Partner Name | Sturdie Trade Services |
---|
State | VIC |
---|
Date of Visit | 21/11/2024 |
---|
Technician's Name | Matt Setches |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 50F0017/0397 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in VIC | brighton |
---|
|
|
---|
Location Name | Brighton |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
DB-1 Chassis A |
19 |
Y |
31 |
35 |
P |
|
|
|
20 |
Y |
38 |
32 |
P |
|
|
|
21 |
Y |
39 |
32 |
P |
|
|
|
22 |
Y |
38 |
32 |
P |
|
|
|
23 |
Y |
38 |
32 |
P |
|
|
|
24 |
Y |
38 |
38 |
P |
|
|
|
25 |
Y |
39 |
39 |
P |
|
|
|
26 |
Y |
32 |
32 |
P |
|
|
|
27 |
Y |
37 |
31 |
P |
|
|
|
28 |
Y |
39 |
48 |
P |
|
|
|
29 |
Y |
38 |
39 |
P |
|
|
|
30 |
Y |
38 |
31 |
P |
|
|
|
31 |
Y |
39 |
40 |
P |
|
|
|
32 |
Y |
41 |
40 |
P |
|
|
|
33 |
Y |
38 |
38 |
P |
|
|
|
34 |
Y |
39 |
31 |
P |
|
|
|
35 |
Y |
38 |
31 |
P |
|
|
|
36 |
Y |
38 |
38 |
P |
|
|
|
37 |
Y |
31 |
39 |
P |
|
|
|
38 |
Y |
38 |
38 |
P |
|
|
|
39 |
Y |
40 |
37 |
P |
|
|
|
40 |
Y |
39 |
37 |
P |
|
|
|
41 |
Y |
35 |
32 |
P |
|
|
|
42 |
Y |
42 |
54 |
P |
|
|
|
43 |
Y |
38 |
32 |
P |
|
|
|
45 |
Y |
38 |
38 |
P |
|
|
|
47 |
Y |
32 |
38 |
P |
|
|
|
49 |
Y |
40 |
38 |
P |
|
|
|
51 |
Y |
37 |
38 |
P |
|
|
|
53 |
Y |
39 |
38 |
P |
|
|
Chassis B |
1 |
Y |
40 |
40 |
P |
|
|
|
2 |
Y |
37 |
35 |
P |
|
|
|
3 |
Y |
39 |
56 |
P |
|
|
|
4 |
Y |
42 |
43 |
P |
|
|
|
5 |
Y |
52 |
48 |
P |
|
|
|
6 |
Y |
41 |
34 |
P |
|
|
|
7 |
Y |
35 |
30 |
P |
|
|
|
8 |
Y |
34 |
44 |
P |
|
|
|
9 |
Y |
31 |
31 |
P |
|
|
|
10 |
Y |
37 |
43 |
P |
|
|
|
11 |
Y |
35 |
32 |
P |
|
|
|
12 |
Y |
39 |
37 |
P |
|
|
|
13 |
Y |
39 |
34 |
P |
|
|
|
14 |
Y |
35 |
37 |
P |
|
|
|
15 |
Y |
31 |
29 |
P |
|
|
|
16 |
Y |
37 |
33 |
P |
|
|
|
17 |
Y |
37 |
38 |
P |
|
|
|
18 |
Y |
31 |
29 |
P |
|
|
|
19 |
Y |
35 |
33 |
P |
|
|
|
20 |
Y |
31 |
33 |
P |
|
|
|
21 |
Y |
38 |
35 |
P |
|
|
|
22 |
Y |
30 |
36 |
P |
|
|
|
23 |
Y |
36 |
32 |
P |
|
|
|
24 |
Y |
45 |
36 |
P |
|
|
|
25 |
Y |
29 |
33 |
P |
|
|
|
26 |
Y |
39 |
38 |
P |
|
|
|
27 |
Y |
33 |
32 |
P |
|
|
|
28 |
Y |
32 |
31 |
P |
|
|
|
29 |
Y |
31 |
32 |
P |
|
|
|
30 |
Y |
42 |
52 |
P |
|
|
|
31 |
Y |
32 |
29 |
P |
|
|
|
32 |
Y |
45 |
36 |
P |
|
|
|
33 |
Y |
33 |
32 |
P |
|
|
|
34 |
Y |
32 |
32 |
P |
|
|
|
35 |
Y |
30 |
33 |
P |
|
|
|
36 |
Y |
32 |
29 |
P |
|
|
|
37 |
Y |
33 |
31 |
P |
|
|
|
38 |
Y |
34 |
35 |
P |
|
|
|
39 |
Y |
35 |
34 |
P |
|
|
|
40 |
Y |
51 |
44 |
P |
|
|
|
41 |
Y |
37 |
32 |
P |
|
|
|
42 |
Y |
39 |
37 |
P |
|
|
|
43 |
Y |
33 |
40 |
P |
|
|
|
44 |
Y |
40 |
35 |
P |
|
|
|
45 |
Y |
32 |
32 |
P |
|
|
|
46 |
Y |
33 |
29 |
P |
|
|
|
47 |
Y |
37 |
52 |
P |
|
|
|
48 |
Y |
40 |
39 |
P |
|
|
|
49 |
Y |
38 |
38 |
P |
|
|
|
51 |
Y |
31 |
39 |
P |
|
|
|
53 |
Y |
38 |
37 |
P |
|
|
|
55 |
Y |
38 |
37 |
P |
|
|
|
57 |
Y |
38 |
35 |
P |
|
|
|
59 |
Y |
31 |
31 |
P |
|
|
DB - 2 |
2 |
Y |
25 |
17 |
P |
|
|
|
4 |
Y |
26 |
17 |
P |
|
|
|
6 |
Y |
24 |
17 |
P |
|
|
|
7 |
Y |
13 |
23 |
P |
|
|
|
8 |
Y |
25 |
16 |
P |
|
|
|
9 |
Y |
11 |
21 |
P |
|
|
|
10 |
Y |
24 |
17 |
P |
|
|
|
11 |
Y |
12 |
22 |
P |
|
|
|
12 |
Y |
24 |
16 |
P |
|
|
|
13 |
Y |
24 |
16 |
P |
|
|
|
14 |
Y |
25 |
25 |
P |
|
|
|
15 |
Y |
25 |
16 |
P |
|
|
|
16 |
Y |
24 |
17 |
P |
|
|
|
17 |
Y |
24 |
15 |
P |
|
|
|
18 |
Y |
28 |
18 |
P |
|
|
|
19 |
Y |
26 |
18 |
P |
|
|
|
20 |
Y |
25 |
25 |
P |
|
|
|
22 |
Y |
24 |
15 |
P |
|
|
|
23 |
Y |
25 |
17 |
P |
|
|
|
24 |
Y |
25 |
17 |
P |
|
|
|
25 |
Y |
25 |
17 |
P |
|
|
|
26 |
Y |
25 |
17 |
P |
|
|
|
27 |
Y |
25 |
23 |
P |
|
|
|
28 |
Y |
27 |
19 |
P |
|
|
|
29 |
Y |
61 |
52 |
P |
|
|
|
30 |
Y |
27 |
18 |
P |
|
|
|
31 |
Y |
25 |
17 |
P |
|
|
|
32 |
Y |
25 |
26 |
P |
|
|
|
33 |
Y |
28 |
28 |
P |
|
|
|
34 |
Y |
25 |
26 |
P |
|
|
|
35 |
Y |
28 |
18 |
P |
|
|
|
36 |
Y |
28 |
18 |
P |
|
|
|
37 |
Y |
28 |
18 |
P |
|
|
|
38 |
Y |
33 |
24 |
P |
|
|
|
39 |
Y |
28 |
18 |
P |
|
|
|
40 |
Y |
24 |
19 |
P |
|
|
|
41 |
Y |
28 |
18 |
P |
|
|
|
42 |
Y |
25 |
17 |
P |
|
|
|
43 |
Y |
26 |
18 |
P |
|
|
|
44 |
Y |
30 |
21 |
P |
|
|
|
45 |
Y |
24 |
16 |
P |
|
|
|
46 |
Y |
25 |
17 |
P |
|
|
|
47 |
Y |
28 |
18 |
P |
|
|
|
48 |
Y |
25 |
17 |
P |
|
|
|
49 |
Y |
25 |
17 |
P |
|
|
|
50 |
Y |
28 |
17 |
P |
|
|
DB - 3 |
1 |
Y |
29 |
19 |
P |
|
|
|
2 |
Y |
28 |
18 |
P |
|
|
|
3 |
Y |
28 |
16 |
P |
|
|
|
4 |
Y |
29 |
19 |
P |
|
|
|
5 |
Y |
25 |
18 |
P |
|
|
|
6 |
Y |
28 |
17 |
P |
|
|
|
7 |
Y |
28 |
16 |
P |
|
|
|
8 |
Y |
28 |
18 |
P |
|
|
|
9 |
Y |
28 |
17 |
P |
|
|
|
10 |
Y |
28 |
18 |
P |
|
|
|
11 |
Y |
28 |
18 |
P |
|
|
|
12 |
Y |
28 |
18 |
P |
|
|
|
13 |
Y |
25 |
17 |
P |
|
|
|
14 |
Y |
24 |
16 |
P |
|
|
|
15 |
Y |
23 |
15 |
P |
|
|
|
16 |
Y |
25 |
18 |
P |
|
|
|
17 |
Y |
24 |
16 |
P |
|
|
|
18 |
Y |
23 |
16 |
P |
|
|
|
19 |
Y |
25 |
18 |
P |
|
|
|
20 |
Y |
28 |
18 |
P |
|
|
|
21 |
Y |
28 |
18 |
P |
|
|
|
22 |
Y |
24 |
25 |
P |
|
|
|
23 |
Y |
26 |
19 |
P |
|
|
|
24 |
Y |
28 |
18 |
P |
|
|
|
25 |
Y |
28 |
18 |
P |
|
|
|
26 |
Y |
28 |
18 |
P |
|
|
|
27 |
Y |
131 |
24 |
P |
|
|
|
28 |
Y |
28 |
18 |
P |
|
|
|
29 |
Y |
28 |
18 |
P |
|
|
|
30 |
Y |
28 |
18 |
P |
|
|
|
31 |
Y |
28 |
18 |
P |
|
|
|
32 |
Y |
28 |
18 |
P |
|
|
|
33 |
Y |
28 |
18 |
P |
|
|
|
34 |
Y |
28 |
18 |
P |
|
|
|
35 |
Y |
28 |
18 |
P |
|
|
|
36 |
Y |
28 |
18 |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB - 1 |
1 |
R |
Y |
Y |
Y |
P |
|
|
|
|
2 |
R |
Y |
Y |
Y |
P |
|
|
|
|
3 |
R |
Y |
Y |
Y |
P |
|
|
|
|
4 |
R |
Y |
Y |
Y |
P |
|
|
|
|
5 |
R |
Y |
Y |
Y |
P |
|
|
|
|
6 |
R |
Y |
Y |
Y |
P |
|
|
|
|
7 |
R |
Y |
Y |
Y |
P |
|
|
|
|
8 |
R |
Y |
Y |
Y |
P |
|
|
|
|
9 |
R |
Y |
Y |
Y |
P |
|
|
|
|
10 |
R |
Y |
Y |
Y |
P |
|
|
|
|
11 |
R |
Y |
Y |
Y |
P |
|
|
|
|
12 |
R |
Y |
Y |
Y |
P |
|
|
|
|
13 |
R |
Y |
Y |
Y |
P |
|
|
|
|
14 |
R |
Y |
Y |
Y |
P |
|
|
|
|
15 |
R |
Y |
Y |
Y |
P |
|
|
|
|
16 |
R |
Y |
Y |
Y |
P |
|
|
|
|
17 |
R |
Y |
Y |
Y |
P |
|
|
|
|
18 |
R |
Y |
Y |
Y |
P |
|
|
|
|
19 |
R |
Y |
Y |
Y |
P |
|
|
|
|
20 |
R |
Y |
Y |
Y |
P |
|
|
|
|
21 |
R |
Y |
Y |
Y |
P |
|
|
|
|
22 |
R |
Y |
Y |
Y |
P |
|
|
|
|
23 |
R |
Y |
Y |
Y |
P |
|
|
|
|
24 |
R |
Y |
Y |
Y |
P |
|
|
|
|
25 |
R |
Y |
Y |
Y |
P |
|
|
|
|
26 |
R |
Y |
Y |
Y |
P |
|
|
|
|
27 |
R |
Y |
Y |
Y |
P |
|
|
|
|
28 |
R |
Y |
Y |
Y |
P |
|
|
|
|
29 |
R |
Y |
Y |
Y |
P |
|
|
|
|
30 |
R |
Y |
Y |
Y |
P |
|
|
|
|
31 |
R |
Y |
Y |
Y |
P |
|
|
|
|
32 |
R |
Y |
Y |
Y |
P |
|
|
|
|
33 |
R |
Y |
Y |
Y |
P |
|
|
|
|
34 |
R |
Y |
Y |
Y |
P |
|
|
|
|
35 |
R |
Y |
Y |
Y |
P |
|
|
|
|
36 |
R |
Y |
Y |
Y |
P |
|
|
|
|
37 |
R |
Y |
Y |
Y |
P |
|
|
|
|
38 |
R |
Y |
Y |
Y |
P |
|
|
|
|
39 |
R |
Y |
Y |
Y |
P |
|
|
|
|
40 |
R |
Y |
Y |
Y |
P |
|
|
|
|
41 |
R |
Y |
Y |
Y |
P |
|
|
|
|
42 |
R |
Y |
Y |
Y |
P |
|
|
|
|
43 |
R |
Y |
Y |
Y |
P |
|
|
|
|
44 |
R |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB - 1 |
1 |
Y |
Y |
Y |
P |
|
|
|
|
2 |
Y |
Y |
Y |
P |
|
|
|
|
3 |
Y |
Y |
Y |
P |
|
|
|
|
4 |
Y |
Y |
Y |
P |
|
|
|
|
5 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
Recessed Double T5 fluorescent light fitting |
Y |
Single 36W fluorescent light fitting |
Y |
Mercury vapour Hi-bay light fitting |
Y |
70mm Downlights |
Y |
MR16 track spot lights LED |
Y |
Halogen recessed spot light |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
Sal LED Linkable |
Storage Room |
1 |
Failed to illuminate |
Y |
N |
N |
|
Sal LED Batten |
Male Toilets |
1 |
Failed to illuminate |
Y |
N |
N |
|
36W Lamp |
Storeroom |
1 |
Failed to illuminate |
Y |
N |
N |
|
LED Driver |
Fisher and Paykel Display light |
1 |
Faulty |
Y |
N |
N |
|
Display Power |
AEG Dishwashers Display lights |
1 |
No power |
Y |
N |
N |
Installed PB4 and IC cable |
Flood Light |
Car Park |
1 |
Failed to illuminate |
Y |
N |
N |
Requires all terrain scissor lift. Added to fortnightly repairs list |
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 21/05/2025 |
---|
| |
---|
| |