Carry out push button test and record the results below.
RCD Details (Initial/12 Months)
Distribution Board No.
Circuit No.
Push Button (YorN)
Pass / Fail (PorF)
Fault?
Repaired on Site (YorN)
DSBM5-A
1
Y
P
3
Y
P
5
Y
P
6
Y
P
8
Y
P
10
Y
P
17
Y
P
19
Y
P
20
Y
P
21
Y
P
22
Y
P
23
Y
P
24
Y
P
25
Y
P
26
Y
P
27
Y
P
28
Y
P
29
Y
P
30
Y
P
31
Y
P
32
Y
P
33
Y
P
34
Y
P
35
Y
P
36
Y
P
37
Y
P
38
Y
P
39
Y
P
40
Y
P
41
Y
P
42
Y
P
43
Y
P
44
Y
P
45
Y
P
46
Y
P
47
Y
P
48
Y
P
49
Y
P
50
Y
P
51
Y
P
52
Y
P
53
Y
P
54
Y
P
55
Y
P
56
Y
P
57
Y
P
58
Y
P
59
Y
P
60
Y
P
61
Y
P
62
Y
P
63
Y
P
64
Y
P
65
Y
P
66
Y
P
67
Y
P
68
Y
P
69
Y
P
70
Y
P
71
Y
P
72
Y
P
DSBM5-B
1
Y
P
2
Y
P
3
Y
P
4
Y
P
5
Y
P
6
Y
P
7
Y
P
8
Y
P
9
Y
P
10
Y
P
11
Y
P
12
Y
P
13
Y
P
14
Y
P
15
Y
P
16
Y
P
17
Y
P
18
Y
P
19
Y
P
20
Y
P
21
Y
P
22
Y
P
23
Y
P
24
Y
P
25
Y
P
26
Y
P
27
Y
P
28
Y
P
29
Y
P
30
Y
P
31
Y
P
32
Y
P
33
Y
P
34
Y
P
35
Y
P
36
Y
P
37
Y
P
38
Y
P
39
Y
P
40
Y
P
41
Y
P
42
Y
P
43
Y
P
44
Y
P
45
Y
P
46
Y
P
47
Y
P
48
Y
P
50
Y
P
64
Y
P
DBM5/1
2
Y
P
7
Y
P
9
Y
P
10
Y
P
11
Y
P
12
Y
P
13
Y
P
14
Y
P
15
Y
P
16
Y
P
17
Y
P
18
Y
P
19
Y
P
21
Y
P
22
Y
P
23
Y
P
24
Y
P
25
Y
P
26
Y
P
27
Y
P
28
Y
P
29
Y
P
30
Y
P
31
Y
P
32
Y
P
33
Y
P
34
Y
P
35
Y
P
36
Y
P
37
Y
P
38
Y
P
39
Y
P
40
Y
P
41
Y
P
42
Y
P
44
Y
P
46
Y
P
48
Y
P
50
Y
P
52
Y
P
61
Y
P
63
Y
P
65
Y
P
68
Y
P
70
Y
P
72
Y
P
THERMOGRAPHIC TEST RESULTS
THERMOGRAPHIC TEST RESULTS
SF43 Exit/Emergency
SF43 EXIT/EMERGENCY LIGHTING
Exit/Emergency Light Checklist
Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
Check timers for correct operation and timing
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No.
ID No.
Surface mounted or recessed? (SorR)
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
DSB M5
1
S
Y
Y
Y
P
2
S
Y
Y
Y
P
3
S
Y
Y
Y
P
4
S
Y
Y
Y
P
5
S
Y
Y
Y
P
6
S
Y
Y
Y
P
7
S
Y
Y
Y
P
8
S
Y
Y
Y
P
9
S
Y
Y
Y
P
10
S
Y
Y
Y
P
11
S
Y
Y
Y
P
12
S
Y
Y
Y
P
13
R
Y
Y
Y
P
14
R
Y
Y
Y
P
15
S
Y
Y
Y
P
16
S
Y
Y
Y
P
17
R
Y
Y
Y
P
18
R
Y
Y
Y
P
19
R
Y
Y
Y
P
20
R
Y
Y
Y
P
21
R
Y
Y
Y
P
22
R
Y
Y
Y
P
23
R
Y
Y
Y
P
24
R
Y
Y
Y
P
25
R
Y
Y
Y
P
26
R
Y
Y
Y
P
27
R
Y
Y
Y
P
28
R
Y
Y
Y
P
29
R
Y
Y
Y
P
30
R
Y
Y
Y
P
31
R
Y
Y
Y
P
32
R
Y
Y
Y
P
33
R
Y
Y
Y
P
HTML Block
EXIT LIGHTS
Distribution Board No.
ID No.
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
DSB M5
1
Y
Y
Y
P
2
Y
Y
Y
P
3
Y
Y
Y
P
4
Y
Y
Y
P
5
Y
Y
Y
P
6
Y
Y
Y
P
7
Y
Y
Y
P
8
Y
Y
Y
P
9
Y
Y
Y
P
10
Y
Y
Y
P
11
Y
Y
Y
P
12
Y
Y
Y
P
13
Y
Y
Y
P
14
Y
Y
Y
P
15
N
N
N
F
Failed 90 min discharge test
Y
N
16
Y
Y
Y
P
17
Y
Y
Y
P
18
Y
Y
Y
P
19
Y
Y
Y
P
20
Y
Y
Y
P
21
Y
Y
Y
P
SF44 General Lighting & Works
SF44 GENERAL LIGHTING & WORKS
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
HTML Block
General Operation/Additional items
Check with Store Manager to ensure there are no other issues
Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au
Yes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten)
Existing (YorN)
90mm LED Downlights
Y
70mm LED Downlights
Y
300W Mercury Hi-Bay Lights
Y
250W Metal Halide Hi-Bay Lights
Y
36W Single Fluorescent Batten Lights
Y
36W Double Diffused Fluorescent Batten Lights
Y
36W Single Diffused Fluorescent Batten Lights
Y
Recessed Emergency Lights
Y
Clevertronics Ceiling Mount Exit Lights
Y
Clevertronics Wall Mount Exit Lights
Y
LED Hi-Bay Light Fitting (Store Room)
Y
Are there any Warranty items needing to be repaired?
No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
Timer TC2
DSBM5/A
1
Timer controlling front entry batten holders is faulty. Replacement is required. Temporarily bypassed time clock to illuminate front batten holders. When reconnecting connect core #80 (blue) into timer to control batten holders and external lighting.
N
Y
Y
Order new time clock and return before trade for 1hr to replace
Main switch
DSBM5/A
1
Cover missing
N
Y
Y
Photo of main switch with details attached. Orde new terminal cover for line side. Return for 0.5hrs to replace
External halogen lights
External front bulk head
1
Circuit is in a dead short. Further investigation re1uired 2ith 2 x technicians.
N
Y
Y
Investigate further when returning to complete other repairs.
High bay
Tv, home security , coffee, fridges
4
Failed to illuminate
N
Y
Y
Return to site with scissor and replace. Ceiling height is 6.9m4 x 2m black piggytail extension lead required for replacement. Deliver scissor to boh loading dock. 2 x technicians required for 1.5hrs
Downlight
Tv
1
Failed to illuminate
Y
N
N
Replaced
Exit #15
Boh
1
Failed 90 min discharge test
Y
N
N
Replaced
Test & tag
Store
60+
Tested 28.01.25 due 28.01.26
-
-
-
-
Next Test Due in 6 months
16/03/2026
The Built Services Group seeks to apply innovation and technology for greater client services, business efficiencies and thinking Green.