| State | WA |
|---|
| Date of Visit | 24/06/2025 |
|---|
| Technician's Name | Connor Stevens |
|---|
| Which Company are you working for? | Sturdie Trade Services |
|---|
| Sturdie Job Number | 50F0023/0246 |
|---|
| Email | Email hidden; Javascript is required. |
|---|
| The Good Guys Site in WA | o'connor_warehouse |
|---|
|
|
|---|
| Location Name | O'Connor Warehouse |
|---|
| |
|---|
| HTML Block |
|
|---|
| Test Period | 6 Monthly (90 minutes) |
|---|
| Push Button Test | - Carry out push button test for correct operation
|
|---|
| Carry out push button test for correct operation | |
|---|
| HTML Block |
|
|---|
| Carry out test with RCD Tester | Carry out push button test and record the results below. |
|---|
| THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
|---|
| RCD Details (6 Month) | | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
| DB 01 |
R1 |
Y |
P |
|
|
|
W1 |
Y |
P |
|
|
|
B1 |
Y |
P |
|
|
|
R2 |
Y |
P |
|
|
|
W2 |
Y |
P |
|
|
|
B2 |
Y |
P |
|
|
|
R3 |
Y |
P |
|
|
|
W3 |
Y |
P |
|
|
|
CB19 |
Y |
P |
|
|
|
|---|
| SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
|---|
| Timers | - Check timers for correct operation and timing
|
|---|
| Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
|---|
| HTML Block |
|
|---|
| EMERGENCY LIGHTS | | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| DB 01 |
12 |
S - Twin Tube Emergency Batten |
N |
N |
N |
F |
Failed 90min Test |
Y |
N |
|
13 |
S |
Y |
Y |
Y |
P |
|
|
|
|
14 |
S |
Y |
Y |
Y |
P |
|
|
|
|
15 |
S - Twin Tube Emergency Batten |
N |
N |
N |
F |
Failed 90min Test |
Y |
N |
|
16 |
S - Twin Tube Emergency Batten |
N |
N |
N |
F |
Failed 90min Test |
Y |
N |
|
17 |
S |
Y |
Y |
Y |
P |
|
|
|
|
18 |
S |
Y |
Y |
Y |
P |
|
|
|
|
19 |
S |
Y |
Y |
Y |
P |
|
|
|
|
20 |
S - Twin Tube Emergency Batten |
N |
N |
N |
F |
Failed 90min Test |
Y |
N |
|
21 |
S |
Y |
Y |
Y |
P |
|
|
|
|
22 |
S |
Y |
Y |
Y |
P |
|
|
|
|
23 |
S |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| HTML Block |
|
|---|
| EXIT LIGHTS | | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| DB 01 |
1 |
Y |
Y |
Y |
P |
|
|
|
|
2 |
Y |
Y |
Y |
P |
|
|
|
|
3 |
Y |
Y |
Y |
P |
|
|
|
|
4 |
Y |
Y |
Y |
P |
|
|
|
|
5 |
Y |
Y |
Y |
P |
|
|
|
|
6 |
Y |
Y |
Y |
P |
|
|
|
|
7 |
N |
N |
N |
F |
Failed 90min Test |
Y |
N |
|
8 |
Y |
Y |
Y |
P |
|
|
|
|
9 |
Y |
Y |
Y |
P |
|
|
|
|
10 |
Y |
Y |
Y |
P |
|
|
|
|
11 |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
|---|
| General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
|---|
| HTML Block |
|
|---|
| General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
|---|
| HTML Block |
|
|---|
| Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
|---|
| Lighting Report | | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
| 400w Hibay |
Y |
| Exit Lights |
Y |
| Jumbo Exit Lights |
Y |
| Surface Mount Emergency Lights |
Y |
| 2 by 36w Emergency Battens |
Y |
|
|---|
| Are there any Warranty items needing to be repaired? | No |
|---|
| LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
| Exit Light #7 |
Warehouse |
1 |
Failed 90min Test |
Y |
N |
N |
- |
| Surface Mount Twin Tube Emergency Batten #12 |
Warehouse |
1 |
Failed 90min Test |
Y |
N |
N |
Replaced with Surface Mount Emergency Light |
| Surface Mount Twin Tube Emergency Batten #15 |
Warehouse |
1 |
Failed 90min Test |
Y |
N |
N |
Replaced with Surface Mount Emergency Light |
| Surface Mount Twin Tube Emergency Batten #16 |
Warehouse |
1 |
Failed 90min Test |
Y |
N |
N |
Replaced with Surface Mount Emergency Light |
| Surface Mount Twin Tube Emergency Batten #20 |
Warehouse |
1 |
Failed 90min Test |
Y |
N |
N |
Replaced with Surface Mount Emergency Light |
|
|---|
| Site Status Selector | Store now fully compliant |
|---|
| Next Test Due in 6 months | 24/12/2025 |
|---|
| |
|---|
| |