Partner Name | Built Services |
---|
State | TAS |
---|
Date of Visit | 07/11/2024 |
---|
Technician's Name | Shae Burnett |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 50F0027/0032 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in TAS | moonah |
---|
|
|
---|
Location Name | Moonah |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
MSB |
1 |
Y |
N/A |
N/A |
P |
|
|
MSB |
2 |
Y |
N/A |
N/A |
P |
|
|
MSB |
3 |
Y |
N/A |
N/A |
P |
|
|
MSB |
4 |
Y |
N/A |
N/A |
P |
|
|
MSB |
5 |
Y |
N/A |
N/A |
P |
|
|
MSB |
6 |
Y |
N/A |
N/A |
P |
|
|
MSB |
7 |
Y |
N/A |
N/A |
P |
|
|
MSB |
8 |
Y |
N/A |
N/A |
P |
|
|
MSB |
9 |
Y |
24.8 |
15.5 |
P |
|
|
MSB |
10 |
Y |
24.4 |
15.7 |
P |
|
|
MSB |
11 |
Y |
N/A |
N/A |
P |
|
|
MSB |
12 |
Y |
N/A |
N/A |
P |
|
|
MSB |
13 |
Y |
N/A |
N/A |
P |
|
|
MSB |
14 |
Y |
24.6 |
24.6 |
P |
|
|
MSB |
15 |
Y |
28 |
18 |
P |
|
|
MSB |
16 |
Y |
24.5 |
24.2 |
P |
|
|
MSB |
17 |
Y |
N/A |
N/A |
P |
|
|
MSB |
18 |
Y |
N/A |
N/A |
P |
|
|
MSB |
19 |
Y |
N/A |
N/A |
P |
|
|
MSB |
20 |
Y |
N/A |
N/A |
P |
|
|
MSB |
21 |
Y |
N/A |
N/A |
P |
|
|
MSB |
22 |
Y |
N/A |
N/A |
P |
|
|
MSB |
23 |
Y |
N/A |
N/A |
P |
|
|
MSB |
24 |
Y |
N/A |
N/A |
P |
|
|
MSB |
25 |
Y |
24.6 |
24.6 |
P |
|
|
MSB |
26 |
Y |
24.8 |
24.8 |
P |
|
|
MSB |
27 |
Y |
24.8 |
24.8 |
P |
|
|
MSB |
28 |
Y |
23.7 |
23.7 |
P |
|
|
MSB |
29 |
Y |
24.4 |
24.4 |
P |
|
|
MSB |
30 |
Y |
N/A |
N/A |
P |
|
|
MSB |
31 |
Y |
N/A |
N/A |
P |
|
|
MSB |
32 |
Y |
N/A |
N/A |
P |
|
|
MSB |
33 |
Y |
N/A |
N/A |
P |
|
|
MSB |
34 |
Y |
28.8 |
18.2 |
P |
|
|
MSB |
35 |
Y |
28.4 |
17.5 |
P |
|
|
MSB |
36 |
Y |
28.4 |
18.4 |
P |
|
|
MSB |
37 |
Y |
N/A |
N/A |
P |
|
|
MSB |
38 |
Y |
N/A |
N/A |
P |
|
|
MSB |
39 |
Y |
N/A |
N/A |
P |
|
|
MSB |
40 |
Y |
23.9 |
23.9 |
P |
|
|
MSB |
41 |
Y |
23.5 |
14.2 |
P |
|
|
MSB |
42 |
Y |
28.4 |
28.4 |
P |
|
|
MSB |
43 |
Y |
28.4 |
18.4 |
P |
|
|
MSB |
44 |
Y |
N/A |
N/A |
P |
|
|
MSB |
45 |
Y |
28.8 |
18.9 |
P |
|
|
MSB |
46 |
Y |
28.4 |
18.0 |
P |
|
|
MSB |
47 |
Y |
28.6 |
18.6 |
P |
|
|
MSB |
48 |
Y |
28.6 |
18.6 |
P |
|
|
SB |
1 |
Y |
N/A |
N/A |
P |
|
|
SB |
2 |
Y |
N/A |
N/A |
P |
|
|
SB |
3 |
Y |
N/A |
N/A |
P |
|
|
SB |
4 |
Y |
N/A |
N/A |
P |
|
|
SB |
5 |
Y |
N/A |
N/A |
P |
|
|
SB |
6 |
Y |
N/A |
N/A |
P |
|
|
SB |
7 |
Y |
N/A |
N/A |
P |
|
|
SB |
8 |
Y |
N/A |
N/A |
P |
|
|
SB |
9 |
Y |
N/A |
N/A |
P |
|
|
SB |
10 |
Y |
N/A |
N/A |
P |
|
|
SB |
11 |
Y |
N/A |
N/A |
P |
|
|
SB |
12 |
Y |
N/A |
N/A |
P |
|
|
SB |
13 |
Y |
N/A |
N/A |
P |
|
|
SB |
14 |
Y |
N/A |
N/A |
P |
|
|
SB |
15 |
Y |
N/A |
N/A |
P |
|
|
SB |
16 |
Y |
N/A |
N/A |
P |
|
|
SB |
17 |
Y |
N/A |
N/A |
P |
|
|
SB |
18 |
Y |
23.3 |
20.8 |
P |
|
|
SB |
19 |
Y |
23.3 |
23.3 |
P |
|
|
SB |
20 |
Y |
N/A |
N/A |
P |
|
|
SB |
21 |
Y |
29.2 |
19.1 |
P |
|
|
SB |
22 |
Y |
28.4 |
18.6 |
P |
|
|
SB |
23 |
Y |
23.7 |
15.7 |
P |
|
|
SB |
24 |
Y |
28.6 |
28.6 |
P |
|
|
SB |
25 |
Y |
24.4 |
15.5 |
P |
|
|
SB |
26 |
Y |
31.4 |
21.6 |
P |
|
|
SB |
27 |
Y |
28.6 |
15.0 |
P |
|
|
SB |
28 |
Y |
N/A |
N/A |
P |
|
|
SB |
29 |
Y |
23.9 |
15.9 |
P |
|
|
SB |
30 |
Y |
28.6 |
18.6 |
P |
|
|
SB |
31 |
Y |
N/A |
N/A |
P |
|
|
SB |
32 |
Y |
28.6 |
14.8 |
P |
|
|
SB |
33 |
Y |
23.3 |
14.8 |
P |
|
|
SB |
34 |
Y |
23.9 |
14.6 |
P |
|
|
SB |
36 |
Y |
N/A |
N/A |
P |
|
|
SB |
37 |
Y |
N/A |
N/A |
P |
|
|
SB |
38 |
Y |
N/A |
N/A |
P |
|
|
SB |
44 |
Y |
23.9 |
13.9 |
P |
|
|
SB |
45 |
Y |
24.4 |
14.4 |
P |
|
|
SB |
46 |
Y |
24.6 |
15.3 |
P |
|
|
SB |
47 |
Y |
29.0 |
18.9 |
P |
|
|
SB |
48 |
Y |
28.6 |
18.6 |
P |
|
|
SB |
49 |
Y |
23.9 |
15.3 |
P |
|
|
SB |
50 |
Y |
28.6 |
18.6 |
P |
|
|
SB |
51 |
Y |
28.4 |
18.6 |
P |
|
|
SB |
52 |
Y |
24.2 |
13.9 |
P |
|
|
SB |
53 |
Y |
24.2 |
14.7 |
P |
|
|
SB |
54 |
Y |
N/A |
N/A |
P |
|
|
SB |
55 |
Y |
N/A |
N/A |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
SB |
1 |
S |
Y |
Y |
Y |
P |
|
|
|
SB |
2 |
S |
Y |
Y |
Y |
P |
|
|
|
SB |
3 |
S |
Y |
Y |
Y |
P |
|
|
|
SB |
4 |
S |
Y |
Y |
Y |
P |
|
|
|
SB |
5 |
S |
Y |
Y |
Y |
P |
|
|
|
SB |
6 |
S |
Y |
Y |
Y |
P |
|
|
|
SB |
7 |
S |
Y |
Y |
Y |
P |
|
|
|
SB |
9 |
S |
Y |
Y |
Y |
P |
|
|
|
SB |
10 |
S |
Y |
Y |
Y |
P |
|
|
|
SB |
11 |
S |
Y |
Y |
Y |
P |
|
|
|
SB |
12 |
S |
Y |
Y |
Y |
P |
|
|
|
SB |
13 |
S |
Y |
Y |
Y |
P |
|
|
|
SB |
15 |
S |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
MSB |
1 |
Y |
Y |
Y |
P |
|
|
|
MSB |
2 |
Y |
Y |
Y |
P |
|
|
|
MSB |
3 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Are there any Warranty items needing to be repaired? | No |
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 07/05/2025 |
---|
| |
---|
| |