |
Y |
|
|
P |
|
|
|
W5 |
Y |
|
|
P |
|
|
|
B5 |
Y |
|
|
P |
|
|
|
R6 |
Y |
|
|
P |
|
|
|
W6 |
Y |
|
|
P |
|
|
|
B6 |
Y |
|
|
P |
|
|
|
R7 |
Y |
|
|
P |
|
|
|
R8 |
Y |
|
|
P |
|
|
|
R10 |
Y |
|
|
P |
|
|
|
W10 |
Y |
|
|
P |
|
|
|
B10 |
Y |
|
|
P |
|
|
|
R11 |
Y |
|
|
P |
|
|
|
W11 |
Y |
|
|
P |
|
|
|
B11 |
Y |
|
|
P |
|
|
|
R12 |
Y |
|
|
P |
|
|
|
W12 |
Y |
|
|
P |
|
|
|
B12 |
Y |
|
|
P |
|
|
|
R13 |
Y |
|
|
P |
|
|
|
W13 |
Y |
|
|
P |
|
|
|
B13 |
Y |
|
|
P |
|
|
|
R14 |
Y |
|
|
P |
|
|
|
W14 |
Y |
|
|
P |
|
|
|
B14 |
Y |
|
|
P |
|
|
|
R15 |
Y |
|
|
P |
|
|
|
W15 |
Y |
|
|
P |
|
|
|
B15 |
Y |
|
|
P |
|
|
|
R16 |
Y |
|
|
P |
|
|
|
W16 |
Y |
|
|
P |
|
|
|
B16 |
Y |
|
|
P |
|
|
|
R17 |
Y |
|
|
P |
|
|
|
W17 |
Y |
|
|
P |
|
|
|
B17 |
Y |
|
|
P |
|
|
|
R18 |
Y |
|
|
P |
|
|
|
W18 |
Y |
|
|
P |
|
|
|
B18 |
Y |
|
|
P |
|
|
|
B19 |
Y |
|
|
P |
|
|
|
R20 |
Y |
|
|
P |
|
|
|
RWB21 |
Y |
|
|
P |
|
|
|
R26 |
Y |
|
|
P |
|
|
|
R33 |
Y |
|
|
P |
|
|
|
W33 |
Y |
|
|
P |
|
|
|
B33 |
Y |
|
|
P |
|
|
|
R34 |
Y |
|
|
P |
|
|
|
W34 |
Y |
|
|
P |
|
|
|
B34 |
Y |
|
|
P |
|
|
|
R35 |
Y |
|
|
P |
|
|
|
W35 |
Y |
|
|
P |
|
|
|
B35 |
Y |
|
|
P |
|
|
|
R36 |
Y |
|
|
P |
|
|
|
W36 |
Y |
|
|
P |
|
|
|
B36 |
Y |
|
|
P |
|
|
|
R37 |
Y |
|
|
P |
|
|
|
W37 |
Y |
|
|
P |
|
|
|
B37 |
Y |
|
|
P |
|
|
|
R45 |
Y |
|
|
P |
|
|
|
W45 |
Y |
|
|
P |
|
|
|
B45 |
Y |
|
|
P |
|
|
|
R46 |
Y |
|
|
P |
|
|
|
B46 |
Y |
|
|
P |
|
|
|
R47 |
Y |
|
|
P |
|
|
|
W47 |
Y |
|
|
P |
|
|
|
B47 |
Y |
|
|
P |
|
|
|
R48 |
Y |
|
|
P |
|
|
|
W48 |
Y |
|
|
P |
|
|
|
B48 |
Y |
|
|
P |
|
|
|
R49 |
Y |
|
|
P |
|
|
|
W49 |
Y |
|
|
P |
|
|
|
B49 |
Y |
|
|
P |
|
|
|
RWB51 |
Y |
|
|
P |
|
|
DB2 |
CB1 |
Y |
|
|
P |
|
|
|
CB2 |
Y |
|
|
P |
|
|
|
CB3 |
Y |
|
|
P |
|
|
|
CB4 |
Y |
|
|
P |
|
|
|
CB5 |
Y |
|
|
P |
|
|
|
CB6 |
Y |
|
|
P |
|
|
|
CB8 |
Y |
|
|
P |
|
|
|
CB9 |
Y |
|
|
P |
|
|
|
CB10 |
Y |
|
|
P |
|
|
|
CB11 |
Y |
|
|
P |
|
|
|
CB12 |
Y |
|
|
P |
|
|
|
CB13 |
Y |
|
|
P |
|
|
|
CB14 |
Y |
|
|
P |
|
|
|
CB15 |
Y |
|
|
P |
|
|
|
CB16 |
Y |
|
|
P |
|
|
|
CB17 |
Y |
|
|
P |
|
|
|
CB18 |
Y |
|
|
P |
|
|
|
CB19 |
Y |
|
|
P |
|
|
|
CB21 |
Y |
|
|
P |
|
|
|
CB23 |
Y |
|
|
P |
|
|
|
CB25 |
Y |
|
|
P |
|
|
|
CB26 |
Y |
|
|
P |
|
|
|
CB27 |
Y |
|
|
P |
|
|
|
CB28 |
Y |
|
|
P |
|
|
|
CB29 |
Y |
|
|
P |
|
|
|
CB30 |
Y |
|
|
P |
|
|
|
CB31 |
Y |
|
|
P |
|
|
|
CB33 |
Y |
|
|
P |
|
|
|
CB35 |
Y |
|
|
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB1 |
3 |
S |
Y |
Y |
Y |
P |
|
|
|
|
7 |
S |
Y |
Y |
Y |
P |
|
|
|
|
9 |
S |
Y |
Y |
Y |
P |
|
|
|
|
11 |
S |
Y |
Y |
Y |
P |
|
|
|
|
14 |
S |
Y |
Y |
Y |
P |
|
|
|
|
16 |
S |
Y |
Y |
Y |
P |
|
|
|
|
18 |
S |
Y |
Y |
Y |
P |
|
|
|
|
20 |
S |
Y |
Y |
Y |
P |
|
|
|
|
22 |
S |
Y |
Y |
Y |
P |
|
|
|
|
25 |
S |
Y |
Y |
Y |
P |
|
|
|
|
27 |
S |
Y |
Y |
Y |
P |
|
|
|
|
30 |
S |
Y |
Y |
Y |
P |
|
|
|
|
32 |
R |
Y |
Y |
Y |
P |
|
|
|
|
34 |
R |
Y |
Y |
Y |
P |
|
|
|
|
36 |
S |
Y |
Y |
Y |
P |
|
|
|
|
38 |
R |
Y |
Y |
Y |
P |
|
|
|
|
40 |
S |
Y |
Y |
Y |
P |
|
|
|
|
44 |
S |
Y |
Y |
Y |
P |
|
|
|
|
46 |
S |
Y |
Y |
Y |
P |
|
|
|
|
50 |
R |
Y |
Y |
Y |
P |
|
|
|
|
51 |
R |
Y |
Y |
Y |
P |
|
|
|
|
53 |
R |
Y |
Y |
Y |
P |
|
|
|
|
54 |
R |
Y |
Y |
Y |
P |
|
|
|
|
55 |
R |
Y |
Y |
Y |
P |
|
|
|
|
56 |
R |
Y |
Y |
Y |
P |
|
|
|
|
57 |
R |
Y |
Y |
Y |
P |
|
|
|
|
58 |
R |
Y |
Y |
Y |
P |
|
|
|
|
59 |
S |
Y |
Y |
Y |
P |
|
|
|
|
60 |
S |
Y |
N |
N |
F |
Battery |
Y |
N |
|
61 |
S |
Y |
Y |
Y |
P |
|
|
|
|
62 |
S |
Y |
Y |
Y |
P |
|
|
|
|
63 |
S |
Y |
Y |
Y |
P |
|
|
|
|
64 |
R |
Y |
Y |
Y |
P |
|
|
|
|
65 |
R |
Y |
Y |
Y |
P |
|
|
|
|
66 |
S |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB1 |
1 |
Y |
Y |
Y |
P |
|
|
|
|
2 |
Y |
Y |
Y |
P |
|
|
|
|
4 |
Y |
Y |
Y |
P |
|
|
|
|
5 |
Y |
Y |
Y |
P |
|
|
|
|
6 |
Y |
Y |
Y |
P |
|
|
|
|
8 |
Y |
Y |
Y |
P |
|
|
|
|
10 |
Y |
Y |
Y |
P |
|
|
|
|
12 |
Y |
Y |
Y |
P |
|
|
|
|
13 |
Y |
Y |
Y |
P |
|
|
|
|
15 |
Y |
Y |
Y |
P |
|
|
|
|
17 |
Y |
Y |
Y |
P |
|
|
|
|
19 |
Y |
Y |
Y |
P |
|
|
|
|
21 |
Y |
Y |
Y |
P |
|
|
|
|
23 |
Y |
Y |
Y |
P |
|
|
|
|
24 |
Y |
Y |
Y |
P |
|
|
|
|
26 |
Y |
Y |
Y |
P |
|
|
|
|
28 |
Y |
Y |
Y |
P |
|
|
|
|
29 |
Y |
Y |
Y |
P |
|
|
|
|
31 |
Y |
Y |
Y |
P |
|
|
|
|
33 |
Y |
Y |
Y |
P |
|
|
|
|
35 |
Y |
Y |
Y |
P |
|
|
|
|
37 |
Y |
Y |
Y |
P |
|
|
|
|
39 |
Y |
Y |
Y |
P |
|
|
|
|
41 |
Y |
Y |
Y |
P |
|
|
|
|
42 |
Y |
Y |
Y |
P |
|
|
|
|
43 |
Y |
Y |
Y |
P |
|
|
|
|
47 |
Y |
Y |
Y |
P |
|
|
|
|
48 |
Y |
Y |
Y |
P |
|
|
|
|
49 |
Y |
Y |
Y |
P |
|
|
|
|
52 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
400w Hibay |
Y |
400w Low Bay |
Y |
400w Low Bay Defused |
Y |
LED Down Lights SAL |
Y |
1 by 36w Defused Battens |
Y |
1 by 30w Defused Battens |
Y |
Jumbo Exit |
Y |
2 by par 38 Spot |
Y |
1 by 30w Defused Emergency Batten Dual Operation |
Y |
Oyster Light |
Y |
LED Oyster Light |
Y |
150w Round MH Shop Light |
Y |
Exits |
Y |
2 by 36w Defused Emergency Batten |
Y |
Spitfire Emergency |
Y |
40w Batten |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
RCD |
CB18 DB2 |
1 |
Nuisance Tripping |
N |
N |
TBA |
Quote #1548 submitted to Compliance on 23/09/2024. Awaiting approval. |
HiBay |
Near TV's |
1 |
Faulty |
Y |
N |
N |
Scissor Lift was required. |
Surface Mount Emergency Light #60 |
Back of House |
1 |
Faulty Battery |
Y |
N |
N |
Scissor Lift was required. |
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 14/05/2025 |
---|
| |
---|
| |