StateTAS
Date of Visit28/05/2025
Technician's NameNathan Gilbert
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number50F0027/0036
EmailEmail hidden; Javascript is required.
The Good Guys Site in TASmoonah

Location NameMoonah
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
MSB Chassis 1 L&P 1 Y P
2 Y P
3 Y P
4 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
21 Y P
22 Y P
23 N F Tripping N
24 N F Tripping N
25 Y P
26 Y P
27 Y P
28 Y P
29 Y P
30 Y P
31 Y P
32 Y P
33 Y P
34 Y P
35 Y P
36 Y P
37 Y P
38 Y P
39 N F Tripping N
40 Y P
41 Y P
42 Y P
43 Y P
44 Y P
45 Y P
46 Y P
47 Y P
48 Y P
MSB Chassis 2 2 N F Tripping N
5 Y P
29 Y P
SB1 1 Y P
2 Y P
3 Y P
4 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
21 Y P
22 Y P
23 Y P
24 Y P
25 Y P
26 Y P
27 Y P
28 Y P
29 Y P
30 Y P
31 Y P
32 Y P
33 Y P
35 Y P
36 Y P
37 Y P
38 Y P
41 N F Tripping N
43 N F Tripping N
45 Y P
46 Y P
47 Y P
48 Y P
49 Y P
50 Y P
51 Y P
52 Y P
53 Y P
54 Y P
55 Y P
72 N F Tripping N
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
SB1 1 S Y Y Y P
2 S Y Y Y P
3 S Y Y Y P
4 S Y Y Y P
5 S Y Y Y P
6 S Y Y Y P
7 R Y Y Y P
MSB 8 R Y Y Y P
9 R Y Y Y P
10 R Y Y Y P
11 R Y Y Y P
12 R Y Y Y P
13 R Y Y Y P
14 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
SB1 1 Y Y Y P
MSB 14 N N N F Damaged Y N
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
2 x 36W Bare Batten Y
Diffused Hi Bays Y
2 x 36W Diffused Batten Y
1 x 36W Diffused Batten Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
CB23 MSB1 1 Tripping - Too Much Power On Circuit N N N Quote #4897 submitted to H/O under job #2825699
CB24 MSB1 1 Tripping - Too Much Power On Circuit N N N Quote #4897 submitted to H/O under job #2825699
CB39 MSB1 1 Tripping - Too Much Power On Circuit N N N Quote #4897 submitted to H/O under job #2825699
CB2 MSB2 1 Tripping - Too Much Power On Circuit N N N Quote #4897 submitted to H/O under job #2825699
CB41 SB1 1 Tripping - Too Much Power On Circuit N N N Quote #4897 submitted to H/O under job #2825699
CB43 SB1 1 Tripping - Too Much Power On Circuit N N N Quote #4897 submitted to H/O under job #2825699
CB72 SB1 1 Tripping - Too Much Power On Circuit N N N Quote #4897 submitted to H/O under job #2825699
Exit Light 14 1 Damaged Y N N
Site Status SelectorStore now fully compliant
Next Test Due in 6 months28/11/2025