State | QLD |
---|
Date of Visit | 31/03/2025 |
---|
Technician's Name | Antonio Cavaliere (168680) |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 50F0019/0390 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in QLD | cairns |
---|
|
|
---|
Location Name | Cairns |
---|
| |
---|
HTML Block |
|
---|
Test Period | 6 Monthly (90 minutes) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
RCD Details (6 Month) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
DB1 |
1 |
Y |
P |
|
|
DB1 |
2 |
Y |
P |
|
|
DB1 |
3 |
Y |
P |
|
|
DB1 |
4 |
Y |
P |
|
|
DB1 |
5 |
Y |
P |
|
|
DB1 |
6 |
Y |
P |
|
|
DB1 |
7 |
Y |
P |
|
|
DB1 |
14 |
Y |
P |
|
|
DB1 |
15 |
Y |
P |
|
|
DB1 |
16 |
Y |
P |
|
|
DB1 |
17 |
Y |
P |
|
|
DB1 |
18 |
Y |
P |
|
|
DB1 |
22 |
Y |
P |
|
|
DB1 |
23 |
Y |
P |
|
|
DB1 |
24 |
Y |
P |
|
|
DB1 |
25 |
Y |
P |
|
|
DB1 |
26 |
Y |
P |
|
|
DB1 |
27 |
Y |
P |
|
|
DB1 |
28 |
Y |
P |
|
|
DB1 |
34 |
Y |
P |
|
|
DB1 |
35 |
Y |
P |
|
|
DB1 |
58 |
Y |
P |
|
|
DB1 |
59 |
Y |
P |
|
|
DB1 |
63 |
Y |
P |
|
|
DB1 |
64 |
Y |
P |
|
|
DB1 |
65 |
Y |
P |
|
|
DB1 |
69 |
Y |
P |
|
|
DB - SR2 |
11 |
Y |
P |
|
|
DB - SR2 |
13 |
Y |
P |
|
|
DB - SR2 |
15 |
Y |
P |
|
|
DB - SR2 |
17 |
Y |
P |
|
|
DB - SR2 |
19 |
Y |
P |
|
|
DB - SR2 |
2 |
Y |
P |
|
|
DB - SR2 |
4 |
Y |
P |
|
|
DB - SR2 |
6 |
Y |
P |
|
|
DB - SR2 |
8 |
Y |
P |
|
|
DB - SR2 |
10 |
Y |
P |
|
|
DB - SR2 |
12 |
Y |
P |
|
|
DB - SR2 |
14 |
Y |
P |
|
|
DB - SR2 |
20 |
Y |
P |
|
|
DBX |
1 |
Y |
P |
|
|
DBX |
3 |
Y |
P |
|
|
DBX |
5 |
Y |
P |
|
|
DBX |
7 |
Y |
P |
|
|
DBX |
11 |
Y |
P |
|
|
DBX |
13 |
Y |
P |
|
|
DBX |
15 |
Y |
P |
|
|
DBX |
17 |
Y |
P |
|
|
DBX |
19 |
Y |
P |
|
|
DBX |
21 |
Y |
P |
|
|
DBX |
23 |
Y |
P |
|
|
DBX |
25 |
Y |
P |
|
|
DBX |
27 |
Y |
P |
|
|
DBX |
29 |
Y |
P |
|
|
DBX |
31 |
Y |
P |
|
|
DBX |
33 |
Y |
P |
|
|
DBX |
35 |
Y |
P |
|
|
DBX |
2 |
Y |
P |
|
|
DBX |
4 |
Y |
P |
|
|
DBX |
6 |
Y |
P |
|
|
DBX |
8 |
Y |
P |
|
|
DBX |
10 |
Y |
P |
|
|
DBX |
12 |
Y |
P |
|
|
DBX |
14 |
Y |
P |
|
|
DBX |
16 |
Y |
P |
|
|
DBX |
18 |
Y |
P |
|
|
DBX |
20 |
Y |
P |
|
|
DBX |
22 |
Y |
P |
|
|
DBX |
24 |
Y |
P |
|
|
DBX |
26 |
Y |
P |
|
|
DBX |
28 |
Y |
P |
|
|
DBX |
30 |
Y |
P |
|
|
DBX |
32 |
Y |
P |
|
|
DBX |
34 |
Y |
P |
|
|
DBX2 |
1 |
Y |
P |
|
|
DBX2 |
2 |
Y |
P |
|
|
DBX2 |
3 |
Y |
P |
|
|
DBX2 |
4 |
Y |
P |
|
|
DBX2 |
5 |
Y |
P |
|
|
DBX2 |
6 |
Y |
P |
|
|
DBX2 |
7 |
Y |
P |
|
|
DBX2 |
8 |
Y |
P |
|
|
DBX2 |
9 |
Y |
P |
|
|
DBX2 |
10 |
Y |
P |
|
|
DBX2 |
11 |
Y |
P |
|
|
DBX2 |
12 |
Y |
P |
|
|
DBX2 |
13 |
Y |
P |
|
|
DBX2 |
14 |
Y |
P |
|
|
DBX2 |
15 |
Y |
P |
|
|
DBX2 |
16 |
Y |
P |
|
|
DBX2 |
17 |
Y |
P |
|
|
DBX2 |
18 |
Y |
P |
|
|
DBX2 |
19 |
Y |
P |
|
|
DBX2 |
20 |
Y |
P |
|
|
DBX2 |
21 |
Y |
P |
|
|
DBX2 |
22 |
Y |
P |
|
|
DBX2 |
23 |
Y |
P |
|
|
DBX2 |
24 |
Y |
P |
|
|
DB5 |
4 |
Y |
P |
|
|
DB5 |
5 |
Y |
P |
|
|
DB5 |
6 |
Y |
P |
|
|
DB5 |
7 |
Y |
P |
|
|
DB5 |
8 |
Y |
P |
|
|
DB5 |
13 |
Y |
P |
|
|
DB5 |
14 |
Y |
P |
|
|
DB5 |
15 |
Y |
P |
|
|
DB5 |
16 |
Y |
P |
|
|
DB5 |
17 |
Y |
P |
|
|
DB5 |
18 |
Y |
P |
|
|
DB5 |
19 |
Y |
P |
|
|
DB5 |
20 |
Y |
P |
|
|
DB5 |
21 |
Y |
P |
|
|
DB5 |
22 |
Y |
P |
|
|
DB5 |
23 |
Y |
P |
|
|
DB5 |
24 |
Y |
P |
|
|
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB1 |
0 |
R |
N |
N |
N |
F |
Battery |
Y |
N |
|
1 |
R |
Y |
Y |
Y |
P |
|
|
|
|
2 |
R |
Y |
Y |
Y |
P |
|
|
|
|
3 |
R |
Y |
Y |
Y |
P |
|
|
|
|
4 |
R |
Y |
Y |
Y |
P |
|
|
|
|
5 |
R |
Y |
Y |
Y |
P |
|
|
|
|
6 |
R |
Y |
Y |
Y |
P |
|
|
|
|
7 |
R |
Y |
Y |
Y |
P |
|
|
|
|
8 |
R |
Y |
Y |
Y |
P |
|
|
|
|
9 |
R |
Y |
Y |
Y |
P |
|
|
|
|
10 |
R |
Y |
Y |
Y |
P |
|
|
|
|
11 |
R |
Y |
Y |
Y |
P |
|
|
|
|
12 |
R |
Y |
Y |
Y |
P |
|
|
|
|
13 |
R |
Y |
Y |
Y |
P |
|
|
|
|
14 |
R |
Y |
Y |
Y |
P |
|
|
|
|
15 |
R |
Y |
Y |
Y |
P |
|
|
|
|
16 |
R |
Y |
Y |
Y |
P |
|
|
|
|
17 |
R |
Y |
Y |
Y |
P |
|
|
|
|
18 |
R |
Y |
Y |
Y |
P |
|
|
|
|
19 |
R |
Y |
Y |
Y |
P |
|
|
|
|
20 |
R |
Y |
Y |
Y |
P |
|
|
|
|
21 |
R |
Y |
Y |
Y |
P |
|
|
|
|
22 |
R |
Y |
Y |
Y |
P |
|
|
|
|
23 |
R |
Y |
Y |
Y |
P |
|
|
|
|
24 |
R |
Y |
Y |
Y |
P |
|
|
|
|
25 |
S |
Y |
Y |
Y |
P |
|
|
|
|
26 |
S |
Y |
Y |
Y |
P |
|
|
|
|
27 |
S |
Y |
Y |
Y |
P |
|
|
|
|
28 |
S |
Y |
Y |
Y |
P |
|
|
|
|
29 |
S |
Y |
Y |
Y |
P |
|
|
|
|
30 |
S |
Y |
Y |
Y |
P |
|
|
|
|
31 |
R |
Y |
Y |
Y |
P |
|
|
|
|
32 |
R |
Y |
Y |
Y |
P |
|
|
|
|
33 |
R |
Y |
Y |
Y |
P |
|
|
|
|
34 |
R |
Y |
Y |
Y |
P |
|
|
|
|
35 |
R |
Y |
Y |
Y |
P |
|
|
|
|
36 |
R |
Y |
Y |
Y |
P |
|
|
|
|
37 |
R |
Y |
Y |
Y |
P |
|
|
|
|
38 |
R |
Y |
Y |
Y |
P |
|
|
|
|
39 |
R |
Y |
Y |
Y |
P |
|
|
|
|
60 |
R |
Y |
Y |
Y |
P |
|
|
|
|
61 |
R |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB1 |
40 |
Y |
Y |
Y |
P |
|
|
|
|
41 |
Y |
Y |
Y |
P |
|
|
|
|
42 |
Y |
Y |
Y |
P |
|
|
|
|
43 |
Y |
Y |
Y |
P |
|
|
|
|
44 |
Y |
Y |
Y |
P |
|
|
|
|
45 |
Y |
Y |
Y |
P |
|
|
|
|
46 |
Y |
Y |
Y |
P |
|
|
|
|
47 |
Y |
Y |
Y |
P |
|
|
|
|
48 |
Y |
Y |
Y |
P |
|
|
|
|
49 |
Y |
Y |
Y |
P |
|
|
|
|
50 |
Y |
Y |
Y |
P |
|
|
|
|
51 |
Y |
Y |
Y |
P |
|
|
|
|
52 |
Y |
Y |
Y |
P |
|
|
|
|
53 |
Y |
Y |
Y |
P |
|
|
|
|
54 |
Y |
Y |
Y |
P |
|
|
|
|
55 |
Y |
Y |
Y |
P |
|
|
|
|
56 |
Y |
Y |
Y |
P |
|
|
|
|
57 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
Double 2ft Fluro |
Y |
Downlights LED & Diachronic |
Y |
Downlights - Small Display |
Y |
Panel Lights - LED |
Y |
Square Lights (Showroom Trading Lights) |
Y |
4FT Fluro |
Y |
LED Strip Lighting - Displays CFL's |
Y |
Hi-bay Lights |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
External Lights |
Walkway Outside |
1 |
Not Illuminating |
N |
N |
N |
Quote Recommendation Added To Fortnightly Repairs List |
External Lights |
Walkway Outside |
1 |
Not Illuminating |
N |
N |
N |
Quote Recommendation Added To Fortnightly Repairs List |
External Lights |
Walkway Outside |
1 |
Not Illuminating |
N |
N |
N |
Quote Recommendation Added To Fortnightly Repairs List |
External Lights |
Above Pad Mount Transformer (Side of Building) |
1 |
Not Illuminating |
N |
N |
N |
Quote Recommendation Added To Fortnightly Repairs List |
External Lights |
Above Pad Mount Transformer (Side of Building) |
1 |
Not Illuminating |
N |
N |
N |
Quote Recommendation Added To Fortnightly Repairs List |
External Lights |
Above Pad Mount Transformer (Side of Building) |
1 |
Not Illuminating |
N |
N |
N |
Quote Recommendation Added To Fortnightly Repairs List |
External Lights |
Back Carpark |
1 |
Not Illuminating |
N |
N |
N |
Quote Recommendation Added To Fortnightly Repairs List |
Recessed Emergency Light |
0 |
1 |
Battery |
Y |
N |
N |
|
LED Hi-bay |
Warehouse |
1 |
Not Illuminating |
Y |
N |
N |
Installed Temporary Light Under WO 2734050, Replaced With Proper Fitting Under Audit |
|
---|
Site Status Selector | QLD - Maintenance has been completed in accordance to ASS2293.2 and QDC MP6.1. - Store now fully compliant |
---|