Carry out push button test and record the results below.
THERMOGRAPHIC TEST RESULTS
THERMOGRAPHIC TEST RESULTS
RCD Details (6 Month)
Distribution Board No.
Circuit No.
Push Button (YorN)
Pass / Fail (PorF)
Fault?
Repaired on Site (YorN)
DB1
15
Y
P
16
Y
P
17
Y
P
18
Y
P
19
Y
P
20
Y
P
21
Y
P
22
Y
P
23
Y
P
24
Y
P
25
Y
P
26
Y
P
27
Y
P
28
Y
P
29
Y
P
30
Y
P
31
Y
P
32
Y
P
34
Y
P
36
Y
P
44
Y
P
45
Y
P
46
Y
P
48
Y
P
TDB.1
12
Y
P
13
Y
P
14
Y
P
18
Y
P
19
Y
P
20
Y
P
21
Y
P
MSB-24
13
Y
P
16
Y
P
19
Y
P
20
Y
P
21
Y
P
22
Y
P
23
Y
P
24
Y
P
25
Y
P
26
Y
P
27
Y
P
28
Y
P
29
Y
P
30
Y
P
31
Y
P
32
Y
P
33
Y
P
34
Y
P
35
Y
P
36
Y
P
44
Y
P
46
Y
P
48
Y
P
49
Y
P
51
Y
P
52
Y
P
53
Y
P
54
Y
P
55
Y
P
56
Y
P
57
Y
P
58
Y
P
59
Y
P
60
Y
P
61
Y
P
62
Y
P
63
Y
P
64
Y
P
65
Y
P
66
Y
P
67
Y
P
68
Y
P
69
Y
P
70
Y
P
71
Y
P
72
Y
P
73
Y
P
74
Y
P
75
Y
P
76
Y
P
77
Y
P
78
Y
P
79
Y
P
80
Y
P
SF43 Exit/Emergency
SF43 EXIT/EMERGENCY LIGHTING
Timers
Check timers for correct operation and timing
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No.
ID No.
Surface mounted or recessed? (SorR)
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
MSB-24
1
S
Y
Y
Y
P
2
S
Y
Y
Y
P
3
S
Y
Y
Y
P
4
S
Y
Y
Y
P
5
S
Y
Y
Y
P
6
S
N
N
N
F
Partially illuminated
N
N
7
S
Y
Y
Y
P
8
S
Y
Y
Y
P
9
S
Y
Y
Y
P
10
S
Y
Y
Y
P
11
S
Y
Y
Y
P
12
S
Y
Y
Y
P
DB1
13
S
N
N
N
F
Failed 90 min discharge test
N
N
14
R
Y
Y
Y
P
15
R
Y
Y
Y
P
TDB.1
16
R
Y
Y
Y
P
17
R
Y
Y
Y
P
18
R
Y
Y
Y
P
19
R
Y
Y
Y
P
20
R
Y
Y
Y
P
21
R
Y
Y
Y
P
22
R
Y
Y
Y
P
HTML Block
EXIT LIGHTS
Distribution Board No.
ID No.
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
MSB-24
1
Y
Y
Y
P
2
Y
Y
Y
P
3
Y
Y
Y
P
4
Y
Y
Y
P
5
Y
Y
Y
P
6
Y
Y
Y
P
7
Y
Y
Y
P
DB1
8
Y
Y
Y
P
MSB-24
9
Y
Y
Y
P
10
Y
Y
Y
P
11
Y
Y
Y
P
12
Y
Y
Y
P
TDB.1
13
Y
Y
Y
P
14
Y
Y
Y
P
SF44 General Lighting & Works
SF44 GENERAL LIGHTING & WORKS
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
HTML Block
General Operation/Additional items
Check with Store Manager to ensure there are no other issues
Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au
Yes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten)
Existing (YorN)
400W Hi-Bay Mercury Vapour Fitting
Y
4FT 36W Fluorescent Fittings
Y
Single Batten Fluorescent Emergency 36W Fitting
Y
Double Batten Fluorescent Emergency 36W Fitting
Y
70mm Downlights
Y
Single Bare Batten 36W Fluorescent Fitting
Y
200W Hi-Bay Mercury Vapour Fitting
Y
Single Batten 36W Fluorescent Diffuser
Y
90mm LED Downlights
Y
Wall washer
Y
Are there any Warranty items needing to be repaired?
Yes
WARRANTY
Defect Item
Location of Item (on premises)
Quantity
Details of fault/problem
Manufacturer
Part Number
Repaired on Site
Comments
Wall washer spotlight
Hoover, perfect temperature, Samsung washers, Bosch washers, laundry accessories, asko ovens, Westinghouse ovens, hair ovens, tv wall brackets
10
Flickering/ failed to illuminate
N/a
N/a
N
Scissor lift is required to reach fitting. Return with scissor to remove fittings and get info. Fittings are then to be brought back to sturdie office for warranty process
Geotag photo(s)
Have you sent the Geotag photo(s) to maintenance@sturdie.com.au, referring to the Store Location in the email, e.g. Canberra City?
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
Emg #6
Freestanding cooktops
1
Partially illuminated
N
Y
Y
Return with long narrow scissor and 1 x surface emergency light and replace. Fitting is 6.3m off floor
Emg #13
Tv
1
Failed 90 min discharge test
N
Y
Y
Return with long narrow scissor and 1 x surface emergency light and replace. Fitting is 6.3m off floor
72mm downlight
Tv
4
Failed to illuminate
Y
N
N
Replaced
Test & tag
Store
60+
Tested 10.02.25 due 10.02.26
-
-
-
-
Next Test Due in 6 months
23/12/2025