Partner NameBuilt Services
StateNSW
Date of Visit11/11/2024
Technician's NameJed Staude
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number50F0015/0462
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWballina

Location NameBallina
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB-4 3 Y 13 27 P
DB-4 5 Y 33 27 P
DB-4 7 Y 34 28 P
DB-4 9 Y 24 19 P
DB-4 11 Y 34 28 P
DB-4 13 Y 34 27 P
DB-4 15 Y 24 27 P
DB-4 17 Y 34 31 P
DB-4 21 Y 23 28 P
DB-4 2 Y 23 18 P
DB-4 4 Y 34 18 P
DB-4 6 Y 34 29 P
DB-4 8 Y 31 29 P
DB-4 10 Y 34 18 P
DB-4 12 Y 33 18 P
DB-4 14 Y 24 32 P
DB-4 16 Y 34 21 P
DB-1 11 Y 26 32 P
DB-1 13 Y 27 18 P
DB-1 15 Y 29 29 P
DB-1 17 Y 38 32 P
DB-1 47 Y 23 32 P
DB-1 28 Y 24 31 P
DB-1 30 Y 21 26 P
DB-1 32 Y 82 28 P
DB-1 34 Y 28 38 P
DB-1 36 Y 24 29 P
DB-1 38 Y 14 18 P
DB-3 1 Y 26 33 P
DB-3 3 Y 24 25 P
DB-3 5 Y 24 24 P
DB-3 7 Y 29 31 P
DB-3 9 Y 24 32 P
DB-3 2 Y 26 19 P
DB-3 4 Y 25 33 P
DB-3 6 Y 28 29 P
DB-3 8 Y 27 16 P
DB-3 10 Y 24 21 P
DB-3 12 Y TRIPPING TRIPPING F Failed Test Y
DB-2 1 Y 25 36 P
DB-2 3 Y 38 28 P
DB-2 5 Y 38 28 P
DB-2 7 Y 25 19 P
DB-2 9 Y 30 17 P
DB-2 11 Y 29 17 P
DB-2 13 Y 29 29 P
DB-2 2 Y 25 31 P
DB-2 4 Y 33 31 P
DB-2 6 Y 24 31 P
DB-2 8 Y 26 18 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
HTML Block
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
LED Hibay Fridges 1 Not working Y N N
RCBO No.12 Switchboard 1 Tripping Y N N Has been disconnected as unable to access (restricted access) Manager has advised that all is still working as normal and if an issue arises - to submit a service request.
EX/EM Lighting Circuit Breaker 1 Warning Label N N Y To be placed on site at next visit.
Site Status SelectorStore now fully compliant
Next Test Due in 6 months09/05/2025