Carry out push button test and record the results below.
RCD Details (Biennial)
Distribution Board No.
Circuit No.
Push Button (YorN)
0 Degrees
180 Degrees
Pass / Fail (PorF)
Fault?
Repaired on Site (YorN)
DB-4
3
Y
13
27
P
DB-4
5
Y
33
27
P
DB-4
7
Y
34
28
P
DB-4
9
Y
24
19
P
DB-4
11
Y
34
28
P
DB-4
13
Y
34
27
P
DB-4
15
Y
24
27
P
DB-4
17
Y
34
31
P
DB-4
21
Y
23
28
P
DB-4
2
Y
23
18
P
DB-4
4
Y
34
18
P
DB-4
6
Y
34
29
P
DB-4
8
Y
31
29
P
DB-4
10
Y
34
18
P
DB-4
12
Y
33
18
P
DB-4
14
Y
24
32
P
DB-4
16
Y
34
21
P
DB-1
11
Y
26
32
P
DB-1
13
Y
27
18
P
DB-1
15
Y
29
29
P
DB-1
17
Y
38
32
P
DB-1
47
Y
23
32
P
DB-1
28
Y
24
31
P
DB-1
30
Y
21
26
P
DB-1
32
Y
82
28
P
DB-1
34
Y
28
38
P
DB-1
36
Y
24
29
P
DB-1
38
Y
14
18
P
DB-3
1
Y
26
33
P
DB-3
3
Y
24
25
P
DB-3
5
Y
24
24
P
DB-3
7
Y
29
31
P
DB-3
9
Y
24
32
P
DB-3
2
Y
26
19
P
DB-3
4
Y
25
33
P
DB-3
6
Y
28
29
P
DB-3
8
Y
27
16
P
DB-3
10
Y
24
21
P
DB-3
12
Y
TRIPPING
TRIPPING
F
Failed Test
Y
DB-2
1
Y
25
36
P
DB-2
3
Y
38
28
P
DB-2
5
Y
38
28
P
DB-2
7
Y
25
19
P
DB-2
9
Y
30
17
P
DB-2
11
Y
29
17
P
DB-2
13
Y
29
29
P
DB-2
2
Y
25
31
P
DB-2
4
Y
33
31
P
DB-2
6
Y
24
31
P
DB-2
8
Y
26
18
P
THERMOGRAPHIC TEST RESULTS
THERMOGRAPHIC TEST RESULTS
SF43 Exit/Emergency
SF43 EXIT/EMERGENCY LIGHTING
Timers
Check timers for correct operation and timing
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
HTML Block
HTML Block
SF44 General Lighting & Works
SF44 GENERAL LIGHTING & WORKS
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
HTML Block
General Operation/Additional items
Check with Store Manager to ensure there are no other issues
Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au
Yes
Are there any Warranty items needing to be repaired?
No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
LED Hibay
Fridges
1
Not working
Y
N
N
RCBO No.12
Switchboard
1
Tripping
Y
N
N
Has been disconnected as unable to access (restricted access) Manager has advised that all is still working as normal and if an issue arises - to submit a service request.
EX/EM Lighting
Circuit Breaker
1
Warning Label
N
N
Y
To be placed on site at next visit.
Site Status Selector
Store now fully compliant
Next Test Due in 6 months
09/05/2025
The Built Services Group seeks to apply innovation and technology for greater client services, business efficiencies and thinking Green.