Partner NameBuilt Services
StateVIC
Date of Visit12/03/2025
Technician's NameZac Forbes
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number50F0017/0444
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICmildura

Location NameMildura
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB 2 1 Y P
12 Y P
3 Y P
14 Y P
5 Y P
16 Y P
7 Y P
18 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
DB 1 14 Y P
DB 2 15 Y P
DB 1 16 Y P
DB2 17 Y P
DB 1 18 Y P
DB 2 19 Y P
DB 1 20 Y P
22 Y P
23 Y P
24 Y F Y Has since been replaced by a different technician / company
25 Y P
DB 2 26 Y P
DB 1 26 Y P
27 Y P
28 Y P
29 Y P
30 Y P
31 Y P
32 Y P
33 Y P
34 Y P
35 Y P
36 Y P
37 Y P
38 Y P
39 Y P
40 Y P
41 Y P
42 Y P
43 Y P
44 Y P
45 Y P
46 Y P
47 Y P
48 Y P
49 Y P
50 Y P
51 Y P
52 Y P
53 Y P
54 Y P
55 Y P
56 Y P
57 Y P
58 Y P
59 Y P
60 Y P
61 Y P
62 Y P
63 Y P
64 Y P
65 Y P
66 Y P
67 Y P
68 Y P
69 Y P
70 Y P
71 Y P
72 Y P
73 Y P
74 Y P
75 Y P
76 Y P
77 Y P
78 Y P
80 Y P
82 Y P
84 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 1 1 S Y Y Y P
2 S Y Y Y P
3 S Y Y Y P
4 S Y Y Y P
5 S Y Y Y P
6 S Y Y Y P
7 S N N N Y Failed 90minute Test Y Y
8 S Y Y Y P
9 S Y Y Y P
10 S Y N N Y Failed 90minute Test Y Y
11 S Y Y Y P
12 S N N Y Y Failed 90minute Test Y Y
13 S N N Y Y Failed 90minute Test Y Y
14 S N N Y Y Failed 90minute Test Y N
15 S N N Y Y Failed 90minute Test Y Y
16 S N N Y Y Failed 90minute Test Y N
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 2 1 Y Y Y P
2 Y Y Y P
3 Y Y Y P
4 Y Y Y P
5 N N N F Failed 90minute Test Y Y
6 Y Y Y P
7 Y Y Y P
8 Y Y Y P
9 Y Y Y P
10 Y Y Y P
11 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
HiBay 400w Y
2 x 36w Emergency Battens Y
75w Mercury Vapour Downlights (250mm) Y
Exit Light Legrand 32m Y
Exit Light Legrand 24m Y
Exit Light Legrand FS24m Y
Compact Fluorescent Downlights 18w Y
Are there any Warranty items needing to be repaired?Yes
WARRANTY
Defect Item Location of Item (on premises) Quantity Details of fault/problem Manufacturer Part Number Repaired on Site Comments
Jumbo Exit Light #5 1 Failed 90minute Test Clevertronics STU LJELED-40 Y
Surface Mount Emergency Batten #7 1 Failed 90minute Test Stellar V - Y
Surface Mount Emergency Batten #10 1 Failed 90minute Test Stellar V - Y
Surface Mount Emergency Batten #12 1 Failed 90minute Test Stellar V - Y
Surface Mount Emergency Batten #13 1 Failed 90minute Test Stellar V - Y
Surface Mount Emergency Batten #15 1 Failed 90minute Test Stellar V - Y
Geotag photo(s)
  • Have you sent the Geotag photo(s) to maintenance@sturdie.com.au, referring to the Store Location in the email, e.g. Canberra City?
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
RCD #24 DB 1 1 Failed push button test Y N N Has been replaced by a different technician / company
Surface Mount Emergency Light #14 1 Failed 90minute Test Y N N Scissor Lift was required
Surface Mount Emergency Light #16 1 Failed 90minute Test Y N N Scissor Lift was required
Site Status SelectorStore now fully compliant
Next Test Due in 6 months12/09/2025